2018-11-02 16:34:04 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. ROOF PRODUCT APPROVAL WAS SUBMITTED; FBC 107 PRODUCT |
| APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL TO THE CITY. NOTE THAT THE ASSEMBLY |
| DOES NOT MEET THE DESIGN PRESSURES FOR ZONES 2 & 3, SO |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| THIS CAN BE ADDRESSED AT THIS TIME OR WILL BE A PROVISO |
| ITEM, SUBMIT WITH ROOF PERMIT APPLICATION, REVIEW |
| REQUIRED AT THAT TIME. |
| |
| 2. FBC 107, AN INDEX PAGE IS SUGGESTED. NOTE THAT, |
| WITHOUT AN INDEX, IT IS VERY DIFFICULT TO FIND |
| INFORMATION. FOR INSTANCE, LS001 WHICH INCLUDES |
| INFORMATION NEEDED FOR REVIEW OF ALL OTHER SHEETS, IS |
| AT THE END OF THE FILE DUE TO THE WAY THAT IT WAS |
| NAMED; THIS IS TYPICALLY IN THE BEGINNING OR RIGHT |
| AFTER CIVILS. |
| |
| 3. LS001, LS002, A TEMPORARY LIFE SAFETY PLAN WAS |
| PROVIDED FOR TWO LEVELS. PROVIDE A LIFE SAFETY PLAN FOR |
| FINISHED CONSTRUCTION, FBC B CHAPTER 10. THIS SHOULD |
| INCLUDE THE NEW OCCUPANT LOAD FBC B 1004. |
| |
| 4. LS001, NOTES FOR 508, 508.4 ARE NOT CLEAR AS TO |
| DESIGN INTENT AND WHICH NOTE IS APPLICABLE TO THE |
| STORAGE AREAS. I COULD NOT FIND OCCUPANCY |
| CLASSIFICATION FOR THE STORAGE AREAS; REVISE TO |
| INCLUDE. IT APPEARS THAT THE STORAGE MAY BE S2, WHICH |
| PER THE NOTE 508.4, SEPARATION IS REQUIRED. |
| |
| 4. DA121, FBC B 1017, SECOND TIER LEVEL, EXITING FOR |
| THE STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW |
| EXIT ACCESS TRAVEL DISTANCE. |
| |
| 5. DA131, FBC B 1017, THIRD TIER LEVEL, EXITING FOR THE |
| STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW EXIT |
| ACCESS TRAVEL DISTANCE. |
| |
| 6. LS001, REVISE DESCRIPTION OF WORK TO INCLUDE THE 2ND |
| AND 3RD TIER STORAGE AREAS, FBC 107. |
| |
| 7. DA121, FBC B 713, 2 HR FIRE RATED CHASE IS SHOWN; |
| REVISE PLAN TO INDICATE WHICH ASSEMBLY IS PROPOSED. |
| |
| 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS, |
| DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR, |
| FAC61G15. |
| |
| 9. PROVIDE A SITE PLAN SHOWING COMPLIANCE WITH FBC B |
| TABLES 602, 705.8. |
| |
| 10. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISOS: |
| |
| A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO |
| INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH |
| PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND |
| ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE. |
| |
| B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| |
| |