Plan Review Notes For Permit 18090558
Permit Number 18090558
Review Stop P
Sequence Number 3
Notes
Date Text
2018-12-20 06:26:231) SHT. P-1 - THE SAMPLING PORT SHOWN FOR THE GREASE
 TRAP IS UNACCEPTABLE .THE SAMPLING PORT SHALL BE
 MINIMUM 4 INCH TWO WAY CLEANOUT PER THE CITY OF WEST
 PALM BEACH UTILITIES DEPT.YOU HAVE REVISED THE PLAN
 VIEW BUT HAVE NOT REMOVED THIS DETAIL FROM THE
 PLANS.2ND REQUEST.
 2) THE PLUMBING SANITARY RISER AND PLAN VIEW FOR THE
 BAR AREA STILL SHOWS THE ICE BINS DISCHARGING TO THE
 INTERCEPTOR. THE CLEAR WATER WASTE SHALL NOT DISCHARGE
 TO THE INTERCEPTOR. 2017 FBC-PLUMBING. SEC. 1003.2. 2ND
 REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW