Date |
Text |
2018-10-04 08:28:21 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW: |
| GAS COMMENTS: DENIED |
| |
| 1. RE: PLAN SHEET P-2; GAS ISOMETRIC. EMERGENCY HOOD |
| SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE CEILING. |
| THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM OF KITCHEN |
| EQUIPMENT. UNION TO BE DOWN STREAM OF MANUAL VALVE. |
| SECS. 10.4, 10.5 OF NFPA 96-08. |
| A. EMERGENCY GAS VALVE PIPING IS SHOWN GOING TO A DEAD |
| END. ACCESSIBLE EMERGENCY GAS VALVE TO BE INSTALLED IN |
| LINE TO KITCHEN COOKING APPLIANCES AND CONTROLLED BY |
| THE ANSUL SYSTEM TO COMPLY. |
| 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING |
| REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC FG 402.2, AND 301.3 GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FBC FG 305.1 |
| 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS FOR GAS REGULATOR VENTS IF APPLICABLE (SEE NOTE |
| 2 AND FBC FG 410.3) PER FBC-FG SECS. 502 THRU 505 WPB |
| FBC 107.2.1 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
2018-10-02 16:14:48 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW: |
| PLUMBING COMMENTS: DENIED |
| |
| 1. RE: PLAN SHEET P-2; GAS ISOMETRIC. GAS PIPING DOES |
| NOT GO THROUGH THE ANSUL SYSTEM. ACCESSIBLE EMERGENCY |
| VALVE TO BE INSTALLED IN LINE TO KITCHEN COOKING LINE. |
| 2. PROVIDE MANUFACTURER"S SPECS FOR ALL GAS FIRED |
| EQUIPMENT INCLUDING THE TANKLESS WATER HEATER. WPB FBC |
| 107.2.1 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |