2018-09-25 05:47:591) PROVIDE A COMPLETE DESCRIPTION OF THE WORK ON THE
 PERMIT APPLICATION. THE DESCRIPTION OF WORK ON THE
 APPLICATION JUST NOTES "GENERATOR". IS THIS GENERATOR
 REPLACING AN EXISTING? THE PLANS ARE VAGUE. 2017 FBC
 SEC. 107.2.1.
 2) THE PLANS SHOW A FUEL TANK. IS THE TANK NEW OR
 ESISTING? WHAT IS THE CAPACITY? WHAT TYPE OF TANK IS
 IT? SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE FUEL TANK. 2017 FBC SEC.
 107.2.1.
 3) THE TANK INSTALLATION SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF NFPA 30.
 4) SUBMIT TWO COPIES OF THE MSDS SHEETS FOR THE FUEL.
 2017 FBC SEC. 107.2.1.
 5) SUBMIT A FUEL PIPING RISER DIAGRAM FOR ANY NEW FUEL
 PIPING THAT WILL BE INSTALLED.
  