Plan Review Notes
Plan Review Notes For Permit 18090469
Permit Number 18090469
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-10-15 10:26:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.01 - THERE IS NO INDICATIONS WHETHER THIS
 IS A MIXED OR SEPARATED OCCUPANCY. THERE DOES NOT
 APPEAR TO ANY RATED WALL ASSEMBLIES FOR THE CORRIDORS
 FROM THE RETAIL SPACES.
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE
 REFERNECES.
  
  
  
 2) SHEET LS 0.01 - THERE IS AN INDICATION OF SMOKE
 CONTROL HOWEVER, THERE ARE NO CLEAR INDICATIONS OF TYPE
 AND NO RATIONAL ANALYSIS SUBMITTED.
  
 PER NFPA 1, CHAPTER 10 , GENERAL SAFETY REQUIREMENTS
  
 10.14.3.4.4 ENGINEERING ANALYSIS AND CALCULATIONS. AN
 ENGINEERING ANALYSIS AND CALCULATIONS SHALL BE PROVIDED
 WITH THE
 FOLLOWING:
 (1) SMOKE PROTECTION CALCULATIONS AS FOLLOWS:
 (A) SMOKE EXHAUST AND FRESH AIR REQUIREMENTS PER NFPA
 92, STANDARD FOR SMOKE CONTROL SYSTEMS
 (B) SMOKE MAINTAINED AT A LEVEL SIX FT ABOVE THE FLOOR
 OF THE
 MEANS OF EGRESS
 (C) PROPOSED TESTING PROTOCOL FOR SMOKE SYSTEM AND
 PASS/FAIL CRITERIA
 (D) CALCULATIONS FOR PERFORMANCE-BASED DESIGN METHODS
 ACCEPTED BY THE AHJ
 (E) SMOKE AND FIRE MODELING
 (F) TIMED EGRESS ANALYSIS
 (G) ASSUMED FLOW RATES AND TRAVEL SPEED
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) LS 0.01 - THERE IS A COMMAND ROMM INDICATED. PLEASE
 ENSURE A GENEREATOR SWITCH AND FIRE SPRINKLER VALVE AND
 WATER FLOW PANEL ARE PROVIDED.
  
 PER NFPA 1, CHAPTER 11, BUILDING SERVICES
  
 11.9 EMERGENCY COMMAND CENTER. WHERE REQUIRED,
 EMERGENCY
 COMMAND CENTERS SHALL COMPLY WITH SECTION 11.9.
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND
 CENTER:
 (1) THE FIRE DEPARTMENT COMMUNICATION UNIT
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND
 DETAILING THE BUILDING CORE MEANS OF EGRESS, FIRE
 PROTECTION
 SYSTEMS, FIRE-FIGHTING EQUIPMENT, AND FIRE DEPARTMENT
 ACCESS
 (4) WORK TABLE
 (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS
 FOR THE
 BUILDING
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS
 SHALL BE PROVIDED WITHIN THE EMERGENCY COMMAND CENTER:
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT
 (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE
 ELEVATORS AND
 WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER
 FEATURES
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER
 SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 AND
  
 PER NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH
 RISE BUILDINGS
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4 A) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE
 OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO
 NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION
 REQUIRED.
  
 PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES
  
  
  
  
 4 B) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE
 OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO
 NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION
 REQUIRED.
  
 PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES
  
  
  
  
  
 5) SHEET F 1.01 - THERE ARE INDICATIONS OF A FIRE PUMP
 TEST HEADER AND FIRE DEPARTMENT CONNECTION AT THE SAME
 LOCATION.
  
 PLEASE ENSURE THAT THESE ARE NOT ONE PIECE OF EQUIPMENT
 AS THEY ARE TWO DISTINCT PIECES WITH DIFFERENT
 FUNCTIONS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
  
 6) SHEET P 1.01 - THERE DOES NOT APPEAR TO BE ANY CLEAR
 INDICATIONS OF A FLOOR DRAIN IN THE FIRE PUMP ROOM
  
 PER NFPA 20, CHAPTER 4, GENERAL REQUIREMENTS
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
  
  
  
 7) SHEET A 4.01 - THE IS AN INDICATION OF A FUEL TANK
 IN THE FUEL TANK ROOM; HOWEVER, THERE ARE NO DETAILS
 PROVIDED ON THE FUEL TANK.
  
 THIS FUEL TANK PROVIDE EMERGENCY POWER AND SHALL COMPLY
 WITH NFPA
  
 PER NFPA 110
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA
 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED.
 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED
 BETWEEN THE
 PRIME MOVER AND THE FUEL PIPING.
  
 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE
 INDICATING
 TYPE.
 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE
 MAINTAINED ON ALL SIDES.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 8) THERE IS AN INDICATION OF A FUEL TANK WITHIN THE
 GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS
 DOUBLE WALLED OR THERE IS CONTAIMENT.
  
 PER NFPA 30
  
 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL.
 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO
 PREVENT
 THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC
 SEWERS,
 OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN
 SPECIFICALLY
 APPROVED.
  
 PLEASE PROVIDE SPECIFIC DETAILS FOR SPILL CONTAINMENT.
  
  
 9) SHEET A 4.01 AND M 1.01 - THERE IS AN INDICATION OF
 A GENERATOR AND EXHAUST PIPING, HOWEVER, THERE ARE NO
 DETAILS.
  
 THE INSTALLATION OF THE GENERATOR SHALL BE UNDER
 SEPARATE PERMIT APPLICATION
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS.
  
  
  
 10) SHEET AE 4.01 - DOORS # 115A, 115C AND 122A
 INDICATION THEIR SWING TO WHAT APPEARS TO BE AGAINST
 THE PATH OF TRAVEL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW THE OCCUPANCY LOAD CALCULATIONS AND
 POTENIAL EGRESS THRU THESE DOORS AND CORRECT OF JUSTIFY
 WITH SPECIFIC DETAILS.
  
  
  
  
  
 11) SHEET LS 1.06 - THERE IS AN OPEN/PUBLIC SPACE WITH
 AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC.
  
 THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN
 OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 106 PERSONS.
  
 BASED ON THIS NEW OCCUPANCY LOAD THE DOORS/GATES
 LEADING INTO THE GARAGE AREA SHALL SWING IN THE PATH OF
 TRAVEL.
  
 PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
  
 12 A) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE
 WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ;
 14 PERSONS
  
 THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN
 OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 89 PERSONS.
  
 BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO
 THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN
 ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER #
 4 ABOVE.
  
 PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 12 B) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE
 WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ;
 16 PERSONS
  
 THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN
 OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 199 PERSONS.
  
 BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO
 THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN
 ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER #
 4 ABOVE.
  
 PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
  
  
  
 13) SHEET FA 1.02 - THERE IS A PULL STATION AT STAIRWAY
 # 3 THAT IS INDICATED MORE THAN 5' FROM THE EXIT DOOR.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 14) SHEET FA 1.02 - THERE IS NO PULL STATION LOCATED AT
 THE REAR OFFICE EXIT DOOR 201 FROM THE OFFICE AREA.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
 15) SHEET FA 1.02 - THERE IS A PULL STATION INDICATED
 ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.02
 DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION.
  
 THERE IS NO EXIT DOOR SHOWN ON THIS PLAN SHEET AT
 STAIRWAY # 5 AS COMPARED TO AE 4.02 WHICH INDICATES A
 COMPLETLY DIFFERENT STAIRWAY DESIGN.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT
  
  
  
 16) SHEET FA 1.03 - THERE IS A PULL STATION INDICATED
 ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.03
 DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT
  
  
  
 17) SHEET FA 1.04 - THERE IS NO PULL STATION LOCATED AT
 THE REAR OFFICE EXIT DOOR 401 FROM THE OFFICE AREA.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 18) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 19) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL