2018-10-03 11:47:16 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| |
| PAGE E-0 |
| |
| 1) ARC FAULT NOTE #1 TO INCLUDE KITCHEN AND LAUNDRY |
| AREAS 201,12 (A), FBC RE3902.16 |
| |
| 2)RISER DIAGRAM SHOWS NO GROUNDING AT GYM BUILDING. |
| 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) |
| OR BRANCH CIRCUIT |
| A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. PROVIDE |
| DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM AND |
| WIRING. NEC 250.32; FBC RE3607.3 |
| |
| 3) LOAD CALCULATION FOR DP USES DEMANDED LOADS FROM |
| PANEL "A"? |
| PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| NEC 220; FBC RE3602.3 |
| |
| 4) PANEL "A" ON LOAD CALCULATION SHOWS 39.4 KW OF AC |
| LOAD BUT USES ONLY 16KW LOAD IN THE CALCULATION? |
| PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS. |
| NEC 220; FBC RE3602.3 |
| |
| 5) PANEL DB USES 41.4KW OF LOAD FOR PANEL "A" WHICH HAS |
| BEEN DEMANDED DOWN TO 41.4KW |
| |
| PAGE E-1 |
| |
| 6) NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS? (NOT |
| REQUIRED) |
| |
| 7) ALL AIR HANDLERS IN ATTIC NEED LIGHTING OUTLET |
| INSTALLED PER 210.70(A)(3) |
| |
| 8) GROUNDING AT GYM BUILDING TO BE PER 250.32 BUILDINGS |
| OR STRUCTURES SUPPLIED BY A FEEDER(S) OR BRANCH CIRCUIT |
| A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. |
| PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM |
| AND WIRING. NEC 250.32; FBC RE3607.3 |
| |
| 9) DISHWASHER TO BE GFCI PROTECTED PER 210.8(D)< FBC |
| RE3902.10 |
| |
| 10) OUTLET FOR WASHER IN GARAGE NOT SHOWN TO BE GFCI, |
| 210.8; FBC RE3902.2 |