Plan Review Notes
Plan Review Notes For Permit 18090633
Permit Number 18090633
Review Stop B
Sequence Number 2
Notes
Date Text
2019-03-18 08:30:27****CORRECTIONS****
 W.P.B. PERMIT: 18090633
 REVIEWED: MARCH 18, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS.
 THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED
 IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR
 LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS
 HORIZONTAL (2 PERCENT).
 -PLEASE ADD LANDING OUTLINE AND LANDING DIMENSIONS TO
 FLOOR PLAN.
  
 2) 602 FBC[R] WOOD WALL CONSTRUCTION.
 -PROVIDE CONNECTOR TYPE AND SPACING FOR BASE PLATE TO
 FOUNDATION.
 -PROVIDE CONNECTOR AND SPACING OF LEDGER BOARD AND WALL
 STUDS TO EXISTING STRUCTURE.
  
 3) 107.3.4 FBC[AMENDED] PREVIOUS COMMENT WAS TO PROVIDE
 PRODUCT APPROVALS. THE RESPONSE WAS TO SEE NOTE 1A, 2
 AND 3.
 -NOTE 1A HAS NINE DOORS LISTED WITH THE PRODUCT
 APPROVAL NUMBER LISTED. PLEASE SELECT THE ONE TO BE
 USED AND PRINT OUT TWO COPIES OF THE PRODUCT APPROVAL.
 MAKE SURE IT IS APPROVED FOR FLORIDA BUILDING CODE 6 TH
 EDITION 2017.
 ALSO, WE NEED TWO COPIES OF THE PRODUCT APPROVAL FOR
 THE LAUNDRY ROOM DOOR.
  
 3) 602.3(3)TABLE FBC[R] REQUIREMENTS FOR WOOD
 STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND
 PRESSURES.
 -PROVIDE SHEATHING NAIL SIZE AND SPACING FROM TABLE
 R602.3(3).
  
 4) THIS COMMENT IS NOT FROM THE BUILDING CODE. THIS IS
 A GENERAL OBSERVATION AND NO RESPONSE IS REQUIRED.
 -FROM THE LOOK OF LAUNDRY DOOR AND WATER HEATER
 PLACEMENT I DO NOT SEE HOW YOU WOULD GET TWO APPLIANCES
 IN THE SPACE. WHEN ONE APPLIANCE IS IN IT BLOCKS THE
 DOOR AND MAY HINDER THE NEXT APPLIANCE FROM GETTING
 INTO SPACE. MAYBE MOVE WATER HEATER DOWN OR CONSIDER
 DOUBLE DOORS.
  
 5) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND
 LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED.
 -ADD ROOF PITCH TO PLANS AND ADD NOTE FOR DOUBLE
 UNDERLAYMENT IS PITCH IS LESS THAN FOUR UNITS VERTICAL
 IN 12 UNITS HORIZONTAL (4:12)
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS.
 FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE
 REQUIRED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  