2018-12-20 05:09:441) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR ALL GAS EQQUIPMENT.A NOTE ON
 SHT.P-3 FOR THE TANKLESS WATER HEATER IS INSUFFICIENT.
 EQUIPMENT SHALL BE LISTED AND LABELED PER 2017 FBC-FUEL
 GAS SEC.301.3, WPB AMEND. TO FBC SEC.. 107.2.1. 2ND
 REQUEST.
 2) SHOW THE DISTANCE FROM THE TANKLESS WATER HEATER TO
 THE REAR DOOR AND ALL OTHER OPENINGS INTO THE BUILDING.
 THE TANKLESS WATER HEATER SHALL BE LOCATED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION MANUAL.
 2017 FBC-FUEL GAS SEC.305.1.
 3) THE COMBUSTION AIR CALCULATIONS THAT HAVE BEEN
 SUBMITTED DO NOT CORRELATE WITH THE EQUATION IN THE
 CODE ALTHOUGH THE FINAL TOTAL CFM IS CORRECT. REVISE
 THE EQUATION NUMBERS TO COMPLY WITH THE CODE. PLEASE
 REFER TO 2017 FBC-FUEL GAS SEC.304.9.
 4) EACH OF THE APPLIANCES SERVED SHALL BE INTERLOCKED
 WITH THE MECHANICAL AIR SUPPLY SYSTEM TO PREVENT MAIN
 BURNER OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM
 IS NOT IN OPERATION. 2017 FBC- FUEL GAS SEC. 304.9.2.
  