Plan Review Notes For Permit 18090558 |
Permit Number |
18090558 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-12-20 06:26:23 | 1) SHT. P-1 - THE SAMPLING PORT SHOWN FOR THE GREASE | | TRAP IS UNACCEPTABLE .THE SAMPLING PORT SHALL BE | | MINIMUM 4 INCH TWO WAY CLEANOUT PER THE CITY OF WEST | | PALM BEACH UTILITIES DEPT.YOU HAVE REVISED THE PLAN | | VIEW BUT HAVE NOT REMOVED THIS DETAIL FROM THE | | PLANS.2ND REQUEST. | | 2) THE PLUMBING SANITARY RISER AND PLAN VIEW FOR THE | | BAR AREA STILL SHOWS THE ICE BINS DISCHARGING TO THE | | INTERCEPTOR. THE CLEAR WATER WASTE SHALL NOT DISCHARGE | | TO THE INTERCEPTOR. 2017 FBC-PLUMBING. SEC. 1003.2. 2ND | | REQUEST. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|