2018-12-10 11:37:37 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC ACC |
| 2017 6TH EDITION. |
| A) 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED |
| WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| PARTITION. |
| B) 604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL |
| BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE |
| SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR |
| FROM THE REAR WALL. SHOW DIMENSIONS ON CLEAR FLOOR |
| SPACE. |
| C) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE |
| THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 |
| INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42 |
| INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM |
| FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM |
| THE REAR WALL. |
| E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36 |
| INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF |
| THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 |
| INCHES MINIMUM ON THE OTHER SIDE. |
| F) 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE |
| INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM) |
| MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. |
| G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL |
| COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 |
| INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| MAXIMUM ABOVE THE FINISH FLOOR. |
| H) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR |
| COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| I) 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE |
| COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| PROVIDED. |
| J) 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED |
| WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| K) THE SHOWER IN THE MANAGERS BATHROOM ON THE 1ST FLOOR |
| SHALL COMPLY WITH ONE OF THE FOLLOWING. |
| 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.TRANSFER TYPE |
| SHOWER COMPARTMENTS SHALL BE 36 INCHES BY 36 INCHES |
| CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS |
| OF OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM |
| ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE |
| OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM |
| MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED. |
| 608.2.2 STANDARD ROLL-IN TYPE SHOWER |
| COMPARTMENTS.STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS |
| SHALL BE 30 INCHES WIDE MINIMUM BY 60 INCHES DEEP |
| MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES |
| WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER |
| COMPARTMENT. |
| 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER |
| COMPARTMENTS.ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS |
| SHALL BE 36 INCHES WIDE AND 60 INCHES DEEP MINIMUM |
| CLEAR INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF |
| OPPOSING SIDES.A 36 INCH WIDE MINIMUM ENTRY SHALL BE |
| PROVIDED AT ONE END OF THE LONG SIDE OF THE |
| COMPARTMENT. |
| |
| 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE FUEL OIL |
| FILL STATION, AUTOMATIC FUEL POLISHER, WATER HEATER, |
| ELEVATOR SUMP PUMP, GREASE INTERCEPTOR AND DOMESTIC |
| WATER BOOSTER PUMP. |
| |
| 3. SHT. P1.01 THE BACK PREVENTER'S ON THE DOMESTIC |
| WATER MAIN AND FIRE LINE MAINS SHALL BE INSTALLED AS |
| CLOSE AS POSSIBLE TO THE WATER METERS. PLEASE CONTACT |
| DAVE PEARSON 822-2242 WPB UTILITIES DEPT. |
| |
| 4. PLEASE PLACE NOTES ON THE PLAN SEPARATE PERMITS ARE |
| REQUIRED FOR BACKFLOWS, GREASE INTERCEPTORS. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 5. THE PLAN SHOWS 3000 GAL. GREASE INTERCEPTOR THE |
| MAXIMUM SIZE ALLOWED IN WPB IS 1250 GAL. PLEASE CONTACT |
| JEFFERY ODOMS 822-2172 WPB UTILITIES DEPT. |
| |
| 6. PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTORS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 7. SANITARY FACILITY'S WILL BE REQUIRED FOR THE RETAIL |
| SPACE ON FST FLOOR WILL THERE BE ANY ROUGH PIPING |
| INSTALLED ON THIS PROJECT. PER FBC PL 403.1 |
| |
| 8. PLEASE LABEL ALL STACKS AND RISERS ON THE FLOOR |
| PLANS AND ISOMETRIC DRAWINGS FOR THE SANITARY, WATER |
| AND STORM DRAIN. WPB AMEND TO FBC 107.2.1 |
| |
| 9. WHAT IS THE CONDENSATE RECYCLED WATER BEING USED FOR |
| PLEASE PROVIDE PIPING DIAGRAM AND SHOW PIPING ON FLOOR |
| PLAN. WPB AMEND TO FBC 107.2.1 |
| |
| 10. SHTS. P-1.02 THRU P-1.10 SHOW PIPING SIZES AND |
| LABEL STACKS. WPB AMEND TO FBC 107.2.1 |
| |
| 11. SHT P-1.10 SHOWS A NOTE THAT STATES 4" |
| STORM/OVERFLOW FROM ABOVE BUT NO PIPING IS SHOWN PLEASE |
| CLARIFY. WPB AMEND TO FBC 107.2.1 |
| |
| 12. SHT. SHT. P4.01 PLEASE CLARIFY WHAT G.C.O. STANDS |
| FOR. LOCATED BETWEEN LINE F AND G. WPB AMEND TO FBC |
| 107.2.1 |
| |
| 13. PROVIDE PLUMBING FIXTURE BREAKDOWN PER FLOOR. WPB |
| AMEND TO FBC 107.2.1 |
| |
| 14. SHT. P-4.02B A WATER FOUNTAIN IS REQUIRED FOR |
| OFFICE SPACE. PER FBC PL TABLE 403.1 |
| |
| 15. THE THERMOSTATIC MIXING VALVE FOR THE TEMPERED |
| WATER TO THE LAVATORY'S SHALL COMPLY WITH ASSE 1070 |
| PLEASE PROVIDE MANUFACTURES SPECIFICATIONS TO VERIFY |
| COMPLIANCE. PER FBC PL 416.5 |
| |
| 16. SHT. P5.02 THE POLISHING SYSTEM FOR THE FUEL OILS |
| NOT SHOWN AS BEING PIPED INTO THE REST OF THE SYSTEM |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 17. PROVIDE THE MSDS SHEETS FOR THE FUEL OIL USED BY |
| GENERATOR. . PER WPB AMEND TO FBC 107.2.1 |
| |
| 18. SHT. P-9.02 SHOW ON THE PLAN THE PIPE SLOPE AND ON |
| THE PIPE ITSELF SHOW THE SQFT AND OR GPM. . PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 19. PROVIDE A SANITARY COLLECTION ISOMETRIC DRAWING. . |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 20. PROVIDE A COMPLETE WATER ISOMETRIC DRAWING. . PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 21. PROVIDE DETAIL TO SHOW COMPLIANCE WITH FBC PL |
| 308.6 SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE |
| PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45 |
| DEGREES (0.79 RAD) FOR PIPE SIZES 4 INCHES AND LARGER. |
| 308.7 ANCHORAGE. ANCHORAGE SHALL BE PROVIDED TO |
| RESTRAIN DRAINAGE PIPING FROM AXIAL MOVEMENT. |
| 308.7.1 LOCATION. FOR PIPE SIZES GREATER THAN 4 INCHES |
| , RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL |
| CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER |
| GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING |
| AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING |
| MANUFACTURER SHALL BE UTILIZED. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 22. SHT. P-4.09 SHOW DISTANCE OF SANITARY VENTS FROM |
| AIR INTAKES MUST BE MIN. OF 10'. PER FBC PL 903.5 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |