2018-11-28 07:03:52 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| GAS COMMENTS: DENIED |
| |
| 1.PLAN SHEET P-2; GAS ISOMETRIC. GAS PIPING DOES NOT GO |
| THROUGH THE ANSUL SYSTEM. ACCESSIBLE EMERGENCY VALVE TO |
| BE INSTALLED IN LINE TO KITCHEN COOKING LINE. |
| A. EMERGENCY GAS VALVE PIPING IS SHOWN GOING TO A DEAD |
| END. ACCESSIBLE EMERGENCY GAS VALVE TO BE INSTALLED IN |
| LINE TO KITCHEN COOKING APPLIANCES AND CONTROLLED BY |
| THE ANSUL SYSTEM TO COMPLY. |
| 2. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE |
| TANKLESS WATER HEATER TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND FBC FG 402.2, AND 301.3 |
| GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1 |
| 3. SHT. P-2 - THERE IS A NOTE AT THE GAS RISER THAT |
| REFERS TO THE 2014 FUEL GAS CODE. THE GAS CODE IN |
| EFFECT IS THE 2017 CODE. REVISE THE NOTE. |
| 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS |
| EQUIPMENT PER 2017 FBC-FUEL GAS SEC. 304.1.WHERE |
| COMBUSTION AIR IS PROVIDED BY THE BUILDING'S MECHANICAL |
| VENTILATION SYSTEM,THE SYSTEM SHALL PROVIDE THE |
| SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS |
| SEC.304.9.3. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |