Plan Review Notes
Plan Review Notes For Permit 18090589
Permit Number 18090589
Review Stop P
Sequence Number 2
Notes
Date Text
2019-01-10 09:07:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. SECOND REQUEST
 A) RE: PLAN SHEET A2, A3, P0.1, P2.1 & P3.1; THE
 ACCESSIBILITY CODE REQUIRES A MINIMUM OF 1 SINK IN EACH
 TYPE OF ACCESSIBLE ROOM COMPLY WITH FBC ACC 606 PER FBC
 ACC 212.3. PLEASE NOTE THAT THE ARCHITECT HAS NOT
 PROVIDED THIS INFORMATION ON THE PLANS AND NEEDS TO DO
 SO BEFORE THE PLUMBING PERMIT APPLICATION CAN BE
 APPROVED. THE PROVIDED INFORMATION BY THE ARCHITECT
 NEEDS TO INCLUDE SUCH THINGS AS THE DESIGNATED
 ACCESSIBLE ROOM (IE. EXAM RM #4), MILL WORK PLAN AND
 ELEVATION VIEWS, AND POSSIBLY ANOTHER DESIGNATED
 PLUMBING FIXTURE IN THE PLUMBING FIXTURE SCHEDULE.
 2. PLAN SHEET A2 INDICATES AN EXISTING WATER HEATER IN
 THE EXISTING STORAGE ROOM. P0.1 AND P3.1 INDICATE A NEW
 WATER HEATER.
 A) RESPONSE BY ENGINEER IS THAT THE EXISTING WATER
 HEATER IS TO BE REPLACED WITH A NEW WATER HEATER OF
 LIKE KIND. REQUIRED INFORMATION CONCERNING THIS HAS
 BEEN INCLUDED IN THE PLUMBING FIXTURE SCHEDULE AND
 DETAIL.
 B) ARCHITECT TO REMOVE NOTE ?EXISTING WATER HEATER? AND
 ON PLAN SHEET A2 AND PROVIDE NOTE ?REPLACE EXISTING
 WATER HEATER WITH NEW? PER WPB FBC 107.2.1
 3. RE: PLAN SHEET A1; CODE SUMMARY. REFERENCES TO
 FLORIDA ACCESSIBILITY CODE 2014, FBC PLUMBING CODE 2014
 AND FBC FUEL GAS CODE 2014 SHALL BE CORRECTED TO SHOW
 COMPLIANCE WITH THE 6TH EDITION, 2017 CODE PER WPB FBC
 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
  