2018-11-02 16:34:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ROOF PRODUCT APPROVAL WAS SUBMITTED; FBC 107 PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE CITY. NOTE THAT THE ASSEMBLY
 DOES NOT MEET THE DESIGN PRESSURES FOR ZONES 2 & 3, SO
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 THIS CAN BE ADDRESSED AT THIS TIME OR WILL BE A PROVISO
 ITEM, SUBMIT WITH ROOF PERMIT APPLICATION, REVIEW
 REQUIRED AT THAT TIME.
  
 2. FBC 107, AN INDEX PAGE IS SUGGESTED. NOTE THAT,
 WITHOUT AN INDEX, IT IS VERY DIFFICULT TO FIND
 INFORMATION. FOR INSTANCE, LS001 WHICH INCLUDES
 INFORMATION NEEDED FOR REVIEW OF ALL OTHER SHEETS, IS
 AT THE END OF THE FILE DUE TO THE WAY THAT IT WAS
 NAMED; THIS IS TYPICALLY IN THE BEGINNING OR RIGHT
 AFTER CIVILS.
  
 3. LS001, LS002, A TEMPORARY LIFE SAFETY PLAN WAS
 PROVIDED FOR TWO LEVELS. PROVIDE A LIFE SAFETY PLAN FOR
 FINISHED CONSTRUCTION, FBC B CHAPTER 10. THIS SHOULD
 INCLUDE THE NEW OCCUPANT LOAD FBC B 1004.
  
 4. LS001, NOTES FOR 508, 508.4 ARE NOT CLEAR AS TO
 DESIGN INTENT AND WHICH NOTE IS APPLICABLE TO THE
 STORAGE AREAS. I COULD NOT FIND OCCUPANCY
 CLASSIFICATION FOR THE STORAGE AREAS; REVISE TO
 INCLUDE. IT APPEARS THAT THE STORAGE MAY BE S2, WHICH
 PER THE NOTE 508.4, SEPARATION IS REQUIRED.
  
 4. DA121, FBC B 1017, SECOND TIER LEVEL, EXITING FOR
 THE STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW
 EXIT ACCESS TRAVEL DISTANCE.
  
 5. DA131, FBC B 1017, THIRD TIER LEVEL, EXITING FOR THE
 STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW EXIT
 ACCESS TRAVEL DISTANCE.
  
 6. LS001, REVISE DESCRIPTION OF WORK TO INCLUDE THE 2ND
 AND 3RD TIER STORAGE AREAS, FBC 107.
  
 7. DA121, FBC B 713, 2 HR FIRE RATED CHASE IS SHOWN;
 REVISE PLAN TO INDICATE WHICH ASSEMBLY IS PROPOSED.
  
 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS,
 DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR,
 FAC61G15.
  
 9. PROVIDE A SITE PLAN SHOWING COMPLIANCE WITH FBC B
 TABLES 602, 705.8.
  
 10. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE.
  
 B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
  