Plan Review Notes For Permit 18090558 |
Permit Number |
18090558 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-11-16 15:00:34 | 1) THE SAMPLING PORT SHOWN FOR THE GREASE TRAP IS | | UNACCEPTABLE. THE SAMPLING PORT SHALL BE A MINIMUM 4 | | INCH TWO WAY CLEANOUT PER THE CITY OF WEST PALM BEACH | | UTILITIES DEPT. | | 2) THE CLEAR WATER WASTE FROM THE ICE BIN, ICE MAKER | | AND ANY OTHER CLEAR WATER WASTE SHALL NOT DISCHARGE | | INTO THE GREASE INTERCEPTOR. 2017 FBC-PLUMBING | | SEC.1003.2. | | 3) THE HOT WATER LINES SHALL BE INSULATED IN ACCORDANCE | | WITH THE 2017 FBC-ENERGY SEC.C404.4 & IN THE THICKNESS | | REQUIRED BY TABLE C403.2.10. | | 4) THE LOCATION OF THE TANKLESS WATTER HEATER SHALL BE | | LOCATED A MINIMUM OF 4 FEET FROM OPERABLE DOORS AND | | WINDOWS PER THE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|