2018-12-10 11:37:371ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC ACC
 2017 6TH EDITION.
 A) 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION.
 B) 604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL. SHOW DIMENSIONS ON CLEAR FLOOR
 SPACE.
 C) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM
 FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM
 THE REAR WALL.
 E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
 F) 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR.
 H) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 I) 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
 J) 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 K) THE SHOWER IN THE MANAGERS BATHROOM ON THE 1ST FLOOR
 SHALL COMPLY WITH ONE OF THE FOLLOWING.
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.TRANSFER TYPE
 SHOWER COMPARTMENTS SHALL BE 36 INCHES BY 36 INCHES
 CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS
 OF OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 608.2.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS
 SHALL BE 30 INCHES WIDE MINIMUM BY 60 INCHES DEEP
 MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENTS.ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS
 SHALL BE 36 INCHES WIDE AND 60 INCHES DEEP MINIMUM
 CLEAR INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF
 OPPOSING SIDES.A 36 INCH WIDE MINIMUM ENTRY SHALL BE
 PROVIDED AT ONE END OF THE LONG SIDE OF THE
 COMPARTMENT.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE FUEL OIL
 FILL STATION, AUTOMATIC FUEL POLISHER, WATER HEATER,
 ELEVATOR SUMP PUMP, GREASE INTERCEPTOR AND DOMESTIC
 WATER BOOSTER PUMP.
  
 3. SHT. P1.01 THE BACK PREVENTER'S ON THE DOMESTIC
 WATER MAIN AND FIRE LINE MAINS SHALL BE INSTALLED AS
 CLOSE AS POSSIBLE TO THE WATER METERS. PLEASE CONTACT
 DAVE PEARSON 822-2242 WPB UTILITIES DEPT.
  
 4. PLEASE PLACE NOTES ON THE PLAN SEPARATE PERMITS ARE
 REQUIRED FOR BACKFLOWS, GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
  
 5. THE PLAN SHOWS 3000 GAL. GREASE INTERCEPTOR THE
 MAXIMUM SIZE ALLOWED IN WPB IS 1250 GAL. PLEASE CONTACT
 JEFFERY ODOMS 822-2172 WPB UTILITIES DEPT.
  
 6. PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTORS. PER WPB AMEND TO FBC 107.2.1
  
 7. SANITARY FACILITY'S WILL BE REQUIRED FOR THE RETAIL
 SPACE ON FST FLOOR WILL THERE BE ANY ROUGH PIPING
 INSTALLED ON THIS PROJECT. PER FBC PL 403.1
  
 8. PLEASE LABEL ALL STACKS AND RISERS ON THE FLOOR
 PLANS AND ISOMETRIC DRAWINGS FOR THE SANITARY, WATER
 AND STORM DRAIN. WPB AMEND TO FBC 107.2.1
  
 9. WHAT IS THE CONDENSATE RECYCLED WATER BEING USED FOR
 PLEASE PROVIDE PIPING DIAGRAM AND SHOW PIPING ON FLOOR
 PLAN. WPB AMEND TO FBC 107.2.1
  
 10. SHTS. P-1.02 THRU P-1.10 SHOW PIPING SIZES AND
 LABEL STACKS. WPB AMEND TO FBC 107.2.1
  
 11. SHT P-1.10 SHOWS A NOTE THAT STATES 4"
 STORM/OVERFLOW FROM ABOVE BUT NO PIPING IS SHOWN PLEASE
 CLARIFY. WPB AMEND TO FBC 107.2.1
  
 12. SHT. SHT. P4.01 PLEASE CLARIFY WHAT G.C.O. STANDS
 FOR. LOCATED BETWEEN LINE F AND G. WPB AMEND TO FBC
 107.2.1
  
 13. PROVIDE PLUMBING FIXTURE BREAKDOWN PER FLOOR. WPB
 AMEND TO FBC 107.2.1
  
 14. SHT. P-4.02B A WATER FOUNTAIN IS REQUIRED FOR
 OFFICE SPACE. PER FBC PL TABLE 403.1
  
 15. THE THERMOSTATIC MIXING VALVE FOR THE TEMPERED
 WATER TO THE LAVATORY'S SHALL COMPLY WITH ASSE 1070
 PLEASE PROVIDE MANUFACTURES SPECIFICATIONS TO VERIFY
 COMPLIANCE. PER FBC PL 416.5
  
 16. SHT. P5.02 THE POLISHING SYSTEM FOR THE FUEL OILS
 NOT SHOWN AS BEING PIPED INTO THE REST OF THE SYSTEM
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 17. PROVIDE THE MSDS SHEETS FOR THE FUEL OIL USED BY
 GENERATOR. . PER WPB AMEND TO FBC 107.2.1
  
 18. SHT. P-9.02 SHOW ON THE PLAN THE PIPE SLOPE AND ON
 THE PIPE ITSELF SHOW THE SQFT AND OR GPM. . PER WPB
 AMEND TO FBC 107.2.1
  
 19. PROVIDE A SANITARY COLLECTION ISOMETRIC DRAWING. .
 PER WPB AMEND TO FBC 107.2.1
  
 20. PROVIDE A COMPLETE WATER ISOMETRIC DRAWING. . PER
 WPB AMEND TO FBC 107.2.1
  
 21. PROVIDE DETAIL TO SHOW COMPLIANCE WITH FBC PL
 308.6 SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE
 PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45
 DEGREES (0.79 RAD) FOR PIPE SIZES 4 INCHES AND LARGER.
 308.7 ANCHORAGE. ANCHORAGE SHALL BE PROVIDED TO
 RESTRAIN DRAINAGE PIPING FROM AXIAL MOVEMENT.
 308.7.1 LOCATION. FOR PIPE SIZES GREATER THAN 4 INCHES
 , RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL
 CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER
 GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING
 AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING
 MANUFACTURER SHALL BE UTILIZED.
 PER WPB AMEND TO FBC 107.2.1
  
 22. SHT. P-4.09 SHOW DISTANCE OF SANITARY VENTS FROM
 AIR INTAKES MUST BE MIN. OF 10'. PER FBC PL 903.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711