Plan Review Notes
Plan Review Notes For Permit 18090558
Permit Number 18090558
Review Stop B
Sequence Number 2
Notes
Date Text
2018-11-14 12:26:21****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA, INCLUDING DESIGN PRESSURES FOR THE NEW DOORS.
  
 2. PRIOR TO INSTALLATION, DOOR ENGINEERING REVIEWED BY
 DESIGNER OF RECORD IS TO BE SUBMITTED AND ISSUED PRIOR
 TO INSTALLATION. A SEPARATE SUBMITTAL HAS BEEN
 GENERATED FOR THE DOOR ENGINEERING TO FACILITATE
 ISSUANCE OF THIS PERMIT.
  
 3. REVISE THE LIFE SAFETY PLAN; OCCUPANT LOAD IS OVER
 50 SO REQUIRES TWO REMOTELY LOCATED EXITS. THE THREE
 FRENCH DOORS ARE SHOWN AS NON-EGRESS, BUT ONE IS
 REQUIRED. BUILDING OFFICIAL HAS AGREED TO APPLICANT'S
 PROPOSAL OF DOOR SIGNAGE INDICATING "OPEN" OR "CLOSED"
 AND AGREEMENT THAT THE DOORS WILL REMAIN UNLOCKED AT
 ALL TIMES THAT THE RESTAURANT IS OPEN.
  
  
  
  
  