Plan Review Notes
Plan Review Notes For Permit 18090632
Permit Number 18090632
Review Stop M
Sequence Number 1
Notes
Date Text
2018-12-12 10:06:051ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090632
 12/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 37-2018
 NFPA 110-
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M-401: THE GENERATOR/TANK (EPS) ROOM DRAWINGS
 SHOW THE INTAKE AND EXHAUST AIRFLOW ARROWS REVERSED.
 THE RADIATOR IS EXHAUST AND THE LOUVER BY THE DOORS IN
 ALLEY IS INTAKE- PLEASE CORRECT.
  
 2) M-401: IT APPEARS THAT THE GENERATOR RADIATOR
 EXHAUST DISCHARGE AND EF-2 ARE BOTH DISCHARGING INTO
 THE PARKING GARAGE. PLEASE REVIEW THE FOLLOWING LIST OF
 CODE SECTIONS AND CORRECT:
  
 A) SECTION 501.3 FBC M: AIR REMOVED BY MECHANICAL
 EXHAUST SYSTEMS SHALL DISCHARGE TO THE OUTDOORS.
  
 B) SECTION 510.6.7 FBC M: HAZARDOUS EXHAUST DUCT
 SYSTEMS SHALL EXTEND DIRECTLY TO THE EXTERIOR OF THE
 BUILDING.
  
 C) SECTION 6.3.6.5.2 NFPA 37- 2015: VENTILATION SHALL
 DISCHARGE TO A SAFE LOCATION OUTSIDE OF THE BUILDING.
  
 D) SECTION 7.7.4.2 NFPA 110- 2016: RADIATOR AIR SHALL
 DISCHARGE BE DUCTED OUTDOORS.
  
 3) M-401: PLEASE CORRECT KEYED NOTE #3. THE EXHAUST
 SYSTEM IN THE GENERATOR/TANK (EPS) ROOM (EF-2) SHALL
 RUN CONTINUOUSLY- SECTIONS 4.1.2.1.3 & 6.3.6.5.1 NFPA
 37, AND SECTION 502.4.2 FBC M.
  
 4) M-401: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE GENERATOR/TANK (EPS) ROOM, AND PROVIDE AN EQUIPMENT
 SCHEDULE FOR EF-2- SECTION 502.4.2 FBC M.
  
 5) M-401: INDICATE THE TYPE AND GAGE OF THE EXHAUST
 DUCTWORK- SECTION 510.9 FBC M.
  
 6) M-401: THE OUTSIDE AIR INTAKE FOR THE GENERATOR/TAN
 K (EPS) ROOM SHALL BE 10' FROM THE ALLEY IN ACCORDANCE
 WITH SECTION 510.6.5 AND 401.4 (1) & (2) FBC M.
  
 7) M-401: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND
 VERIFY THAT THE VENTILATION AIRFLOW IN THE
 GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE
 MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR
 MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE
 HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER,
 EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT-
 SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND
 VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE
 PROVISONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY,
 LOUVERS, ETC.- SECTION 7.7.7.
  
 8)1SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS,
 AND PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL
 SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL
 COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, AND
 ANY CONTRACTOR SUPPLIED PIPING.
  
 9) THE MAXIMUM BACKPRESSURE FOR THE EXHAUST SYSTEM PER
 THE MANUFACTURER'S SPECS IS 10 KPA PLEASE PROVIDE A
 BACKPRESSURE CALCULATION TO SHOW COMPLIANCE. THE CALC
 MUST INCLUDE ALL COMPONENTS OF THE EXHAUST SYSTEM,
 INCLUDING THE SILENCER AND ALL FACTORY OR CONTRACTOR
 SUPPLIED PIPING.
  
 10) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND
 THE FUEL TANK- SECTION 304.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  