2019-03-18 08:30:27 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18090633 |
| REVIEWED: MARCH 18, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT |
| LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED |
| IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR |
| LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (2 PERCENT). |
| -PLEASE ADD LANDING OUTLINE AND LANDING DIMENSIONS TO |
| FLOOR PLAN. |
| |
| 2) 602 FBC[R] WOOD WALL CONSTRUCTION. |
| -PROVIDE CONNECTOR TYPE AND SPACING FOR BASE PLATE TO |
| FOUNDATION. |
| -PROVIDE CONNECTOR AND SPACING OF LEDGER BOARD AND WALL |
| STUDS TO EXISTING STRUCTURE. |
| |
| 3) 107.3.4 FBC[AMENDED] PREVIOUS COMMENT WAS TO PROVIDE |
| PRODUCT APPROVALS. THE RESPONSE WAS TO SEE NOTE 1A, 2 |
| AND 3. |
| -NOTE 1A HAS NINE DOORS LISTED WITH THE PRODUCT |
| APPROVAL NUMBER LISTED. PLEASE SELECT THE ONE TO BE |
| USED AND PRINT OUT TWO COPIES OF THE PRODUCT APPROVAL. |
| MAKE SURE IT IS APPROVED FOR FLORIDA BUILDING CODE 6 TH |
| EDITION 2017. |
| ALSO, WE NEED TWO COPIES OF THE PRODUCT APPROVAL FOR |
| THE LAUNDRY ROOM DOOR. |
| |
| 3) 602.3(3)TABLE FBC[R] REQUIREMENTS FOR WOOD |
| STRUCTURAL PANEL WALL SHEATHING USED TO RESIST WIND |
| PRESSURES. |
| -PROVIDE SHEATHING NAIL SIZE AND SPACING FROM TABLE |
| R602.3(3). |
| |
| 4) THIS COMMENT IS NOT FROM THE BUILDING CODE. THIS IS |
| A GENERAL OBSERVATION AND NO RESPONSE IS REQUIRED. |
| -FROM THE LOOK OF LAUNDRY DOOR AND WATER HEATER |
| PLACEMENT I DO NOT SEE HOW YOU WOULD GET TWO APPLIANCES |
| IN THE SPACE. WHEN ONE APPLIANCE IS IN IT BLOCKS THE |
| DOOR AND MAY HINDER THE NEXT APPLIANCE FROM GETTING |
| INTO SPACE. MAYBE MOVE WATER HEATER DOWN OR CONSIDER |
| DOUBLE DOORS. |
| |
| 5) 905.2.2 FBC[R] & 905.1.1 FBC[R] FOR ROOF SLOPES FROM |
| TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND |
| LESS THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| (4:12), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. |
| -ADD ROOF PITCH TO PLANS AND ADD NOTE FOR DOUBLE |
| UNDERLAYMENT IS PITCH IS LESS THAN FOUR UNITS VERTICAL |
| IN 12 UNITS HORIZONTAL (4:12) |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -COMMENTS ARE A BRIEF OVERVIEW OF CODE SECTIONS. |
| FURTHER REVIEW OF THE REFERENCED CODE SECTIONS WILL BE |
| REQUIRED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |