Plan Review Notes
Plan Review Notes For Permit 18090469
Permit Number 18090469
Review Stop P
Sequence Number 2
Notes
Date Text
2019-02-25 15:36:522ND REVIEW: 18090469
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PLEASE SHOW ALL STACKS WITH TAGS ON THE FLOOR PLANS
 SHEETS P1.02-P1.11. PER WPB AMEND TO FBC 107.2.1
 2. THERE IS 2 P9-01 SHEETS THE SHEET FROM 1ST SUBMITTAL
 NEEDS TO BE REMOVED. PER WPB AMEND TO FBC 107.2.1
 3. THE JANITORS SINK AND WATER FOUNTAINS ON THE 18TH
 FLOOR ARE MISSING FROM THE FLOOR PLANS SHEETS P1.10 AND
 P4.11 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 4. PLEASE PROVIDE PIPING DETAIL FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
 5. MANUFACTURE SPECIFICATIONS FOR THE FUEL OIL SYSTEM
 AND TANKS AND GENERATOR IS REQUIRED FOR APPROVAL. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  