2019-04-01 12:37:38 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090469 |
| 360 S. ROSEMARY |
| 4/1/19 |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| 1) THE REQUEST BY TLC ENGINEERING TO ADD THE FOLLOWING |
| ITEMS TO THE DEFERRED SUBMITTAL IS ACCEPTED: |
| A) AC COOLING AND HEATING CALCULATIONS. |
| B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| SPACES. |
| C) COMMISSIONING PLAN: THE PLAN IS THE FIRST STEP IN |
| THE PROCESS WHICH CULMINATES WITH SUBMITTAL OF A FINAL |
| COMMISSIONING REPORT. |
| |
| 2) REVISED M1.01 PLAN ERRORS AND OMISSIONS: |
| A) KEYNOTE #3 IS BEING USED TO INDICATE BOTH EXHAUST AT |
| THE GENERATOR ROOM AND AIR INTAKE OPENING FOR THE LOBBY |
| AND CORE ROOMS AND SPACES. THE REQUESTED DAMPER AT THE |
| INLET NOT SHOWN- SECTION C403.2.4.3 FBC EC. |
| B) AH-DX-1-1 AND AH-DX-1-2 NOT IDENTIFIED- SECTION |
| 107.2.1 WPB. |
| C) AH-DX-1-7 IN THE POWER ROOM NOT SHOWN- SECTION |
| 107.2.1 WPB. |
| D) NOTE #5 INDICATES A FIRE-RATED ENCLOSURE FOR THE |
| TANK ROOM MAKE UP AIR DUCT WHICH IS NOT REQUIRED, |
| HOWEVER FIRE DAMPERS ARE REQUIRED AT THE DUCT |
| PENETRATIONS OF FIRE-RATED WALLS- SECTION 607.5.2 FBC |
| M. |
| E) THE EXHAUST DUCT RUN FROM THE TANK ROOM TO THE |
| EXTERIOR OF THE BUILDING IS NOT SHOWN, AND NO DUCT |
| SPECIFICATIONS HAVE BEEN PROVIDED- TYPE AND SIZE OF |
| DUCT, TERMINATION LOCATION AND CLEARANCES ETC- SECTION |
| 510 FBC M. |
| F) CONSTRUCTION DETAILS FOR THE FIRE-RATED EXHAUST DUCT |
| ENCLOSURE NOT PROVIDED. THE RESPONSE NARRATIVE FROM TLC |
| IS CALLING THIS OUT AS AN "INTERSTITIAL WALL". NO NOTES |
| ON THE PLAN PROVIDED- SECTION 713.2 FBC B. |
| G) THE LETTER DAIKIN CERTIFYING THE INSTALLATIONS OF |
| THE OUTDOOR CONDENSERS IN THE ENCLOSED GARAGES IS NOT |
| ACCEPTED: 1) IT IS INDICATING THE UNITS ARE TO BE |
| INSTALLED IN AN "OPEN GARAGE" AND NOT AN ENCLOSED |
| GARAGE. 2) THE LETTER IS FROM BECAUSE A SALES MANAGER, |
| AND ALTERNATE DESIGNS AND METHODS MUST BE SUBMITTED BY |
| A LICENSED DESIGN PROFESSIONAL. THE MANUFACTURER'S |
| TECHNICAL DEPARTMENT CAN PROVIDE INSTALLATION DETAILS |
| FOR INDOOR INSTALLATIONS THAT WOULD BE ACCEPTABLE IF |
| THE DETAILS BEAR A SHOP DRAWING STAMP OF APPROVAL BY |
| THE ENGINEER OF RECORD FOR THE PROJECT. PLEASE NOTE |
| THAT THE LETTER MUST ADDRESS ALL THE CONDENSERS ON ALL |
| FLOORS THAT ARE BEING INSTALLED IN THE ENCLOSED |
| GARAGES- SECTION 304.1 FBC M. |
| H) RETURN AIR MISSING FROM THE ENGINEERING ROOM- |
| SECTION 601.6 FBC M. |
| |
| 3) REVISED M1.02 PLAN ERRORS AND OMISSIONS: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| |
| 4) REVISED M1.03 PLAN ERRORS AND OMISSIONS: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| B) THE PLAN APPEARS TO SHOW A 4" ROUND DUCT SUPPLYING |
| 660 CFMS OF CONDITIONED SUPPLY AIR TO THE FUTURE |
| OFFICE, HOWEVER THE AIRFLOW ARROW SHOWN BY THE 12X10 |
| OPENING IS IS MOST LIKELY REVERSED. I'M ASSUMING THIS |
| IS SUPPOSED TO INDICATE THE O/A SUPPLY. PLEASE CORRECT |
| AND PROVIDE NOTES TO CLARIFY- SECTION 107.2.1 WPB. |
| C) NO TEXT HAS BEEN PROVIDED AT KEYED NOTE #6. |
| |
| 5) REVISED M1.04: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| B) IT APPEARS THE O/A SUPPLY DUCT LAYOUT IS INCOMPLETE. |
| NO INLET LOCATION IS SHOWN, NO NOTES- SECTION 107.2.1 |
| WPB. |
| |
| 6) REVISED M1.05: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| B) SEE COMMENT #4B ABOVE FOR SIMILAR DEFICIENCY. |
| |
| 7) REVISED M1.06: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1 |
| WPB. |
| |
| 8) REVISED M1.07: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1 |
| WPB. |
| |
| 9) REVISED M1.08: |
| A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| ROOM- SECTION 404.3 FBC M. |
| B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1 |
| WPB. |
| |
| 10) M1.09: PLACE NOTES ON THE PLAN TO SHOW THE |
| LOCATIONS OF THE O/A, THE TOILET EXHAUST, AND THE SMOKE |
| EXHAUST SMOKE SHAFTS- |
| A) PROVIDE MOTORIZED FIRE/SMOKE DAMPERS AT THE EXHAUST |
| AND AIR INLET OPENINGS AT THE SHAFTS- SECTION 607.5.5 |
| FBC M. |
| |
| PLEASE NOTE THE FOLLOWING: |
| 1) SEPARATE PERMITS ARE REQUIRED FOR THE FUTURE |
| RESTAURANT AND OFFICES, KITCHEN EXHAUST HOODS AND FIRE |
| SUPPRESSION SYSTEM, WALK IN COOLERS AND FREEZERS. |
| 2) DEFERRED SUBMITTALS |
| REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP |
| DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME |
| OF INSPECTION. |
| 1) SMOKE CONTROL FANS INCLUDING SMOKE EXHAUST FANS, AND |
| STAIRWELL AND ELEVATOR PRESSURIZATION FANS. |
| 2) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. |
| 3) MOTORIZED AND BAROMETRIC DAMPERS |
| 4) DUCT SMOKE DETECTORS |
| 5) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES |
| INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT |
| APPROVALS AND/OR MIAMI-DADE NOA'S |
| 6) AC STAND NOA'S OR FL. PRODUCT APPROVALS |
| 7) C0, N02, & CO2 SENSORS, AND REFRIGERANT LEAK |
| DETECTORS. |
| 8) COOLING TOWERS |
| 9) FACTORY BUILT DUCTWORK |
| 10) DUCT FIRE WRAPPING |
| 11) CLOTHES DRYERS |
| 12) COOKING APPLIANCES |
| 13) TEST AND BALANCE REPORTS |
| 14) SMOKE CONTROL TEST REPORTS. |
| |
| SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT |
| FOR REVIEW. |
| 1) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR |
| INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND |
| APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR |
| DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE |
| TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED |
| ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE |
| STRUCTURAL ENGINEER RECORD. |
| 2) GENERATORS AND FUEL TANKS AND ALL ASSOCIATED |
| EQUIPMENT, VENT FLUES, AND FUEL OIL PIPING. |
| 3) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR |
| DUCTS AND VENT FLUES. |
| 4) COMMISSIONING REPORTS |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |