2018-11-01 14:15:59 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. ROOF FRAMING - PROPOSED ROOF INDICATES A |
| PRE-ENGINEERED ROOF SYSTEM. DETAIL - TYP.RIDGE COPING |
| DETAIL ON PLAN PAGE A-4 INDICATES A RIDGE BEAM AND |
| RAFTER SYSTEM. PLEASE CLARIFY. |
| 2. WALL INSULATION - ENERGY SUBMITTAL REQUIRES R-19. |
| PLANS INDICATE R-15. PLEASE CLARIFY. |
| 3. CRAWL SPACE INSULATION - ENERGY SUBMITTAL REQUIRED |
| R-19. PLANS SHOW NO INSULATION IN CRAWL SPACE. PLEASE |
| CLARIFY. |
| 4. PROVIDE CRAWL SPACE VENTS PER R408.1 AND ACCESS PER |
| R408.4. |
| 5. EGRESS WINDOW - PGT-700 SERIES. WINDOW SIZE FROM |
| WINDOW SCHEDULE 3' X 5' DOES NOT PROVIDE THE REQUIRED |
| EGRESS OPENING PER R310.2.1. SELECT WINDOW FROM PGT |
| CATALOG THAT MEETS EGRESS REQUIREMENTS. CHANGE ROUGH |
| OPENING DEMENSIONS FOR NEW WINDOW. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |