2018-10-03 11:47:16FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE E-0
  
 1) ARC FAULT NOTE #1 TO INCLUDE KITCHEN AND LAUNDRY
 AREAS 201,12 (A), FBC RE3902.16
  
 2)RISER DIAGRAM SHOWS NO GROUNDING AT GYM BUILDING.
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE
 DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM AND
 WIRING. NEC 250.32; FBC RE3607.3
  
 3) LOAD CALCULATION FOR DP USES DEMANDED LOADS FROM
 PANEL "A"?
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE3602.3
  
 4) PANEL "A" ON LOAD CALCULATION SHOWS 39.4 KW OF AC
 LOAD BUT USES ONLY 16KW LOAD IN THE CALCULATION?
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE3602.3
  
 5) PANEL DB USES 41.4KW OF LOAD FOR PANEL "A" WHICH HAS
 BEEN DEMANDED DOWN TO 41.4KW
  
 PAGE E-1
  
 6) NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS? (NOT
 REQUIRED)
  
 7) ALL AIR HANDLERS IN ATTIC NEED LIGHTING OUTLET
 INSTALLED PER 210.70(A)(3)
  
 8) GROUNDING AT GYM BUILDING TO BE PER 250.32 BUILDINGS
 OR STRUCTURES SUPPLIED BY A FEEDER(S) OR BRANCH CIRCUIT
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER.
 PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM
 AND WIRING. NEC 250.32; FBC RE3607.3
  
 9) DISHWASHER TO BE GFCI PROTECTED PER 210.8(D)< FBC
 RE3902.10
  
 10) OUTLET FOR WASHER IN GARAGE NOT SHOWN TO BE GFCI,
 210.8; FBC RE3902.2