2019-01-16 09:51:152ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090632
 1/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 37-2018
 NFPA 110-
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTIONS 7.7.2,1 &, 7.7.2.3 & 7.7.3 NFPA
 110: PER THE ENGINEER'S PLAN AND NARRATIVE, THE
 VENTILATION AIR FOR THE GENERATOR IS BEING DRAWN IN
 THROUGH A LOUVERED OPENING IN THE 2HR. FIRE-RATED WALL
 GENERATOR ROOM WALL THAT ADJACENT TO THE PARKING GARAGE
 WHICH IS NOT PERMITTED PER SECTION 7.7.2.1 & 7.7.3.
 THESE SECTIONS STATE THAT VENTILATION AIR MUST BE
 SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE BUILDING.
 SECTION 7.7.2.3 PROHIBITS THE USE OF A FIRE DAMPER TO
 PROTECT THE OPENING, THEREFORE THE VENTILATION OPENING
 LOCATION WOULD NOT BE COMPLIANT BECAUSE OPENINGS IN
 FIRE BARRIERS REQUIRE PROTECTION ACCORDING TO SECTION
 607.5.2 FBC M.
  
 2) THE SUBMITTED CUT SHEET FOR THE IN LINE FAN (EF-2)
 IN THE GENERATOR/TANK ROOM IS FOR A MODEL THAT IS NOT
 THE SAME AS FAN IN THE SUBMITTED SCHEDULE. THE NEW FAN
 DOES NOT APPEAR TO BE IN COMPLAINCE WITH SECTIONS 503.1
 AND 503.2 FBC M WHICH REQUIRE THE MOTOR FOR THE FAN TO
 BE OUTSIDE THE DUCT, AND ALL PARTS OF THE FAN IN
 CONTACT WITH FLAMMABLE VAPORS, FUMES, OR DUSTS SHALL BE
 OF NONFERROUS OR NONSPARKING MATERIALS ETC.
  
 3) THE EXHAUST DUCT WORK FOR EF-2 SHALL BE G90 PER
 SECTIONS 510.9 AND SHALL ALSO BE ENCLOSED IN 2HR,
 FIRE-RESISTANT RATED CONSTRUCTION FROM POINT OF
 PENETRATRION TO THE OUTLET TERMINAL- SECTIONS 510.2 &
 510.7.3 FBC M, AND 6.3.6.5.1 NFPA 37.
  
 4) AS PREVIOUSLY REQUESTED SUBMIT THE GENERATOR EXHAUST
 PIPE SPECS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  