2018-11-06 12:30:39 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1-IMPACT FEES - DIGITAL SUBMITTALS |
| PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS |
| OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] |
| |
| 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| FBC R 401.3 (DRAINAGE) |
| FBC 107.2.5 (SITE PLAN) |
| FBC 110.9 (IMPACT OF CONSTRUCTION) |
| |
| SEC. R401.3 FBC_RESIDENTIAL: |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF |
| DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE |
| DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING |
| STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE |
| SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO |
| WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN |
| THE |
| APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR |
| WHEN OTHERWISE WARRANTED. |
| |
| SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS |
| OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY |
| OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE |
| CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, |
| DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW |
| CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL |
| HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| POOLS, PATIOS, DRIVEWAYS, DECKS |
| OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A |
| SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY |
| PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE |
| DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION, |
| PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A |
| LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE |
| INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL |
| INSPECTION. |
| |
| |
| 3- SURVEY: SURVEY IS NOT SIGNED AND SEALED. NEED TO |
| PROVIDE HARD COPY OF SURVEY WITH ORIGINAL SEAL AND |
| SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR SUBMIT |
| DIGITALLY SIGNED SURVEY. COORDINATE WITH CITY LIBRARIAN |
| (LAURA MARCHANT (561)805-6658 OR CAROLINE PUELL |
| (561)805-6659) FOR PROPER UPLOADING. |
| |
| 4- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED |
| FLOOR ELEVATIONS 6 AND 7. ELEVATION CERTIFICATES ARE |
| REQUIRED BASED ON CONSTRUCTION DRAWINGS, BUILDING UNDER |
| CONSTRUCTION AND FINISHED CONSTRUCTION. PROVIDE THE |
| CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE. SEC. |
| 18-284 CITY ORDINANCE NO. 4729-17. |
| |
| 5- SIZE OF ENTRY DOOR E.01 DOESN'T COMPLY WITH SEC. |
| R311.2 FBC-RESIDENTIAL. NEED DOOR THAT PROVIDE 32" MIN. |
| CLEAR OPENING. DOOR SPECIFIED IS 30" WIDTH. REVISE AS |
| REQUIRED. |
| |
| 6- CLARIFY SIZE AND CONFIGURATION OF SECOND FLOOR |
| BEDROOM CASEMENT EGRESS WINDOW (40"X57") TO VERIFY |
| COMPLIANCE WITH EGRESS SEC. R310.2.1 FBC-RESIDENTIAL. |
| IS THERE A WINDOW MULLION IN THE MIDDLE OF THE |
| WINDOWS?. IF SO, WHAT'S THE MINIMUM CLEAR WIDTH?. |
| PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THE CLEAR |
| OPENINGS TO VERIFY EGRESS. |
| |
| 7- A) FLOOR PLANS ARE INCOMPLETE. PROVIDE FLOOR PLANS |
| WITH COMPLETE DIMENSIONS. DOOR SCHEDULE DOESN'T MATCH |
| DOORS KEYED ON PLANS. REVISE AS REQUIRED AND PROVIDE |
| COMPLETE INFORMATION FOR ALL INTERIOR DOORS. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| B) SPECIFY SIZE OF BATHROOM DOORS ON FIRST FLOOR TO |
| VERIFY COMPLIANCE WITH SEC. R320 FBC-RESIDENTIAL. |
| |
| C) PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO |
| THE INTERIOR OF THE HOUSE TO COMPLY WITH SEC. R302.5.1 |
| FBC-RESIDENTIAL. |
| |
| |
| D) PROVIDE DETAILS AND SPECIFICATIONS FOR INTERIOR |
| WALLS FRAMING AND SPECIFY INSULATION BETWEEN GARAGE AND |
| MAIN HOUSE. SEC. R103.2 FBC-ENERGY CONSERVATION. |
| |
| 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION IN ALL ROOF |
| AREAS IN THE FIRST FLOOR AND SECOND FLOOR AS REQUIRED |
| BY SEC. R807 FBC-RESIDENTIAL. |
| |
| 9- PROVIDE SOIL TEST REPORT. SEC. R401.4 |
| FBC-RESIDENTIAL. |
| |
| 10- REVISE ENERGY CALCULATIONS. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. COORDINATE WITH ARCHITECTURAL |
| PLANS TO AVOID CONFLICTS/DELAYS: |
| |
| SEPARATE GYM STRUCTURE: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, CORRECT BUILDER'S NAME, PERMIT |
| OFFICE, ETC. |
| B) REVISE ITEM #4. THERE ARE NO BEDROOMS IN THE GYM. |
| C) ARCHITECTURAL PLANS DON'T SPECIFY INSULATION ON SLAB |
| ON GRADE. REVISE ITEM #8. |
| D) WALL INSULATION SPECIFIED ON ITEM #9 DOESN'T MATCH |
| PLANS. |
| E) CEILING INSULATION SPECIFIED ON ITEM #10 DOESN'T |
| MATCH ARCHITECTURAL PLANS. |
| F) THERE IS NO KITCHEN IN THE GYM. REVISE SPACES |
| INFORMATION ON PAGE 2 OF 4. |
| G) WALLS INFORMATION ON PAGE 3 OF 4 IS MISSING THE EAST |
| WALL. |
| H) REVISE DOOR INFORMATION PAGE 3 OF 4. THERE IS NOT |
| INSULATED DOOR IN THE SOUTH WALL. SEE PLANS AND PRODUCT |
| APPROVAL AND REVISE AS REQUIRED. NOTE: GLAZING IN THIS |
| DOOR NEEDS TO BE INCLUDED IN THE WINDOW GLAZING AREA. |
| SEE SEC. R405.5.3 FBC-ENERGY CONSERVATION. |
| I)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH |
| PLANS. |
| J) NEED TO PROVIDE HARD COPY OF ENERGY CALCULATIONS |
| WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER |
| 472 F. S. OR SUBMIT REPORT DIGITALLY SIGNED. COORDINATE |
| WITH CITY LIBRARIAN (LAURA MARCHANT (561)805-6658 OR |
| CAROLINE PUELL (561)805-6659) FOR PROPER UPLOADING. |
| |
| MAIN HOUSE: |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, CORRECT BUILDER'S NAME, PERMIT |
| OFFICE, ETC. |
| B) REVISE ITEM #4. NUMBER OF BEDROOMS DON'T MATCH |
| PLANS. |
| C) ARCHITECTURAL PLANS DON'T SPECIFY INSULATION ON SLAB |
| ON GRADE OR FLOOR OVER OTHER SPACE. . REVISE ITEM #8. |
| D) WALL INSULATION SPECIFIED ON ITEM #9 DOESN'T MATCH |
| PLANS AND IS MISSING THE INFORMATION FOR ADJACENT WALL |
| BETWEEN GARAGE AND MAIN HOUSE. |
| E) CEILING INSULATION SPECIFIED ON ITEM #10 DOESN'T |
| MATCH ARCHITECTURAL PLANS. |
| F) REVISE NUMBER OF PEOPLE IN THE SPACES INFORMATION ON |
| PAGE 2 OF 6. COORDINATE WITH NUMBER OF BEDROOMS SHOWN |
| ON PLANS. |
| G) REVISE DOOR INFORMATION PAGE 3 OF 6. THERE ARE NOT |
| INSULATED DOORS. SEE PLANS AND PRODUCT APPROVALS AND |
| REVISE AS REQUIRED. NOTE: GLAZING IN THIS DOORS NEEDS |
| TO BE INCLUDED IN THE WINDOW GLAZING AREA. SEE SEC. |
| R405.5.3 FBC-ENERGY CONSERVATION. |
| H)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH |
| PLANS. |
| I)NEED TO PROVIDE HARD COPY OF ENERGY CALCULATIONS WITH |
| ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 |
| F. S. OR SUBMIT REPORT DIGITALLY SIGNED. COORDINATE |
| WITH CITY LIBRARIAN (LAURA MARCHANT (561)805-6658 OR |
| CAROLINE PUELL (561)805-6659) FOR PROPER UPLOADING. |
| |
| NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| ARE NOT USING THE DEFAULT FACTOR. |
| |
| 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| |
| A) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| |
| C)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY |
| SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| WITH THE CALCULATED DESIGN PRESSURES. |
| |
| D) DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL |
| FL10765.1-R6 FOR FRENCH DOORS DON'T HAVE IMPACT GLASS. |
| THEREFORE, HURRICANE SHUTTERS ARE REQUIRED. PROVIDE |
| HURRICANE SHUTTERS PRODUCT APPROVAL AND COMPLETE |
| INSTALLATION SCHEDULE. |
| |
| E) PROVIDE PRODUCT APPROVAL FOR MASTER BEDROOM CASEMENT |
| WINDOW #107 SPECIFIED SIZE 36"X99". |
| |
| F) DESIGN PRESSURES FOR EXTERIOR DOORS FLORIDA PRODUCT |
| APPROVAL FL18657-R1 DON'T SEEM TO COMPLY WITH THE |
| CALCULATED DESIGN PRESSURES. CLARIFY WHERE ARE THESE |
| DOORS GOING TO BE INSTALLED AND PROVIDE PRODUCT |
| APPROVAL THAT METS THE CALCULATED DESIGN PRESSURES. |
| |
| G) PROVIDE PRODUCT APPROVAL FOR INSWING ENTRY DOOR AS |
| SHOWN ON PLANS. |
| |
| H) CLAY TILE NOA 17-0626.03: PROVIDE PRODUCT APPROVAL |
| FOR ADHESIVE TO BE USED. SEE LISTED ADHESIVES ON NOA. |
| |
| I) POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK |
| WHICH ASSEMBLY FROM SEC. 5.6.4 OF FLORIDA PRODUCT |
| APPROVAL IS GOING TO BE USED TO VERIFY COMPLIANCE WITH |
| THE CALCULATED DESIGN PRESSURES. |
| |
| J) OPERABLE SHUTTERS AS SHOWN ON EXTERIOR ELEVATIONS |
| AND PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| SAMPLE OR PROVIDE COMPLETE INFORMATION ON A DIFFERENT |
| FORMAT THAT WILL PROVIDE ALL THE REQUIRED INFORMATION. |
| |
| K) WATER PROOFING AT TERRACE. PROVIDE PRODUCT APPROVAL |
| THAT IS DESIGN TO RECEIVE MATERIAL SPECIFIED BY THE |
| DESIGNER OF RECORD. |
| |
| 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE ALUMINUM TRELLIS. SEC. R301.1 |
| FBC_RESIDENTIAL. |
| NOTE: THIS MAY BE SUBMITTED LATER A A DEFERRED |
| SUBMITTAL OR UNDER A SEPARATE PERMIT. |
| |
| 14- FINISH FLOOR ELEVATION AT ENTRY FOYER DOESN'T |
| COMPLY WITH THE 2 FEET FREE BOARD REQUIRED BY SEC. |
| 18-284 CITY ORDINANCE NO. 4729-17 FOR FLOOD ZONE AREAS. |
| NOTE: SAME APPLIES FOR ELEVATOR PIT. |
| |
| 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| STAIRWAY CONSTRUCTION, INCLUDING RISER, TREADS, |
| HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH SEC. |
| R311.7 FBC-RESIDENTIAL. |
| |
| 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION/INSTALLATION OF THE STAINED WOOD BRACKETS |
| AND ROOF AT THE ENTRY OF THE GYM. SPECIFY ALL FRAMING |
| MEMBERS AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 17- PROVIDE COMPLETE SECOND FLOOR FRAMING |
| |
| 18- BUILDING SEC. 2/306 ON SHEET A-306.0 SHOWS |
| 2'-10-1/4" LANDING. NEED 3'-0" MIN. SEC. R311.3 |
| FBC-RESIDENTIAL. |
| |
| 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| PROPOSED FIREPLACE SHOWING COMPLIANCE WITH CHAPTER 10 |
| FBC-RESIDENTIAL. |
| |
| 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR |
| WATERPROOFING AND FINISH MATERIAL AT THE PROPOSED |
| TERRACE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 21- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| PROPOSED ELEVATOR SHOWING COMPLIANCE WITH SEC. R321 |
| FBC-RESIDENTIAL. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| |