Plan Review Notes
Plan Review Notes For Permit 18090469
Permit Number 18090469
Review Stop E
Sequence Number 2
Notes
Date Text
2019-02-12 15:46:30FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE 446 T5.03
  
 RISER FOR FIBER OPTIC CABLE IS USING THE STAIRWELL TO
 GET TO THE UPPER FLOORS. STAIRWELL CAN NOT BE USED AS
 AMEANS TO RUN CABLE THROUGH A BUILDING
  
 FIREMAN'S COMMUNICATION SYSTEM PENETRATES THE STAIRWELL
 MORE THAN ONE TIME.
  
  
 PER FBC B1023.5 (6TH EDITION 2017) PENETRATIONS IN THE
 STAIRWELLS ARE FORBIDDEN. PLEASE VERIFY RISER WILL NOT
 BE USING STAIRWELLS AS A RACEWAY.
  
  
  