Plan Review Notes For Permit 18090632 |
Permit Number |
18090632 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-12-10 08:45:51 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | NEW COMMENTS WERE CREATED BY THE ADDITIONAL DRAWINGS | | THAT WERE SUBMITTED. | | | | 1) PLANS SHOW A DOUBLE OUTSWING DOOR (002) FOR THE | | GENERATOR ROOM AND THE DOOR SCHEDULE ON SHEET A-6.01 | | LISTS DOOR (002) AS A 3' WIDE DOOR. CLARIFY. FBC | | 107.2.1 | | | | 2) DOORS (001) AND (003) TO THE FIRE COMMAND ROOM ARE | | SINGLE DOORS AND ARE SPECIFIED AS TYPE 5 DOORS IN THE | | SCHEDULE ON A-6.01. THE TYPE 5 DOOR IS A DOUBLE DOOR. | | THE REMARKS FOR DOOR (003) IN THE SCHEDULE STATE THAT | | THIS IS THE DOOR TO THE MAINTENANCE ROOM, NOT THE FIRE | | COMMAND ROOM. PLEASE CORRECT. FBC 107.2.1 | | | | 3) PRODUCT APPROVALS ARE REQUIRED TO BE SUBMITTED FOR | | THE DOORS AND LOUVERS IN THE EXTERIOR WALLS. FBC | | 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR | | THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 | | PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA | | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM | | DESIGN PRESSURES FOR EACH REGULATED PRODUCT. |
|