2018-10-05 12:19:07 | 1ST REVIEW FBC-2017 MECHANICAL |
| REVISION #18090878 |
| 10/5/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE INSTALLATION OF THE NEW COMPESSOR ROOM |
| CONSTITUTES AN INCREASE IN VALUE, THE AMOUNT OF WHICH |
| NEEDS TO BE LISTED ON THE REVISION APPLICATION SO |
| APPROPRIATE PERMITTING AND INSPECTION FEES CAN BE |
| APPLIED- SECTION 109.3 WPB. PLEASE NOTE THAT THE VALUE |
| IS BASED ON LABOR, MATERIALS, EQUIPMENT, SITE WORK, |
| DESIGN FEES, AND OVERHEAD AND PROFIT. PLEASE PROVIDE |
| DETAILED ESTIMATES OR BONA FIDE CONTRACTS FOR ALL |
| PHASES OF THE PROJECT. |
| |
| 2) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE COMPRESSOR- SECTION |
| 304.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |