2018-11-08 08:29:41 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18090633 |
| REVIEWED: NOVEMBER 7, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC EB = FBC EXISTING BUILDING |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FL. STATUTE 471]DOCUMENTS PREPARED BY AN |
| ARCHITECT/ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE |
| TO BE SIGNED, SEALED, DATED ORIGINALS. |
| PLEASE SIGN AND SEAL A-101 AND A-102(BOTH SETS) |
| |
| 2. [FBC AMENDED 107.3.5] PROJECT DATA: |
| OCCUPANCY = R-3 ? |
| AREA TABULATIONS = STATE WHAT IS EXISTING UNDER AIR |
| AND, PROPOSED NEW AMOUNT AND TOTAL THAT WILL NOW BE |
| UNDER AIR. |
| [FBC EXISTING 501]STATE THE LEVEL OF ALTERATION FOR |
| WORK BEING PERFORMED. |
| STATE CODE EDITION BEING USED FOR ALL TRADES. |
| WE ARE CURRENTLY USING FLORIDA BUILDING CODE(FBC), 6TH |
| EDITION (2017) |
| BASIC WIND SPEED=170 |
| RISK CATEGORY = II ? |
| EXPOSURE CATEGORY = B,C OR D ? |
| BUILDING CLASSIFICATION = ENCLOSED ? |
| MEAN BLDG. HGT. = 0 FT.-0 IN. ? |
| WIND SPEED V ULT = 170 ? |
| WIND SPEED V ASD = 132 ? |
| INTERNAL PRESSURE COEFFICIENT GCPI = +/-0.18 |
| |
| 3. [FBC ENERGY R503.1.1]BUILDING ENVELOPE. BUILDING |
| ENVELOPE ASSEMBLIES THAT ARE PART OF THE ALTERATION |
| SHALL COMPLY WITH SECTION R402.1.2 OR R402.1.4, |
| SECTIONS R402.2.1 THROUGH R402.2.13, R402.3.1, |
| R402.3.2, R402.4.3 AND R402.4.5 |
| |
| 4. [FBC EXISTING 807.2]NEW STRUCTURAL ELEMENTS. |
| NEW STRUCTURAL ELEMENTS IN ALTERATIONS, INCLUDING |
| CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE |
| FLORIDA BUILDING CODE, BUILDING. |
| PROVIDE IN-FILL DETAIL, DOOR/WINDOW BUCK DETAILS AND |
| NEW COVERED LAUNDRY AREA CONSTRUCTION DETAILS. |
| |
| 5. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR |
| WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM |
| DEFERED. |
| PROVIDE NEW DOOR/WINDOWS DESIGN PRESSURES AND SIZES. |
| |
| 6. [FBC AMENDED 107.3.5]IF NEW ROOF OVER THE LAUNDRY |
| AREA PROVIDE PRODUCT APPROVAL FOR ROOFING MATERIAL TO |
| BE USED. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |