Text |
2018-09-26 12:58:27 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE ADDITIONAL INFORMATION | | SUPPORTING THE SUBMITTED PRODUCT APPROVAL FOR SHUTTERS. | | IT APPEARS THAT THE SPANS FOR OPENINGS # 3 AND # 5 | | EXCEED THE LIMITS FROM THE PRODUCT APPROVAL. |
|