Plan Review Notes
Plan Review Notes For Permit 18090957
Permit Number 18090957
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-31 12:02:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW BATHROOM FIXTURE COUNT SHALL COMPLY WITH FBC
 PL 403.1.3 POTTY PARITY. IN ASSEMBLY OCCUPANCIES,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS AND URINALS PROVIDED
 FOR MEN, UNLESS THESE ARE TWO OR FEWER SUCH FIXTURES
 FOR MEN, IN ACCORDANCE WITH ?553.86, FLORIDA STATUTES.
  
 2. THE GRAB BARS SHALL SHOWN TO BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISHED FLOOR . PER FBC
 ACC 609.4
  
 3. PLEASE SHOW COMPLIANCE OF THE AMBULATORY STALL PER
 FBC ACC 604.8.2.1 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.
 604.8.2.2 DOORS. TOILET COMPARTMENT DOORS, INCLUDING
 DOOR HARDWARE, SHALL COMPLY WITH 404, EXCEPT THAT IF
 THE APPROACH IS TO THE LATCH SIDE OF THE COMPARTMENT
 DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF THE
 COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. THE DOOR SHALL BE SELF-CLOSING. A
 DOOR PULL COMPLYING WITH 404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
 604.8.2.3 GRAB BARS. GRAB BARS SHALL COMPLY WITH 609. A
 SIDE-WALL GRAB BAR COMPLYING WITH 604.5.1 SHALL BE
 PROVIDED ON BOTH SIDES OF THE COMPARTMENT.
  
 4.PLEASE ENLARGE THE ISOMETRIC DRAWING FOR THE WATER
 SANITARY AND STORM DRAIN THEY ARE TO CONGESTED TO
 DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC
 107.2.1.3
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  