2018-10-11 06:26:13 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. FBC A 226, 902.1, IT APPEARS THAT THERE ARE TWO |
| DINING BAR AREAS; REVISE PLAN TO SHOW COMPLIANCE. BAR |
| HEIGHT IS NOT CLEAR, AND NO ACCESSIBLE PORTION SHOWN. |
| |
| 2. FBC A 227, SALES AND SERVICE A POS AND PICK UP AREA |
| IS SHOWN. REVISE PLAN TO SHOW COMPLIANCE. |
| |
| 3. FBC A TABLE 404.2.41(C), THE TWO BATHROOM DOORS SHOW |
| 12" CLEARANCE ON THE PULL SIDE, BUT IT APPEARS THAT 18" |
| IS REQUIRED. ALTHOUGH THIS IS EXISTING, PLEASE SEE FBC |
| A 202.4. IT APPEARS THAT THERE IS ROOM TO MOVE THE LAV |
| AND MAINTAIN ALL REQUIRED CLEAR FLOOR SPACES. NOTE |
| THAT, AS INSTALLED, A WHEELCHAIR USER COULD ENTER AND |
| USE THE BATHROOM BUT MAY BE UNABLE TO EXIT. |
| |
| 4. A.04, DOOR SCHEDULE SHOWS "NA" FOR ALL DOORS. FLOOR |
| PLAN SHOWS THREE NEW DOUBLE DOORS PROPOSED AS WELL AS |
| EXISTING DOORS AND REFERS TO STRUCTURAL DRAWINGS FOR |
| THE NEW DOORS. NO STRUCTURAL SHEETS WERE SUBMITTED, |
| PLEASE PROVIDE. LIFE SAFETY/FLOOR PLAN SHOULD SHOW THE |
| SIZE OF THE NEW DOORS PROPOSED AS WELL AS PROVIDE |
| INFORMATION REGARDING EXISTING DOORS, FBC 107, FBC B |
| 1609, FBC B CHAPTER 10. |
| |
| 5. FBC B 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN |
| CRITERIA, INCLUDING DESIGN PRESSURES FOR THE NEW DOORS. |
| |
| 6. TO AVOID ANY FIELD CONFLICTS, REVISE THE DOOR |
| SCHEDULE TO INCLUDE THE PANIC BARS REQUIRED BY FBC B |
| 1010.1.10 (PER FBC EB 801.3. |
| |
| 7. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN |
| ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| SIGNED, SEALED DATED ORIGINALS. AT LEAST ONE PAGE WAS |
| SEALED BUT NOT SIGNED AND DATED. PLEASE CONFIRM ALL |
| PAGES PRIOR TO RESUBMITTAL. |
| |
| 8. THIS PERMIT WILL BE ISSUED WITH PROVISO; PRIOR TO |
| INSTALLATION, DOOR PRODUCT APPROVALS REVIEWED BY |
| DESIGNER OF RECORD ARE TO BE SUBMITTED AND ISSUED PRIOR |
| TO REVIEW. ON THE PRODUCT APPROVAL, INDICATE ADA |
| THRESHOLD AND PANIC BARS. IF YOU DO NOT AGREE WITH THIS |
| PROVISO, CONTACT ME PRIOR TO ISSUANCE. |
| |
| |
| |
| |