2018-11-16 15:00:341) THE SAMPLING PORT SHOWN FOR THE GREASE TRAP IS
 UNACCEPTABLE. THE SAMPLING PORT SHALL BE A MINIMUM 4
 INCH TWO WAY CLEANOUT PER THE CITY OF WEST PALM BEACH
 UTILITIES DEPT.
 2) THE CLEAR WATER WASTE FROM THE ICE BIN, ICE MAKER
 AND ANY OTHER CLEAR WATER WASTE SHALL NOT DISCHARGE
 INTO THE GREASE INTERCEPTOR. 2017 FBC-PLUMBING
 SEC.1003.2.
 3) THE HOT WATER LINES SHALL BE INSULATED IN ACCORDANCE
 WITH THE 2017 FBC-ENERGY SEC.C404.4 & IN THE THICKNESS
 REQUIRED BY TABLE C403.2.10.
 4) THE LOCATION OF THE TANKLESS WATTER HEATER SHALL BE
 LOCATED A MINIMUM OF 4 FEET FROM OPERABLE DOORS AND
 WINDOWS PER THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  