Plan Review Notes
Plan Review Notes For Permit 18090558
Permit Number 18090558
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2018-10-24 11:38:48THE PREVIOUS COMMENTS FROM FIRE DO NOT APPEAR TO BE
 ADDRESSED EITHER IN CLOUD REVISIONS NOR NARRATIVE AND
 ARE RESTATED BELOW.
  
 PLEASE ADDRESS FIRE COMMENTS SPECIFICALLY:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 03 - THE OCCUPANCY LOAD CALCULATIONS DO NOT
 INDICATE NUMBERS FOR THE KITCHEN OR BAR SERVICE AREA.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
  
 2) THERE ARE NO DIMENSIONS INDICATED TO VERIFY THE
 OCCUPANCY LOAD OF THE SEATING AREA. THE BATHROOMS
 SHOULD NO BE INCLUDED WITH THE SEATING AREA.
  
 ADDITIONALLY, THERE ARE NO DIMENSIONS INDCATED BETWEEN
 THE SEATS OR EACH AISLE TO ENSURE REQUIRED WIDTHS OR
 PASSAGE.
  
 PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING
 ASSEMBLY OCCUPANCIES
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT
 TABLES SHALL BE
 NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN
 OCCUPANT LOAD
 EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN
 OCCUPANT
 LOAD OF 50 OR FEWER.
 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF
 THE AISLE SHALL
 BE MADE TO A LINE 19 IN. (485 MM), MEASURED
 PERPENDICULARLY TO
 THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID
 TABLE.
 12.2.5.9 APPROVAL OF LAYOUTS.
 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF
 FURNISHINGS OR
 EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE
 BUILDING
 OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE
 WITH THE PROVISIONS OF 12.2.5.
 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY
 ACCEPTABLE
 ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS
 MET:
 (1) THE PLANS ARE REVISED.
 (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED.
 (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE
 APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT
 LOAD IS
 NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) SHEET A 04 - 8 SEATS ARE INDCATED ON THE FLOOR PLAN
 BY THE LEFT SIDE DOUBLE DOORS. 4 OF THE SEAT ENCROACH
 INTO THE PATH OF EGRESS.
  
 THOSE DOORS ARE NOT REQUIRED TO MEET YOUR EGRESS
 DEMAND; HOWEVER, EITHER THOSE DOOR CAN NOT BE INDICATED
 AS AN EXIT OR THE CHAIRS AND TABLES WILL NEED TO BE
 REMOVED.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
  
  
  
 4) SHEET A 06 - THERE IS KITCHEN COOKING AND HOOD
 EQUIPMENT INDICATED. THERE ARE NO INDICATIONS IF THE
 NOTED EQUIPMENT IS NEW OR EXISTING.
  
 PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING
 ASSEMBLY OCCUPANCIES
  
 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT
 IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 ALL COOKING AND HOOD EQUIPMENT NEW OR EXISTING SHALL BE
 INSPECTED AND TESTED FOR COMPLIANCE WITH THE APPLICABLE
 CODE.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
  
 5) FIRE SPRINKLER DOCUMENTS ARE INDICATED WITH THE
 BACK-UP INFORMATION PACKET . THESE DOCUMENTS ARE
 ACCEPTED AS INFORMATIONAL PURPOSES ONLY.
  
 FIRE SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED
 SEPARATELY FOR APPROVAL.
  
  
  
 6) DOOR INFORMATION DOCUMENTS ARE INDICATED WITH THE
 BACK-UP INFORMATION PACKET. THOSE DOCUMENTS ARE
 INDICATED WITH HELLBENT CUSTOM GARAGE IN THE TITLE
 BLOCKS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]