Plan Review Notes
Plan Review Notes For Permit 18090868
Permit Number 18090868
Review Stop P
Sequence Number 4
Notes
Date Text
2019-06-12 12:16:30P.E (MARTHA MCNICHOLAS) CALLEDL TODAY 6/12/19 ASKING
 FOR COMMENTS AS SHE HAS NOT SEEN ANY COMMENTS FROM THE
 2-4 REVIEW.EMAILED TO HER @ 12:15 A COPY OF THE 4TH
 REVIEW COMMENTS.
2019-06-11 16:08:54PLUMBING 4TH REVIEW**DENIED**A 4X PLAN REVIEW FEE HAS
 BEEN ADDED AS COMMENTS HAVE NOT BEEN ADDRESSED AND PLAN
 CHANGES EACH SUBMITTAL WILL CONTINUE TO CAUSE NEW
 COMMENTS PER F.S 553.80 (2) (B). PLEASE HAVE THE DESIGN
 PROFESSIONAL COME IN FOR A MEETING BEFORE RESUBMITTING.
 ERIC FROM BUILD PRO WAS CONTACTED AND ADVISED OF ISSUES
 AND ACKNOWLEDGE OF LAST PLAN REVIEWERS COMMENTS
 REQUESTING A MEETING BUT DUE TO DESIGN PROFESSIONALS
 SCHEDULE SHE WAS NOT ABLE TO COME IN. HE ADVISED HE
 WOULD HAVE DESIGN PROFESSIONAL CALL ME DIRECTLY WHICH
 AS OF 4:03 PM SHE HAS NOT NOR ANSWERED MY PHONE CALL.
  
 1) 4TH REQUEST. PROVIDE A CODE COMPLYING SANITARY
 ISOMETRIC DRAWING. (A) THE WATER CLOSET FIXTURE DRAIN
 NEEDS TO BE SIZED, SHOW A HORIZONTAL TO VERTICAL
 DISCHARGE PIPE WITH NO P-TRAP. (B) KITCHEN DRAIN SHALL
 NOT CONNECT INTO THE BATHROOM GROUP. KITCHEN LINE SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM GROUP WET VENT.
 FBC-R P3108.1(C) CLOTHS WASHER FIXTURE DRAIN SHALL BE
 VENTED. FBC-R P 3101.2
  
 2) 3RD REQUEST. PROVIDE HAMMER ARRESTORS FOR THE CLOTHS
 WASHER. FBC-R P 2903.5
  
 3) 3RD REQUEST. IS THE CLOTHS WASHER OUTSIDE? SHOW THAT
 IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE
 DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. FBC
 107.2.1
  
 4) PROVIDE WATER HEATER INSTALLATION MANUAL AS THE
 HEATER IS NOW SHOWING STORAGE TYPE. PROVIDE WATER
 PIPING DETAIL SHOWING DISCHARGE OF RELIEF LINE INTO THE
 ROOM IT SERVES AND PAN DRAIN LINE SHOWING IT DISCHARGES
 TO THE OUTSIDE. FBC-R P 2108.1, 2804
  
 NEW COMMENTS:
 5)PLUMBING PERMIT CALL OUT 2 BATHROOMS BOTH PLAN IS
 CURRENTLY ONLY SHOWING 1. PLEASE CLARIFY AND CHANGE
 SCOPE OF WORK ON PERMIT APPLICATION. FBC 107.2.1
  
 6)PER ERIC (GC) IT IS YOUR INTENTION TO 100% COMPLY
 WITH 2017 FLORIDA ACCESSIBILITY. IT SO PLEASE ADDRESS
 THE FOLLOWING COMMENTS OTHERWISE REMOVE ALL ADA ITEMS
 FROM PLAN AS I WILL NOT PUT MY SIGNATURE ON A PLAN THAT
 DOES NOT SHOW CODE COMPLIANT ACCESSIBILITY.
 1. SHOW ON ALL SHEETS THE MIN SIZE PERMITTED FOR THE
 SHOWER ALT ROLL IN AS 36? X 60. SHT A-1 DETAIL SHOWS 2?
 9? SEE FBC-ACC 608.2.3
 2. GRAB BARS SHALL BE 33?-36? TO THE TOP OF THE
 GRIPPING SURFACE AND NOT THE CENTER OF THE BAR. FBC-ACC
 608.4
 3. SHOW WASHING MACHINE AS COMPLYING WITH FBC-ACC 611.
 CLEAR FLOOR SPACE, OPERABLE PARTS HEIGHT, ETC
 4. PROVIDE CLEAR FLOOR SPACE FOR THE ALT ROLL IN
 SHOWER. FBC-ACC 608.2.2.1
 5. PROVIDE KITCHEN DETAIL TO INCLUDE CLEAR FLOOR SPACE,
 COUNTER TOP HEIGHT, AND TUNING SPACE. FBC-ACC 606.2,
 606.3
 6. MIRROR SHALL BE MAX 40? TO THE BOTTOM OF THE
 REFLECTIVE SURFACE. YOU CALL OUT 3? 6? (42?) ON DETAIL
 #6 SHT. A-2. FBC-ACC 603.3
 7. LIST 2017 FLORIDA ACCESSIBILITY CODE AS APPLICABLE
 CODE ON SHT. A-1
  
 7) VALUE APPEARS LOW AND HAS BEEN ADDRESSED BY OTHER
 PLAN REVIEWERS BUT NO SUPPORTING DOCUMENTATION HAS BEEN
 PROVIDE. PROVIDE A SIGNED BONA FIDE CONTRACT FOR THE
 ENTIRE JOB. WPB AMEND 109.3
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
  