Plan Review Notes
Plan Review Notes For Permit 18090535
Permit Number 18090535
Review Stop M
Sequence Number 1
Notes
Date Text
2018-11-06 15:19:381ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18090535
 11/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE 2010
 FBC M- FLORIDA MECHANICAL CODE 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 2010
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION 503.2.1 FBC EC.
  
 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTION
 101.4.9 FBC EC.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS AND SHOW
 THE LOCATION OF THE O/A OUTLET INTO THE SPACE- TABLE
 403.3 FBC M.
  
 4) SHEET M101: PROVIDE DUCT SMOKE DETECTORS IN BOTH THE
 SUPPLY AND RETURN SYSTEMS OF THE HP'S- SECTION 606.2.2
 FBC M
  
 5) M101: INDICATE THE SIZE OF THE RETURN OPENINGS AT
 THE HP CLOSETS- SECTION 601.4 FBC M.
  
 6) M101: THE PLAN APPEARS TO SHOW THE DRYER EXHAUST
 DUCT RUNNING THROUGH THE PLENUM WHICH IS PROHIBITED PER
 SECTION 504.4 FBC M.
  
 7) M101: SHOW THE LOCATIONS OF THE THERMOSTATS FOR THE
 HP'S- SECTION 503.2.4.1 FBC EC.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE DRYER, COOKING
 APPLIANCES, AND THE KITCHEN EXHAUST HOOD AND DUCT-
 SECTION 304.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  