Plan Review Notes
Plan Review Notes For Permit 18090632
Permit Number 18090632
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-28 09:23:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CONDUIT SIZE FROM GENERATOR TO ATS NOT ANNOTATED ON
 PLAN. PLEASE PROVIDE CORRECTION. FBC 107.2.1
  
 2. WIRING METHOD AND CONDUIT SIZE FROM GENERATOR TO
 FIRE PUMP CONTROLLER NOT ANNOTATED ON PLAN. WRING
 METHOD MUST COMPLY WITH 695.6A2. PLEASE PROVIDE
 CORRECTION. FBC 107.2.1
  
 3. WIRE SIZE FROM GENERATOR TO ATS NOT ANNOTATED ON
 PLAN. PLEASE PROVIDE CORRECTION. FBC 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  