2019-01-04 18:03:29 | ****CORRECTIONS**** |
| ****REVISED 1/12/19*** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. RAS 117 CALCULATIONS WERE SUBMITTED, BUT ARE |
| DESIGNED TO THE WRONG WIND SPEED, SEE MASTER PERMIT |
| (170 RATHER THAN 180). A ROOF SUB PERMIT WAS SUBMITTED; |
| CAN THIS DOCUMENT BE DELETED? |
| |
| 2. COMMENT FROM FIRST REVIEW: FBC 107, AN INDEX PAGE IS |
| SUGGESTED. NOTE THAT, WITHOUT AN INDEX, IT IS VERY |
| DIFFICULT TO FIND INFORMATION. FOR INSTANCE, LS001 |
| WHICH INCLUDES INFORMATION NEEDED FOR REVIEW OF ALL |
| OTHER SHEETS, IS AT THE END OF THE FILE DUE TO THE WAY |
| THAT IT WAS NAMED; THIS IS TYPICALLY IN THE BEGINNING |
| OR RIGHT AFTER CIVILS. |
| |
| 2ND REVIEW - DOCUMENT "101 - GI1000, 102 - GI1001", |
| ETC. WERE UPLOADED. AS THE OTHER DOCUMENTS ARE A ZERO |
| SERIES (001, 052, 060, ETC.) THE INDEX APPEARS AT THE |
| END OF THE DOCUMENT. SINCE THE PURPOSE WAS TO MAKE THE |
| PLAN EASIER TO REVIEW AND TO FIND INFORMATION, PLEASE |
| RENAME SO IT APPEARS BEFORE THE OTHER SHEETS RATHER |
| THAN AT THE END. |
| |
| 3-4. OK |
| |
| 4. COMMENT FROM FIRST REVIEW: DA121, FBC B 1017, SECOND |
| TIER LEVEL, EXITING FOR THE STORAGE AREAS IS NOT CLEAR. |
| REVISE PLAN TO SHOW EXIT ACCESS TRAVEL DISTANCE. |
| |
| 2ND REVIEW, LS003A & DA131, 209'4" AND 212' ARE NOTED |
| AS THE TRAVEL DISTANCE BUT THE LOCATION OF THE EXIT IS |
| NOT CLEAR. THE PATH OF EGRESS SHOWN ON THE PLAN APPEARS |
| TO END IN THE MIDDLE OF AN OPEN STAIR. CLARIFY EXIT |
| LOCATION AND TRAVEL DISTANCE. LS003A DOES NOT APPEAR TO |
| SHOW THE EXIT. IF THIS IS COVERED UNDER AN EXCEPTION, |
| PLEASE REVISE PLAN TO INCLUDE. |
| |
| 5. COMMENT FROM FIRST REVIEW: DA131, FBC B 1017, THIRD |
| TIER LEVEL, EXITING FOR THE STORAGE AREAS IS NOT CLEAR. |
| REVISE PLAN TO SHOW EXIT ACCESS TRAVEL DISTANCE. |
| |
| 2ND REVIEW, LS003A, DA131, 209'4" AND 212' ARE NOTED AS |
| THE TRAVEL DISTANCES. THIS IS THE SAME AS 2ND FLOOR BUT |
| BOTH APPEAR TO TRAVEL THROUGH AN UNPROTECTED STAIR, NOT |
| CLEAR WHERE 209'4" ENDS FOR EACH STAIR. IF 209'4" IS |
| THE DISTANCE FROM 2ND FLOOR STORAGE ROOM TO AN EXIT, |
| AND 3RD FLOOR USES THE SAME TRAVEL PATH BUT IS ONE |
| FLOOR HIGHER, IT APPEARS THAT THE 3RD FLOOR NUMBER |
| SHOULD BE A LARGER NUMBER. |
| |
| 6-7. OK |
| |
| 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS, |
| DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR, |
| FAC61G15. |
| |
| 2ND REVIEW, RESPONSE LETTER STATES TO REFER TO REVIEW |
| LETTER; UNABLE TO LOCATE. PLEASE PROVIDE OR ADVISE AS |
| TO FILE NAME. |
| |
| 9. OK |
| |
| NEW COMMENT: |
| |
| 10. PER OUR DISCUSSION - SUBMIT THE DELEGATED |
| ENGINEERING AND ENGINEERED SHOP DRAWINGS AS A |
| SUBMITTAL. SUBMIT THE MISSING PAGE DS502 AS A REVISION |
| TO 18060764. IT IS MY UNDERSTANDING THAT THIS IS IN |
| PROGRESS (PENDING CITY STAFF GENERATING A PROJECTDOX |
| SUBMITTAL AND INVIDATION TO UPLOAD). |
| |
| 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISOS: |
| |
| A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE. |
| |
| B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| |
| |