Plan Review Notes
Plan Review Notes For Permit 18090469
Permit Number 18090469
Review Stop M
Sequence Number 3
Notes
Date Text
2019-04-01 12:37:383RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18090469
 360 S. ROSEMARY
 4/1/19
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) THE REQUEST BY TLC ENGINEERING TO ADD THE FOLLOWING
 ITEMS TO THE DEFERRED SUBMITTAL IS ACCEPTED:
 A) AC COOLING AND HEATING CALCULATIONS.
 B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES.
 C) COMMISSIONING PLAN: THE PLAN IS THE FIRST STEP IN
 THE PROCESS WHICH CULMINATES WITH SUBMITTAL OF A FINAL
 COMMISSIONING REPORT.
  
 2) REVISED M1.01 PLAN ERRORS AND OMISSIONS:
 A) KEYNOTE #3 IS BEING USED TO INDICATE BOTH EXHAUST AT
 THE GENERATOR ROOM AND AIR INTAKE OPENING FOR THE LOBBY
 AND CORE ROOMS AND SPACES. THE REQUESTED DAMPER AT THE
 INLET NOT SHOWN- SECTION C403.2.4.3 FBC EC.
 B) AH-DX-1-1 AND AH-DX-1-2 NOT IDENTIFIED- SECTION
 107.2.1 WPB.
 C) AH-DX-1-7 IN THE POWER ROOM NOT SHOWN- SECTION
 107.2.1 WPB.
 D) NOTE #5 INDICATES A FIRE-RATED ENCLOSURE FOR THE
 TANK ROOM MAKE UP AIR DUCT WHICH IS NOT REQUIRED,
 HOWEVER FIRE DAMPERS ARE REQUIRED AT THE DUCT
 PENETRATIONS OF FIRE-RATED WALLS- SECTION 607.5.2 FBC
 M.
 E) THE EXHAUST DUCT RUN FROM THE TANK ROOM TO THE
 EXTERIOR OF THE BUILDING IS NOT SHOWN, AND NO DUCT
 SPECIFICATIONS HAVE BEEN PROVIDED- TYPE AND SIZE OF
 DUCT, TERMINATION LOCATION AND CLEARANCES ETC- SECTION
 510 FBC M.
 F) CONSTRUCTION DETAILS FOR THE FIRE-RATED EXHAUST DUCT
 ENCLOSURE NOT PROVIDED. THE RESPONSE NARRATIVE FROM TLC
 IS CALLING THIS OUT AS AN "INTERSTITIAL WALL". NO NOTES
 ON THE PLAN PROVIDED- SECTION 713.2 FBC B.
 G) THE LETTER DAIKIN CERTIFYING THE INSTALLATIONS OF
 THE OUTDOOR CONDENSERS IN THE ENCLOSED GARAGES IS NOT
 ACCEPTED: 1) IT IS INDICATING THE UNITS ARE TO BE
 INSTALLED IN AN "OPEN GARAGE" AND NOT AN ENCLOSED
 GARAGE. 2) THE LETTER IS FROM BECAUSE A SALES MANAGER,
 AND ALTERNATE DESIGNS AND METHODS MUST BE SUBMITTED BY
 A LICENSED DESIGN PROFESSIONAL. THE MANUFACTURER'S
 TECHNICAL DEPARTMENT CAN PROVIDE INSTALLATION DETAILS
 FOR INDOOR INSTALLATIONS THAT WOULD BE ACCEPTABLE IF
 THE DETAILS BEAR A SHOP DRAWING STAMP OF APPROVAL BY
 THE ENGINEER OF RECORD FOR THE PROJECT. PLEASE NOTE
 THAT THE LETTER MUST ADDRESS ALL THE CONDENSERS ON ALL
 FLOORS THAT ARE BEING INSTALLED IN THE ENCLOSED
 GARAGES- SECTION 304.1 FBC M.
 H) RETURN AIR MISSING FROM THE ENGINEERING ROOM-
 SECTION 601.6 FBC M.
  
 3) REVISED M1.02 PLAN ERRORS AND OMISSIONS:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
  
 4) REVISED M1.03 PLAN ERRORS AND OMISSIONS:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) THE PLAN APPEARS TO SHOW A 4" ROUND DUCT SUPPLYING
 660 CFMS OF CONDITIONED SUPPLY AIR TO THE FUTURE
 OFFICE, HOWEVER THE AIRFLOW ARROW SHOWN BY THE 12X10
 OPENING IS IS MOST LIKELY REVERSED. I'M ASSUMING THIS
 IS SUPPOSED TO INDICATE THE O/A SUPPLY. PLEASE CORRECT
 AND PROVIDE NOTES TO CLARIFY- SECTION 107.2.1 WPB.
 C) NO TEXT HAS BEEN PROVIDED AT KEYED NOTE #6.
  
 5) REVISED M1.04:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) IT APPEARS THE O/A SUPPLY DUCT LAYOUT IS INCOMPLETE.
 NO INLET LOCATION IS SHOWN, NO NOTES- SECTION 107.2.1
 WPB.
  
 6) REVISED M1.05:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) SEE COMMENT #4B ABOVE FOR SIMILAR DEFICIENCY.
  
 7) REVISED M1.06:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1
 WPB.
  
 8) REVISED M1.07:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1
 WPB.
  
 9) REVISED M1.08:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1
 WPB.
  
 10) M1.09: PLACE NOTES ON THE PLAN TO SHOW THE
 LOCATIONS OF THE O/A, THE TOILET EXHAUST, AND THE SMOKE
 EXHAUST SMOKE SHAFTS-
 A) PROVIDE MOTORIZED FIRE/SMOKE DAMPERS AT THE EXHAUST
 AND AIR INLET OPENINGS AT THE SHAFTS- SECTION 607.5.5
 FBC M.
  
 PLEASE NOTE THE FOLLOWING:
 1) SEPARATE PERMITS ARE REQUIRED FOR THE FUTURE
 RESTAURANT AND OFFICES, KITCHEN EXHAUST HOODS AND FIRE
 SUPPRESSION SYSTEM, WALK IN COOLERS AND FREEZERS.
 2) DEFERRED SUBMITTALS
 REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP
 DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME
 OF INSPECTION.
 1) SMOKE CONTROL FANS INCLUDING SMOKE EXHAUST FANS, AND
 STAIRWELL AND ELEVATOR PRESSURIZATION FANS.
 2) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 3) MOTORIZED AND BAROMETRIC DAMPERS
 4) DUCT SMOKE DETECTORS
 5) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 6) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 7) C0, N02, & CO2 SENSORS, AND REFRIGERANT LEAK
 DETECTORS.
 8) COOLING TOWERS
 9) FACTORY BUILT DUCTWORK
 10) DUCT FIRE WRAPPING
 11) CLOTHES DRYERS
 12) COOKING APPLIANCES
 13) TEST AND BALANCE REPORTS
 14) SMOKE CONTROL TEST REPORTS.
  
 SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 1) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR
 DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE
 TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED
 ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE
 STRUCTURAL ENGINEER RECORD.
 2) GENERATORS AND FUEL TANKS AND ALL ASSOCIATED
 EQUIPMENT, VENT FLUES, AND FUEL OIL PIPING.
 3) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR
 DUCTS AND VENT FLUES.
 4) COMMISSIONING REPORTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER