2018-10-15 10:23:27 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE COMPLETED LIGHT FIXTURE SCHEDULE. WPB FBC |
| 107.2.1 |
| 2. IT APPEARS LOAD IS BEING ADDED TO PANEL SEBB AND |
| SWBB FOR THE NEW PANELS. PROVIDE LOAD CALCULATION FOR |
| THESE PANELS, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| CAPACITY IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |