Plan Review Notes
Plan Review Notes For Permit 18090657
Permit Number 18090657
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-18 12:10:331ST REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
 1. TUB/SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB,THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP.
 FBC RES P2708.4
 2. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON
 HOT WATER TO MASTER BATH BATHTUB(S) IS REQUIRED. FBC
 RES P2713.3
 3. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE, DISHWASHER AND CLOTHES WASHER PER FBC RES
 P2903.5
 4. THE VALVES FOR THE STACKABLE WASHING MACHINE(S)
 SHALL BE ACCESSIBLE. FBC RES P2903.9.3
  
 ADDITIONAL NOTE: SEE RED LINE MODIFICATION OF SANITARY
 ISOMETRIC TO MAKE CODE COMPLIANT
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715