Plan Review Notes
Plan Review Notes For Permit 18090469
Permit Number 18090469
Review Stop B
Sequence Number 2
Notes
Date Text
2019-02-27 13:56:13****CORRECTIONS****
 W.P.B. PERMIT: 18090469
 2 ND REVIEW: FEBRUARY 21, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090469
 ADD: 360 ROSEMARY AVE. / PCN: 74-43-43-21-01-022-0040
 CONT: MOSS & ASSOCIATES LLC
 TEL: 954-524-5678
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: MONDAY DEC.10TH/ 2018. COMPLETED REVIEW.
 ACTION: DENIED
  
 1) OK.
 2A-B) OK.
 3A-B) OK.
 3C-D) OK.
 4) OK.
 5) OK.
 6) OK.
 7) OK.
  
 8) IN-PROGRESS
 8A-F) IN-PROGRESS
  
 8G) SHORING AND RESHORING WILL NEED TO BE SUPPLIED AS
 SUBMITTAL.
  
 8H-I) OK.
 9) OK.
 10) OK.
 10A-N) OK.
  
 10O) 008-LS1.01. OK.
 NEW COMMENT 2 ND REVIEW:
 10O) 1006.2.1 FBC[B] EGRESS BASED ON OCCUPANT LOAD AND
 COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO EXITS OR
 EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED
 WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF
 EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN
 TABLE 1006.2.1.
 LOADING DOCK SUPPLIES 1 MARKED EXIT, BUT EXCEEDS TABLE
 1006.2.1 FOR REQUIREMENTS OF SPACE WITH ONE EXIT.
 PLEASE REVIEW LOADING DOCK EGRESS REQUIREMENTS.
  
 NO EXIT SIGNS ARE PROVIDED ON LIFE SAFETY, SO COMMENTS
 ARE USING E SHEETS FOR CROSS REFERENCE. CAN EXIT SIGNS
 BE ADDED TO LIFE SAFETY FOR CLARITY?
  
 10O) 1013.2 FBC[B] EXIT SIGN PLACEMENT SHALL BE SUCH
 THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT
 PASSAGEWAY IS MORE THAN 100 FEET OR THE LISTED VIEWING
 DISTANCE FOR THE SIGN, WHICHEVER IS LESS, FROM THE
 NEAREST VISIBLE EXIT SIGN.
 VERIFY EXIT SIGN PLACEMENT WITH LS SHEETS.
  
 10P) OK.
 10Q) OK.
  
 10Q)(2) SUBMITTAL NEEDED FOR 6" CMU
  
 10R) OK.
 10R)(1) OK.
 10R)(2) OK.
  
 10S) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE
 ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE
 PLAN LEVEL 1 SHOW COMPLIANCE FOR:
  
 10S)(1) 2017 FBC-B 403.6.1 FIRE SERVICE ACCESS
 ELEVATOR. NO FEWER THAN TWO FIRE SERVICE ACCESS
 ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120
 FEET MEASURED FROM THE ELEVATION OF THE STREET LEVEL
 ACCESS.
 COMMENT NOT ADDRESSED. SHEET LS1.01 IS SHOWING ONE
 SERVICE ELEVATOR PLEASE SHOW HOW TWO FIRE SERVICE
 ELEVATORS ARE PROVIDED.
  
 10S)(2) 2017 FBC-B 2017 FBC-B 403.6.1 FIRE SERVICE
 ACCESS ELEVATOR. PLEASE SHOW COMPLIANCE WITH EACH FIRE
 SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF NOT
 LESS THAN 3,500 POUNDS.
  
 10S-T) OK.
  
 THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8)
 THROUGH 11H
 PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS.
  
 10T)(8) PLEASE NOTE THE STAIRWAY #2 AN INTERIOR EXIT
 STAIRWAY THAT IS CONTINUOUS TO THE EXTERIOR DOES NOT
 SHOW STAIRWELL PRESSURIZATION, SMOKEPROOF ENCLOSURES,
 IN ANY OF THE MECHANICAL PLANS, SEE 2017 FBC-B 1023.11
 SMOKEPROOF ENCLOSURES. WHERE REQUIRED BY SECTION
 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND RAMPS
 SHALL BE SMOKEPROOF ENCLOSURES IN ACCORDANCE WITH
 SECTION 909.20.
 11) LEVEL 2: 09LS1.02, 135-AE1.02, & 190/191 AE4.02 A &
 B:
  
 11A)(1) THE LIFE SAFETY SHEET ANALYSIS, NOR LS1, NOR
 LS2 SHOW AN ANALYSIS OF THE PARKING STRUCTURE, HOW MANY
 TOTAL PARKING SPACES THERE IS OR HOW MANY ACCESSIBLE
 PARKING SPACES THERE IS OR COMPLIANCE WITH THE 2017
 FBC-ACCESSIBLE PARKING SPACES. SHOW ACCESSIBLE MATRIX.
  
 11A)(2) SHEET 135-AE1.02 THE OVERALL FLOOR PLAN FOR
 LEVEL 2 SHOWS 4 ACCESSIBLE PARKING SPACES, 3 ACCESSIBLE
 SPACES. SHOW THE ACCESSIBLE ROUTE FOR A WHEEL CHAIR TO
 BE ABLE TO GET TO AN ELEVATOR WITHOUT HAVING TO GO OUT
 INTO THE VEHICULAR TRAVEL LANE. ACCESSIBILITY CODE
 SECTION 206.2. WHERE REQUIRED. AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED WHERE REQUIRED BY
 206.2.
 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE
 FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES
 THAT ARE ON THE SAME SITE.
  
 11B) COMMENT FOR ALL PARKING FLOORS. PLEASE ALSO SHOW
 COMPLIANCE WITH SECTION 208.2.4. VAN PARKING SPACES.
 WHERE VAN PARKING IS PROVIDED PURSUANT TO SECTION
 502.2, FOR EVERY SIX OR FRACTION OF SIX PARKING SPACES
 REQUIRED BY 208.2 TO COMPLY WITH 502, AT LEAST ONE
 SHALL BE A VAN PARKING SPACE COMPLYING WITH 502.
  
 11C) COMMENT FOR ALL PARKING FLOORS. SHEET 182-AE3.18
 BUILDING SECTION. THE PLAN SHOWS ELEVATIONS OF THE
 VARIOUS FLOOR LEVELS AND BY MEASURING BETWEEN FLOOR
 SLABS IT WOULD APPEAR THERE MAYBE ONLY 7 FEET 8 INCHES
 FROM THE BOTTOM OF THE FLOOR PRECAST AND FINISH FLOOR
 BELOW. PLEASE PROVIDE THE CLEAR HEIGHT BETWEEN FLOOR
 SLABS AND THE PRECAST FLOOR JOIST ABOVE, AND ALSO
 PROVIDE FOR THE FIRE SPRINKLERS TO HAVE A TRUE HEIGHT
 FOR THE RAMPS AND FOR THE PARKING AREAS. PLEASE SHOW
 HOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE SECTION
 502.5 VERTICAL CLEARANCE. PARKING SPACES FOR VANS AND
 ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM SHALL
 PROVIDE A VERTICAL CLEARANCE OF 98 INCHES MINIMUM.
  
 11D) PLEASE REVIEW SHEET 270-AE5.39 PARKING DETAILS.
 PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE SEE THE
 ADVISORY 502.3.3 MARKING.
 2017 ACCESSIBILITY CODE. ADVISORY 502.3.3 MARKING. THE
 METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY THESE
 REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL
 LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS PERMIT
 THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING SPACE,
 IT IS IMPORTANT THAT THE AISLE BE CLEARLY MARKED.
 FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL
 STRIPING OF ACCESS AISLES.
 PLEASE REFER TO THE WEST PALM BEACH MUNI CODE 94-485
 FOR STALL PAINTING DETAILS AND REQUIRED DOUBLE LINE
 DIMENSIONS.
  
 11E) THE 2ND LEVEL FLOOR PLAN, : 09LS1.02, 135-AE1.02,
 & 190/191 AE4.02 A & B: WILL NEED TO PROVIDE WHAT THE
 DESIGN FOR THE PARKING FLOORS, IF THESE FLOOR LEVELS
 ARE TO BE CONSIDERED AN OPEN OR ENCLOSED PARKING
 GARAGE? SHOW COMPLIANCE WITH FBC-B 406.5 OPEN PARKING
 GARAGES OR 406.6ENCLOSED PARKING GARAGES.
 IF CONSIDERED OPEN SHOW COMPLIANCE ON THE ELEVATION
 SHEETS AE2.10 THROUGH AE2.22. PLEASE SHOW THE WALL AREA
 IN SQ. FEET. THE OPENING IN SQUARE FEET, PERCENTAGE OF
 OPENING, DEDUCT FOR THE ALUMINUM ARCHITECTURAL SCREEN
 AND TAKE A SECOND DEDUCTION FOR THE BIRD SCREEN AS
 WELL. SHOW COMPLIANCE WITH 406.5.2 OPENINGS OF THE 2017
 FBC-B AND 406.5.6 FIRE SEPARATION DISTANCE CONCERNS
 WITH SOUTH WALL ON GRID LINES F-H SHEET 182AE3.18 SHOWS
 THIS AREA OF THE PARKING GARAGE EXTENDED OVER THE 1ST
 FLOOR LEVEL.
  
 11F) BOTH SHEETS 135-AE1.02 LEVEL 2 AND 190AE4.02 BOTH
 SHOW ATTENDANT BOOTHS AND A GATED ENTRANCE TO THE
 PARKING LEVELS.
  
 11F)(1) PLEASE SHOW CUT SECTIONS FOR THE ATTENDANT
 BOOTHS OF HOW THEY ARE GOING TO BE ANCHORED FOR THE
 WIND, DOES THE WIND TUNNEL TEST HAVE A PRESSURE POINT
 FOR THE BOOTHS, IF NOT HOW ARE PRESSURES TO BE DERIVED?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B
 1609.1.1 DETERMINATION OF WIND LOADS.
  
 11F)(2) ADDITIONAL INFORMATION IS REQUIRED FOR THE
 ATTENDANT BOOTHS, ARE THESE BOOTHS PRE-MANUFACTURERED
 (MODULAR) BUILDINGS UNDER FLORIDA S. 553 PART I
 MANUFACTURED BUILDINGS?
  
 11G) THE PLANS ALSO SHOW USE OF VEHICULAR GATES. IF
 THEY USE KEY CARDS THE THEY WOULD ALSO BE CONSIDERED
 AUTOMATIC VEHICULAR GATES HAVING TO COMPLY WITH: FBC-B
 3110.1 AUTOMATIC VEHICULAR GATES SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTIONS 3110.2 THROUGH 3110.4 AND
 OTHER APPLICABLE SECTIONS OF THIS CODE.
  
 11H) OFFICE 202, AREA OF 5,812 SQ. FT. AND FUTURE
 RESTROOMS MAY BE AT THE OWNERS OWN RISK!!!! DEPENDING
 ON IF THE OFFICE AREA IS SUB-DIVIDED IN TO 2 TENANTS
 AND THE LARGER OF THE 2 TENANTS HAS OVER 49 OCCUPANTS
 THEN 2 EXITS WOULD BE REQUIRED. 2017 FBC-B TABLE
 1006.2.1 .SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY.
  
 THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8)
 THROUGH 11H
 PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS.
  
 11I) OK.
 11J) OK.
 12) OK.
 12A) OK.
  
 12B) OK. SUBMITTAL FOR SIGNAGE TO BE DEFERRED.
  
 12C) OK.
  
 12D) CONCRETE PEDESTAL PAVER SYSTEMS SPECIALTY
 ENGINEERED SUBMITTAL TO BE DEFERRED.
  
 13) OK.
  
 13A) WASHING EQUIPMENT TIE DOWNS TO BE DEFERRED
 SUBMITTAL.
  
 13B) METAL STAIRS, METAL
 PLATFORM AND GUARDRAIL SYSTEM AT ROOF TO BE A DEFERRED
 SUBMITTAL.
  
 14) OK.
 PLEASE PROVIDE FULL LIST OF DEFERRED SUBMITTALS ON
 CONSTRUCTION DOCUMENTS, OR INDICATE WHICH PAGE THE LIST
 IS CURRENTLY ON.
  
 15A-B) OK.
 15B) OK
  
 16) OK.
  
 17) OK.
 18) OK
 19) OK
  
 20) OK.
 21) OK.
 22) OK.
  
 23) FOR ELECTRONIC REVIEWS. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8)
 THROUGH 11H
 PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  