2019-02-27 13:56:13 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18090469 |
| 2 ND REVIEW: FEBRUARY 21, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| |
| 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18090469 |
| ADD: 360 ROSEMARY AVE. / PCN: 74-43-43-21-01-022-0040 |
| CONT: MOSS & ASSOCIATES LLC |
| TEL: 954-524-5678 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 1ST REVIEW |
| DATE: MONDAY DEC.10TH/ 2018. COMPLETED REVIEW. |
| ACTION: DENIED |
| |
| 1) OK. |
| 2A-B) OK. |
| 3A-B) OK. |
| 3C-D) OK. |
| 4) OK. |
| 5) OK. |
| 6) OK. |
| 7) OK. |
| |
| 8) IN-PROGRESS |
| 8A-F) IN-PROGRESS |
| |
| 8G) SHORING AND RESHORING WILL NEED TO BE SUPPLIED AS |
| SUBMITTAL. |
| |
| 8H-I) OK. |
| 9) OK. |
| 10) OK. |
| 10A-N) OK. |
| |
| 10O) 008-LS1.01. OK. |
| NEW COMMENT 2 ND REVIEW: |
| 10O) 1006.2.1 FBC[B] EGRESS BASED ON OCCUPANT LOAD AND |
| COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO EXITS OR |
| EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED |
| WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF |
| EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN |
| TABLE 1006.2.1. |
| LOADING DOCK SUPPLIES 1 MARKED EXIT, BUT EXCEEDS TABLE |
| 1006.2.1 FOR REQUIREMENTS OF SPACE WITH ONE EXIT. |
| PLEASE REVIEW LOADING DOCK EGRESS REQUIREMENTS. |
| |
| NO EXIT SIGNS ARE PROVIDED ON LIFE SAFETY, SO COMMENTS |
| ARE USING E SHEETS FOR CROSS REFERENCE. CAN EXIT SIGNS |
| BE ADDED TO LIFE SAFETY FOR CLARITY? |
| |
| 10O) 1013.2 FBC[B] EXIT SIGN PLACEMENT SHALL BE SUCH |
| THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT |
| PASSAGEWAY IS MORE THAN 100 FEET OR THE LISTED VIEWING |
| DISTANCE FOR THE SIGN, WHICHEVER IS LESS, FROM THE |
| NEAREST VISIBLE EXIT SIGN. |
| VERIFY EXIT SIGN PLACEMENT WITH LS SHEETS. |
| |
| 10P) OK. |
| 10Q) OK. |
| |
| 10Q)(2) SUBMITTAL NEEDED FOR 6" CMU |
| |
| 10R) OK. |
| 10R)(1) OK. |
| 10R)(2) OK. |
| |
| 10S) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE |
| ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE |
| PLAN LEVEL 1 SHOW COMPLIANCE FOR: |
| |
| 10S)(1) 2017 FBC-B 403.6.1 FIRE SERVICE ACCESS |
| ELEVATOR. NO FEWER THAN TWO FIRE SERVICE ACCESS |
| ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| 3007 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120 |
| FEET MEASURED FROM THE ELEVATION OF THE STREET LEVEL |
| ACCESS. |
| COMMENT NOT ADDRESSED. SHEET LS1.01 IS SHOWING ONE |
| SERVICE ELEVATOR PLEASE SHOW HOW TWO FIRE SERVICE |
| ELEVATORS ARE PROVIDED. |
| |
| 10S)(2) 2017 FBC-B 2017 FBC-B 403.6.1 FIRE SERVICE |
| ACCESS ELEVATOR. PLEASE SHOW COMPLIANCE WITH EACH FIRE |
| SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF NOT |
| LESS THAN 3,500 POUNDS. |
| |
| 10S-T) OK. |
| |
| THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8) |
| THROUGH 11H |
| PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS. |
| |
| 10T)(8) PLEASE NOTE THE STAIRWAY #2 AN INTERIOR EXIT |
| STAIRWAY THAT IS CONTINUOUS TO THE EXTERIOR DOES NOT |
| SHOW STAIRWELL PRESSURIZATION, SMOKEPROOF ENCLOSURES, |
| IN ANY OF THE MECHANICAL PLANS, SEE 2017 FBC-B 1023.11 |
| SMOKEPROOF ENCLOSURES. WHERE REQUIRED BY SECTION |
| 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND RAMPS |
| SHALL BE SMOKEPROOF ENCLOSURES IN ACCORDANCE WITH |
| SECTION 909.20. |
| 11) LEVEL 2: 09LS1.02, 135-AE1.02, & 190/191 AE4.02 A & |
| B: |
| |
| 11A)(1) THE LIFE SAFETY SHEET ANALYSIS, NOR LS1, NOR |
| LS2 SHOW AN ANALYSIS OF THE PARKING STRUCTURE, HOW MANY |
| TOTAL PARKING SPACES THERE IS OR HOW MANY ACCESSIBLE |
| PARKING SPACES THERE IS OR COMPLIANCE WITH THE 2017 |
| FBC-ACCESSIBLE PARKING SPACES. SHOW ACCESSIBLE MATRIX. |
| |
| 11A)(2) SHEET 135-AE1.02 THE OVERALL FLOOR PLAN FOR |
| LEVEL 2 SHOWS 4 ACCESSIBLE PARKING SPACES, 3 ACCESSIBLE |
| SPACES. SHOW THE ACCESSIBLE ROUTE FOR A WHEEL CHAIR TO |
| BE ABLE TO GET TO AN ELEVATOR WITHOUT HAVING TO GO OUT |
| INTO THE VEHICULAR TRAVEL LANE. ACCESSIBILITY CODE |
| SECTION 206.2. WHERE REQUIRED. AN |
| ACCESSIBLE ROUTE SHALL BE PROVIDED WHERE REQUIRED BY |
| 206.2. |
| 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE |
| SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE |
| FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES |
| THAT ARE ON THE SAME SITE. |
| |
| 11B) COMMENT FOR ALL PARKING FLOORS. PLEASE ALSO SHOW |
| COMPLIANCE WITH SECTION 208.2.4. VAN PARKING SPACES. |
| WHERE VAN PARKING IS PROVIDED PURSUANT TO SECTION |
| 502.2, FOR EVERY SIX OR FRACTION OF SIX PARKING SPACES |
| REQUIRED BY 208.2 TO COMPLY WITH 502, AT LEAST ONE |
| SHALL BE A VAN PARKING SPACE COMPLYING WITH 502. |
| |
| 11C) COMMENT FOR ALL PARKING FLOORS. SHEET 182-AE3.18 |
| BUILDING SECTION. THE PLAN SHOWS ELEVATIONS OF THE |
| VARIOUS FLOOR LEVELS AND BY MEASURING BETWEEN FLOOR |
| SLABS IT WOULD APPEAR THERE MAYBE ONLY 7 FEET 8 INCHES |
| FROM THE BOTTOM OF THE FLOOR PRECAST AND FINISH FLOOR |
| BELOW. PLEASE PROVIDE THE CLEAR HEIGHT BETWEEN FLOOR |
| SLABS AND THE PRECAST FLOOR JOIST ABOVE, AND ALSO |
| PROVIDE FOR THE FIRE SPRINKLERS TO HAVE A TRUE HEIGHT |
| FOR THE RAMPS AND FOR THE PARKING AREAS. PLEASE SHOW |
| HOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE SECTION |
| 502.5 VERTICAL CLEARANCE. PARKING SPACES FOR VANS AND |
| ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM SHALL |
| PROVIDE A VERTICAL CLEARANCE OF 98 INCHES MINIMUM. |
| |
| 11D) PLEASE REVIEW SHEET 270-AE5.39 PARKING DETAILS. |
| PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE SEE THE |
| ADVISORY 502.3.3 MARKING. |
| 2017 ACCESSIBILITY CODE. ADVISORY 502.3.3 MARKING. THE |
| METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY THESE |
| REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL |
| LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS PERMIT |
| THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING SPACE, |
| IT IS IMPORTANT THAT THE AISLE BE CLEARLY MARKED. |
| FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL |
| STRIPING OF ACCESS AISLES. |
| PLEASE REFER TO THE WEST PALM BEACH MUNI CODE 94-485 |
| FOR STALL PAINTING DETAILS AND REQUIRED DOUBLE LINE |
| DIMENSIONS. |
| |
| 11E) THE 2ND LEVEL FLOOR PLAN, : 09LS1.02, 135-AE1.02, |
| & 190/191 AE4.02 A & B: WILL NEED TO PROVIDE WHAT THE |
| DESIGN FOR THE PARKING FLOORS, IF THESE FLOOR LEVELS |
| ARE TO BE CONSIDERED AN OPEN OR ENCLOSED PARKING |
| GARAGE? SHOW COMPLIANCE WITH FBC-B 406.5 OPEN PARKING |
| GARAGES OR 406.6ENCLOSED PARKING GARAGES. |
| IF CONSIDERED OPEN SHOW COMPLIANCE ON THE ELEVATION |
| SHEETS AE2.10 THROUGH AE2.22. PLEASE SHOW THE WALL AREA |
| IN SQ. FEET. THE OPENING IN SQUARE FEET, PERCENTAGE OF |
| OPENING, DEDUCT FOR THE ALUMINUM ARCHITECTURAL SCREEN |
| AND TAKE A SECOND DEDUCTION FOR THE BIRD SCREEN AS |
| WELL. SHOW COMPLIANCE WITH 406.5.2 OPENINGS OF THE 2017 |
| FBC-B AND 406.5.6 FIRE SEPARATION DISTANCE CONCERNS |
| WITH SOUTH WALL ON GRID LINES F-H SHEET 182AE3.18 SHOWS |
| THIS AREA OF THE PARKING GARAGE EXTENDED OVER THE 1ST |
| FLOOR LEVEL. |
| |
| 11F) BOTH SHEETS 135-AE1.02 LEVEL 2 AND 190AE4.02 BOTH |
| SHOW ATTENDANT BOOTHS AND A GATED ENTRANCE TO THE |
| PARKING LEVELS. |
| |
| 11F)(1) PLEASE SHOW CUT SECTIONS FOR THE ATTENDANT |
| BOOTHS OF HOW THEY ARE GOING TO BE ANCHORED FOR THE |
| WIND, DOES THE WIND TUNNEL TEST HAVE A PRESSURE POINT |
| FOR THE BOOTHS, IF NOT HOW ARE PRESSURES TO BE DERIVED? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B |
| 1609.1.1 DETERMINATION OF WIND LOADS. |
| |
| 11F)(2) ADDITIONAL INFORMATION IS REQUIRED FOR THE |
| ATTENDANT BOOTHS, ARE THESE BOOTHS PRE-MANUFACTURERED |
| (MODULAR) BUILDINGS UNDER FLORIDA S. 553 PART I |
| MANUFACTURED BUILDINGS? |
| |
| 11G) THE PLANS ALSO SHOW USE OF VEHICULAR GATES. IF |
| THEY USE KEY CARDS THE THEY WOULD ALSO BE CONSIDERED |
| AUTOMATIC VEHICULAR GATES HAVING TO COMPLY WITH: FBC-B |
| 3110.1 AUTOMATIC VEHICULAR GATES SHALL COMPLY WITH THE |
| REQUIREMENTS OF SECTIONS 3110.2 THROUGH 3110.4 AND |
| OTHER APPLICABLE SECTIONS OF THIS CODE. |
| |
| 11H) OFFICE 202, AREA OF 5,812 SQ. FT. AND FUTURE |
| RESTROOMS MAY BE AT THE OWNERS OWN RISK!!!! DEPENDING |
| ON IF THE OFFICE AREA IS SUB-DIVIDED IN TO 2 TENANTS |
| AND THE LARGER OF THE 2 TENANTS HAS OVER 49 OCCUPANTS |
| THEN 2 EXITS WOULD BE REQUIRED. 2017 FBC-B TABLE |
| 1006.2.1 .SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY. |
| |
| THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8) |
| THROUGH 11H |
| PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS. |
| |
| 11I) OK. |
| 11J) OK. |
| 12) OK. |
| 12A) OK. |
| |
| 12B) OK. SUBMITTAL FOR SIGNAGE TO BE DEFERRED. |
| |
| 12C) OK. |
| |
| 12D) CONCRETE PEDESTAL PAVER SYSTEMS SPECIALTY |
| ENGINEERED SUBMITTAL TO BE DEFERRED. |
| |
| 13) OK. |
| |
| 13A) WASHING EQUIPMENT TIE DOWNS TO BE DEFERRED |
| SUBMITTAL. |
| |
| 13B) METAL STAIRS, METAL |
| PLATFORM AND GUARDRAIL SYSTEM AT ROOF TO BE A DEFERRED |
| SUBMITTAL. |
| |
| 14) OK. |
| PLEASE PROVIDE FULL LIST OF DEFERRED SUBMITTALS ON |
| CONSTRUCTION DOCUMENTS, OR INDICATE WHICH PAGE THE LIST |
| IS CURRENTLY ON. |
| |
| 15A-B) OK. |
| 15B) OK |
| |
| 16) OK. |
| |
| 17) OK. |
| 18) OK |
| 19) OK |
| |
| 20) OK. |
| 21) OK. |
| 22) OK. |
| |
| 23) FOR ELECTRONIC REVIEWS. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8) |
| THROUGH 11H |
| PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |