Date |
Text |
2018-10-17 13:00:54 | PER NFPA 110 |
| |
| 7.2 LOCATION. |
| 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE |
| INSTALLED IN A |
| SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS. |
| 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST |
| OF THE |
| BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE |
| RATING. |
| |
| PLEASE PROVIDE DETAILS OF THE RATING OF THE PROPOSED |
| ROOM AND DOOR TO THIS GENERATOR ROOM. |
| |
| |
| |
| |
| |
| THERE IS AN INDICATION OF EXHAUST PIPING, HOWEVER, |
| THERE ARE NO DETAILS. |
| |
| PER NFPA 110 |
| |
| 7.10 EXHAUST SYSTEM. |
| 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| INCLUDING |
| PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| OTHER APPLICABLE |
| STANDARDS. |
| 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| PREVENT |
| EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| BUILDINGS |
| AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| WINDOWS, |
| AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| SYSTEM. |
| 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME |
| MOVER |
| BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE |
| INDEPENDENTLY |
| SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR |
| STRESS IS |
| APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. |
| |
| PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS. |
| |
| |
| |
| |
| THERE IS AN INDICATION OF A FUEL TANK INSIDE THE |
| GENERATOR ROOM. THERE IS NO INDICATIONS IF IT MEETS THE |
| REQUIREMENTS OF NFPA 110 OR OTHER APPLICABLE CODES. |
| |
| PER NFPA 110 |
| |
| 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| AND MAINTAINED |
| IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| 54, NATIONAL |
| FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| CODE. |
| 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED. |
| 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED |
| BETWEEN THE |
| PRIME MOVER AND THE FUEL PIPING. |
| 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE |
| INDICATING |
| TYPE. |
| 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE |
| MAINTAINED ON ALL SIDES. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| THERE IS AN INDICATION OF A FUEL TANK WITHIN THE |
| GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS |
| DOUBLE WALLED OR THERE IS CONTAIMENT. |
| |
| PER NFPA 30 |
| |
| 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL. |
| 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO |
| PREVENT |
| THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC |
| SEWERS, |
| OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN |
| SPECIFICALLY |
| APPROVED. |