Plan Review Notes
Plan Review Notes For Permit 18090893
Permit Number 18090893
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-05 14:06:341ST REVIEW FBC-2017 MECHANICAL
 REVISION #18090893
 10/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 CLOTHES DRYERS INCLUDING INSTALLATION INSTRUCTIONS FOR
 THE DRYER EXHAUST- SEE SECTIONS 504.1 AND 504.8.4.2 FBC
 M.
  
 2) SHEET M2.1: PROVIDE DRYER EXHAUST DUCT DIAGRAMS
 INDICATING THE TOTAL RUN LENGTHS OF THE DUCTS FROM THE
 EXHAUST OUTLETS TO THE TERMINATION LOCATIONS.
  
 3) M2.1: INDICATE HOW MAKE UP AIR IS BEING PROVIDED FOR
 THE DRYERS AND PROVIDE AN AIR BALANCE CALCULATION FOR
 THE ROOM.
  
 4) M2.1: PLEASE LABEL THE O/A INTAKE AND EXHAUST OUTLET
 FOR THE ERV AND VERIFY COMPLIANCE WITH REQUIRED
 CLEARANCE DISTANCES AS REQUIRED BY SECTION 401.4(1-4)
 AND 501.3.1(3) FBC M
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved