2018-10-29 11:13:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090957
 10/29/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET DM201: REFER TO SECTION 1101.1 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) DM202: A) SEE NOTES M09 AND M11 AND CLARIFY THE TYPE
 OF EXHAUST THAT IS BEING EXTENDED TO THE NEW
 TERMINATION LOCATION. B) SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND THE MIAMI-DADE NOA FOR THE EXHAUST
 AND OUTSIDE AIR LOUVERS. C) DUCT SMOKE DETECTORS ARE
 REQUIRED FOR THE NEW FAN COIL UNITS IF THESE UNITS ARE
 SHARING THE COMMON OUTDOOR AIR SUPPLY OR COMMON PLENUM-
 SECTION 606.2.2 FBC M. C) PLACE A NOTE TO INDICATING
 THAT NO MORE THAN 10% OF AIR SUPPLIED INTO THE TOILET
 ROOMS WILL BE RECIRCULATED VIA RETURNS INTO THE PLENUM
 OR TO ADJACENT SPACES- TABLE 403.3.1.1 FOOTNOTE G. D)
 PROVIDE NOTES INDICATING THE LOCATION OF THE RISERS
 INTO THE UPPER LEVELS.
  
 3) DM204, 206, 208, 210, 212: THE PLANS SHOW NUMEROUS
 DUCT RISERS PENETRATING FLOORS AND ALSO WHAT APPEARS TO
 BE CHASES OR SHAFT. PLEASE SHOW THE REQUIRED FIRE
 DAMPERS AT THESE LOCATIONS- SECTIONS 607.5.2, 607.5.5,
 & 607.6 FBC M.
  
 4) DM302: PROVIDE A DUCT PENETRATION FIRESTOPPING
 DETAIL- SECTION 714.1.1 FBC B.
  
 5) DM401: PROVIDE A SEQUENCE OF OPERATION FOR FAN SHUT
 DOWN RELATING TO ACTIVATION OF AN AREA OR DUCT SMOKE
 DETECTOR- SECTIONS 606.4 AND 606.4.1 FBC M.
  
 6) DM212: CLARIFY IF THE STAIRWELL WALL THAT THE DUCT
 IS PENETRATING IS A WALL THAT IS ENCLOSING AN INTERIOR
 EXIT STAIRWAY- SEESECTION 1023.5 FBC B.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  