2018-10-05 14:06:34 | 1ST REVIEW FBC-2017 MECHANICAL |
| REVISION #18090893 |
| 10/5/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| CLOTHES DRYERS INCLUDING INSTALLATION INSTRUCTIONS FOR |
| THE DRYER EXHAUST- SEE SECTIONS 504.1 AND 504.8.4.2 FBC |
| M. |
| |
| 2) SHEET M2.1: PROVIDE DRYER EXHAUST DUCT DIAGRAMS |
| INDICATING THE TOTAL RUN LENGTHS OF THE DUCTS FROM THE |
| EXHAUST OUTLETS TO THE TERMINATION LOCATIONS. |
| |
| 3) M2.1: INDICATE HOW MAKE UP AIR IS BEING PROVIDED FOR |
| THE DRYERS AND PROVIDE AN AIR BALANCE CALCULATION FOR |
| THE ROOM. |
| |
| 4) M2.1: PLEASE LABEL THE O/A INTAKE AND EXHAUST OUTLET |
| FOR THE ERV AND VERIFY COMPLIANCE WITH REQUIRED |
| CLEARANCE DISTANCES AS REQUIRED BY SECTION 401.4(1-4) |
| AND 501.3.1(3) FBC M |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |