2018-10-29 11:13:27 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090957 |
| 10/29/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET DM201: REFER TO SECTION 1101.1 FBC-17 EXISTING |
| BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE |
| 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT |
| INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR |
| AIR. |
| |
| 2) DM202: A) SEE NOTES M09 AND M11 AND CLARIFY THE TYPE |
| OF EXHAUST THAT IS BEING EXTENDED TO THE NEW |
| TERMINATION LOCATION. B) SUBMIT MANUFACTURER'S |
| SPECIFICATIONS AND THE MIAMI-DADE NOA FOR THE EXHAUST |
| AND OUTSIDE AIR LOUVERS. C) DUCT SMOKE DETECTORS ARE |
| REQUIRED FOR THE NEW FAN COIL UNITS IF THESE UNITS ARE |
| SHARING THE COMMON OUTDOOR AIR SUPPLY OR COMMON PLENUM- |
| SECTION 606.2.2 FBC M. C) PLACE A NOTE TO INDICATING |
| THAT NO MORE THAN 10% OF AIR SUPPLIED INTO THE TOILET |
| ROOMS WILL BE RECIRCULATED VIA RETURNS INTO THE PLENUM |
| OR TO ADJACENT SPACES- TABLE 403.3.1.1 FOOTNOTE G. D) |
| PROVIDE NOTES INDICATING THE LOCATION OF THE RISERS |
| INTO THE UPPER LEVELS. |
| |
| 3) DM204, 206, 208, 210, 212: THE PLANS SHOW NUMEROUS |
| DUCT RISERS PENETRATING FLOORS AND ALSO WHAT APPEARS TO |
| BE CHASES OR SHAFT. PLEASE SHOW THE REQUIRED FIRE |
| DAMPERS AT THESE LOCATIONS- SECTIONS 607.5.2, 607.5.5, |
| & 607.6 FBC M. |
| |
| 4) DM302: PROVIDE A DUCT PENETRATION FIRESTOPPING |
| DETAIL- SECTION 714.1.1 FBC B. |
| |
| 5) DM401: PROVIDE A SEQUENCE OF OPERATION FOR FAN SHUT |
| DOWN RELATING TO ACTIVATION OF AN AREA OR DUCT SMOKE |
| DETECTOR- SECTIONS 606.4 AND 606.4.1 FBC M. |
| |
| 6) DM212: CLARIFY IF THE STAIRWELL WALL THAT THE DUCT |
| IS PENETRATING IS A WALL THAT IS ENCLOSING AN INTERIOR |
| EXIT STAIRWAY- SEESECTION 1023.5 FBC B. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |