Plan Review Notes
Plan Review Notes For Permit 18090632
Permit Number 18090632
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-17 13:00:54PER NFPA 110
  
 7.2 LOCATION.
 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE
 INSTALLED IN A
 SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS.
 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST
 OF THE
 BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE
 RATING.
  
 PLEASE PROVIDE DETAILS OF THE RATING OF THE PROPOSED
 ROOM AND DOOR TO THIS GENERATOR ROOM.
  
  
  
  
  
 THERE IS AN INDICATION OF EXHAUST PIPING, HOWEVER,
 THERE ARE NO DETAILS.
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS.
  
  
  
  
 THERE IS AN INDICATION OF A FUEL TANK INSIDE THE
 GENERATOR ROOM. THERE IS NO INDICATIONS IF IT MEETS THE
 REQUIREMENTS OF NFPA 110 OR OTHER APPLICABLE CODES.
  
 PER NFPA 110
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA
 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED.
 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED
 BETWEEN THE
 PRIME MOVER AND THE FUEL PIPING.
 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE
 INDICATING
 TYPE.
 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE
 MAINTAINED ON ALL SIDES.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 THERE IS AN INDICATION OF A FUEL TANK WITHIN THE
 GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS
 DOUBLE WALLED OR THERE IS CONTAIMENT.
  
 PER NFPA 30
  
 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL.
 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO
 PREVENT
 THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC
 SEWERS,
 OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN
 SPECIFICALLY
 APPROVED.