2019-06-12 12:16:30 | P.E (MARTHA MCNICHOLAS) CALLEDL TODAY 6/12/19 ASKING |
| FOR COMMENTS AS SHE HAS NOT SEEN ANY COMMENTS FROM THE |
| 2-4 REVIEW.EMAILED TO HER @ 12:15 A COPY OF THE 4TH |
| REVIEW COMMENTS. |
2019-06-11 16:08:54 | PLUMBING 4TH REVIEW**DENIED**A 4X PLAN REVIEW FEE HAS |
| BEEN ADDED AS COMMENTS HAVE NOT BEEN ADDRESSED AND PLAN |
| CHANGES EACH SUBMITTAL WILL CONTINUE TO CAUSE NEW |
| COMMENTS PER F.S 553.80 (2) (B). PLEASE HAVE THE DESIGN |
| PROFESSIONAL COME IN FOR A MEETING BEFORE RESUBMITTING. |
| ERIC FROM BUILD PRO WAS CONTACTED AND ADVISED OF ISSUES |
| AND ACKNOWLEDGE OF LAST PLAN REVIEWERS COMMENTS |
| REQUESTING A MEETING BUT DUE TO DESIGN PROFESSIONALS |
| SCHEDULE SHE WAS NOT ABLE TO COME IN. HE ADVISED HE |
| WOULD HAVE DESIGN PROFESSIONAL CALL ME DIRECTLY WHICH |
| AS OF 4:03 PM SHE HAS NOT NOR ANSWERED MY PHONE CALL. |
| |
| 1) 4TH REQUEST. PROVIDE A CODE COMPLYING SANITARY |
| ISOMETRIC DRAWING. (A) THE WATER CLOSET FIXTURE DRAIN |
| NEEDS TO BE SIZED, SHOW A HORIZONTAL TO VERTICAL |
| DISCHARGE PIPE WITH NO P-TRAP. (B) KITCHEN DRAIN SHALL |
| NOT CONNECT INTO THE BATHROOM GROUP. KITCHEN LINE SHALL |
| CONNECT DOWNSTREAM OF THE BATHROOM GROUP WET VENT. |
| FBC-R P3108.1(C) CLOTHS WASHER FIXTURE DRAIN SHALL BE |
| VENTED. FBC-R P 3101.2 |
| |
| 2) 3RD REQUEST. PROVIDE HAMMER ARRESTORS FOR THE CLOTHS |
| WASHER. FBC-R P 2903.5 |
| |
| 3) 3RD REQUEST. IS THE CLOTHS WASHER OUTSIDE? SHOW THAT |
| IT IS PROTECTED FROM THE ELEMENTS OR PROVIDE |
| DOCUMENTATION THAT IT IS SUITABLE FOR OUTDOOR USE. FBC |
| 107.2.1 |
| |
| 4) PROVIDE WATER HEATER INSTALLATION MANUAL AS THE |
| HEATER IS NOW SHOWING STORAGE TYPE. PROVIDE WATER |
| PIPING DETAIL SHOWING DISCHARGE OF RELIEF LINE INTO THE |
| ROOM IT SERVES AND PAN DRAIN LINE SHOWING IT DISCHARGES |
| TO THE OUTSIDE. FBC-R P 2108.1, 2804 |
| |
| NEW COMMENTS: |
| 5)PLUMBING PERMIT CALL OUT 2 BATHROOMS BOTH PLAN IS |
| CURRENTLY ONLY SHOWING 1. PLEASE CLARIFY AND CHANGE |
| SCOPE OF WORK ON PERMIT APPLICATION. FBC 107.2.1 |
| |
| 6)PER ERIC (GC) IT IS YOUR INTENTION TO 100% COMPLY |
| WITH 2017 FLORIDA ACCESSIBILITY. IT SO PLEASE ADDRESS |
| THE FOLLOWING COMMENTS OTHERWISE REMOVE ALL ADA ITEMS |
| FROM PLAN AS I WILL NOT PUT MY SIGNATURE ON A PLAN THAT |
| DOES NOT SHOW CODE COMPLIANT ACCESSIBILITY. |
| 1. SHOW ON ALL SHEETS THE MIN SIZE PERMITTED FOR THE |
| SHOWER ALT ROLL IN AS 36? X 60. SHT A-1 DETAIL SHOWS 2? |
| 9? SEE FBC-ACC 608.2.3 |
| 2. GRAB BARS SHALL BE 33?-36? TO THE TOP OF THE |
| GRIPPING SURFACE AND NOT THE CENTER OF THE BAR. FBC-ACC |
| 608.4 |
| 3. SHOW WASHING MACHINE AS COMPLYING WITH FBC-ACC 611. |
| CLEAR FLOOR SPACE, OPERABLE PARTS HEIGHT, ETC |
| 4. PROVIDE CLEAR FLOOR SPACE FOR THE ALT ROLL IN |
| SHOWER. FBC-ACC 608.2.2.1 |
| 5. PROVIDE KITCHEN DETAIL TO INCLUDE CLEAR FLOOR SPACE, |
| COUNTER TOP HEIGHT, AND TUNING SPACE. FBC-ACC 606.2, |
| 606.3 |
| 6. MIRROR SHALL BE MAX 40? TO THE BOTTOM OF THE |
| REFLECTIVE SURFACE. YOU CALL OUT 3? 6? (42?) ON DETAIL |
| #6 SHT. A-2. FBC-ACC 603.3 |
| 7. LIST 2017 FLORIDA ACCESSIBILITY CODE AS APPLICABLE |
| CODE ON SHT. A-1 |
| |
| 7) VALUE APPEARS LOW AND HAS BEEN ADDRESSED BY OTHER |
| PLAN REVIEWERS BUT NO SUPPORTING DOCUMENTATION HAS BEEN |
| PROVIDE. PROVIDE A SIGNED BONA FIDE CONTRACT FOR THE |
| ENTIRE JOB. WPB AMEND 109.3 |
| |
| |
| |
| TIM HUNT |
| PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| BUILDING DIVISION |
| CITY OF WEST PALM BEACH |
| 401 CLEMATIS STREET, 1ST FLOOR |
| |