2018-10-15 10:26:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET LS 1.01 - THERE IS NO INDICATIONS WHETHER THIS |
| IS A MIXED OR SEPARATED OCCUPANCY. THERE DOES NOT |
| APPEAR TO ANY RATED WALL ASSEMBLIES FOR THE CORRIDORS |
| FROM THE RETAIL SPACES. |
| |
| PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE |
| REFERNECES. |
| |
| |
| |
| 2) SHEET LS 0.01 - THERE IS AN INDICATION OF SMOKE |
| CONTROL HOWEVER, THERE ARE NO CLEAR INDICATIONS OF TYPE |
| AND NO RATIONAL ANALYSIS SUBMITTED. |
| |
| PER NFPA 1, CHAPTER 10 , GENERAL SAFETY REQUIREMENTS |
| |
| 10.14.3.4.4 ENGINEERING ANALYSIS AND CALCULATIONS. AN |
| ENGINEERING ANALYSIS AND CALCULATIONS SHALL BE PROVIDED |
| WITH THE |
| FOLLOWING: |
| (1) SMOKE PROTECTION CALCULATIONS AS FOLLOWS: |
| (A) SMOKE EXHAUST AND FRESH AIR REQUIREMENTS PER NFPA |
| 92, STANDARD FOR SMOKE CONTROL SYSTEMS |
| (B) SMOKE MAINTAINED AT A LEVEL SIX FT ABOVE THE FLOOR |
| OF THE |
| MEANS OF EGRESS |
| (C) PROPOSED TESTING PROTOCOL FOR SMOKE SYSTEM AND |
| PASS/FAIL CRITERIA |
| (D) CALCULATIONS FOR PERFORMANCE-BASED DESIGN METHODS |
| ACCEPTED BY THE AHJ |
| (E) SMOKE AND FIRE MODELING |
| (F) TIMED EGRESS ANALYSIS |
| (G) ASSUMED FLOW RATES AND TRAVEL SPEED |
| |
| PLEASE REVIEW AND PROVIDE. |
| |
| |
| |
| 3) LS 0.01 - THERE IS A COMMAND ROMM INDICATED. PLEASE |
| ENSURE A GENEREATOR SWITCH AND FIRE SPRINKLER VALVE AND |
| WATER FLOW PANEL ARE PROVIDED. |
| |
| PER NFPA 1, CHAPTER 11, BUILDING SERVICES |
| |
| 11.9 EMERGENCY COMMAND CENTER. WHERE REQUIRED, |
| EMERGENCY |
| COMMAND CENTERS SHALL COMPLY WITH SECTION 11.9. |
| |
| 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| COMMAND |
| CENTER: |
| (1) THE FIRE DEPARTMENT COMMUNICATION UNIT |
| (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE |
| PUBLIC TELEPHONE SYSTEM |
| (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| FLOOR PLAN AND |
| DETAILING THE BUILDING CORE MEANS OF EGRESS, FIRE |
| PROTECTION |
| SYSTEMS, FIRE-FIGHTING EQUIPMENT, AND FIRE DEPARTMENT |
| ACCESS |
| (4) WORK TABLE |
| (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS |
| FOR THE |
| BUILDING |
| 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| OR FUNCTIONS |
| SHALL BE PROVIDED WITHIN THE EMERGENCY COMMAND CENTER: |
| (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT |
| (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT |
| (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE |
| ELEVATORS AND |
| WHETHER THEY ARE OPERATIONAL |
| (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| SYSTEMS |
| (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| SIMULTANEOUSLY |
| (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| PANELS |
| (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| (8) FIRE PUMP STATUS INDICATORS |
| (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| TRANSFER |
| FEATURES |
| (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER |
| SECTIONS OF THIS CODE |
| (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| |
| AND |
| |
| PER NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH |
| RISE BUILDINGS |
| |
| 11.8.6* EMERGENCY COMMAND CENTER. |
| 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| IN A |
| LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| FOLLOWING: |
| (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| SERVICE |
| PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| OF THIS |
| CODE |
| (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| PANELS |
| (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| PROVIDED |
| IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| (8) EMERGENCY GENERATOR STATUS INDICATORS |
| (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| SYSTEM |
| (10) FIRE PUMP STATUS INDICATORS |
| (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE |
| PUBLIC TELEPHONE SYSTEM |
| (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| 11.8.8 |
| |
| |
| PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN |
| APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| |
| |
| |
| 4 A) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE |
| OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO |
| NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION |
| REQUIRED. |
| |
| PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES |
| |
| 12.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 12.2.5.1 GENERAL. |
| 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| ACCORDANCE WITH |
| SECTION 7.5. |
| |
| |
| 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| 7.5.1.3.1 |
| THROUGH 7.5.1.3.7. |
| 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| EXIT DISCHARGE IS |
| REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| EXITS, EXIT ACCESSES, |
| OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| OTHER AND BE |
| ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| HAS THE |
| POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| EMERGENCY |
| CONDITION. |
| |
| 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES ARE |
| REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| ANOTHER NOT |
| LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| DIAGONAL |
| DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| MEASURED IN A |
| STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| EXIT ACCESSES, OR |
| EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| THROUGH |
| 7.5.1.3.5. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES |
| |
| |
| |
| |
| 4 B) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE |
| OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO |
| NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION |
| REQUIRED. |
| |
| PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES |
| |
| 12.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 12.2.5.1 GENERAL. |
| 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| ACCORDANCE WITH |
| SECTION 7.5. |
| |
| |
| 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| 7.5.1.3.1 |
| THROUGH 7.5.1.3.7. |
| 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| EXIT DISCHARGE IS |
| REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| EXITS, EXIT ACCESSES, |
| OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| OTHER AND BE |
| ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| HAS THE |
| POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| EMERGENCY |
| CONDITION. |
| |
| 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| DISCHARGES ARE |
| REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| ANOTHER NOT |
| LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| DIAGONAL |
| DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| MEASURED IN A |
| STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| EXIT ACCESSES, OR |
| EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| THROUGH |
| 7.5.1.3.5. |
| |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES |
| |
| |
| |
| |
| |
| 5) SHEET F 1.01 - THERE ARE INDICATIONS OF A FIRE PUMP |
| TEST HEADER AND FIRE DEPARTMENT CONNECTION AT THE SAME |
| LOCATION. |
| |
| PLEASE ENSURE THAT THESE ARE NOT ONE PIECE OF EQUIPMENT |
| AS THEY ARE TWO DISTINCT PIECES WITH DIFFERENT |
| FUNCTIONS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT. |
| |
| |
| |
| |
| 6) SHEET P 1.01 - THERE DOES NOT APPEAR TO BE ANY CLEAR |
| INDICATIONS OF A FLOOR DRAIN IN THE FIRE PUMP ROOM |
| |
| PER NFPA 20, CHAPTER 4, GENERAL REQUIREMENTS |
| |
| 4.12.7* DRAINAGE. |
| 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| OF ESCAPING |
| WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, |
| DRIVER, CONTROLLER, AND SO FORTH. |
| 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED |
| WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE |
| LOCATION. |
| |
| |
| |
| |
| 7) SHEET A 4.01 - THE IS AN INDICATION OF A FUEL TANK |
| IN THE FUEL TANK ROOM; HOWEVER, THERE ARE NO DETAILS |
| PROVIDED ON THE FUEL TANK. |
| |
| THIS FUEL TANK PROVIDE EMERGENCY POWER AND SHALL COMPLY |
| WITH NFPA |
| |
| PER NFPA 110 |
| |
| 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| AND MAINTAINED |
| IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| 54, NATIONAL |
| FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| CODE. |
| 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED. |
| 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED |
| BETWEEN THE |
| PRIME MOVER AND THE FUEL PIPING. |
| |
| 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE |
| INDICATING |
| TYPE. |
| 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE |
| MAINTAINED ON ALL SIDES. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| |
| 8) THERE IS AN INDICATION OF A FUEL TANK WITHIN THE |
| GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS |
| DOUBLE WALLED OR THERE IS CONTAIMENT. |
| |
| PER NFPA 30 |
| |
| 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL. |
| 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO |
| PREVENT |
| THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC |
| SEWERS, |
| OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN |
| SPECIFICALLY |
| APPROVED. |
| |
| PLEASE PROVIDE SPECIFIC DETAILS FOR SPILL CONTAINMENT. |
| |
| |
| 9) SHEET A 4.01 AND M 1.01 - THERE IS AN INDICATION OF |
| A GENERATOR AND EXHAUST PIPING, HOWEVER, THERE ARE NO |
| DETAILS. |
| |
| THE INSTALLATION OF THE GENERATOR SHALL BE UNDER |
| SEPARATE PERMIT APPLICATION |
| |
| PER NFPA 110 |
| |
| 7.10 EXHAUST SYSTEM. |
| 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| INCLUDING |
| PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| AND USE OF |
| STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| OTHER APPLICABLE |
| STANDARDS. |
| 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| PREVENT |
| EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| BUILDINGS |
| AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| WINDOWS, |
| AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| SYSTEM. |
| 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME |
| MOVER |
| BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE |
| INDEPENDENTLY |
| SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR |
| STRESS IS |
| APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. |
| |
| PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS. |
| |
| |
| |
| 10) SHEET AE 4.01 - DOORS # 115A, 115C AND 122A |
| INDICATION THEIR SWING TO WHAT APPEARS TO BE AGAINST |
| THE PATH OF TRAVEL. |
| |
| PER NFPA 101, CHAPTER 7, MEANS OF EGRESS |
| |
| 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| REQUIRED TO BE |
| OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING |
| IN THE |
| DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING |
| CONDITIONS: |
| (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| OF 50 OR |
| MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| REQUIRED TO |
| SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED |
| BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| TO |
| SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| HEALTH |
| CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| ENCLOSURE, UNLESS |
| THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| OPENS |
| DIRECTLY INTO AN EXIT ENCLOSURE |
| (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| CONTENTS AREA |
| |
| PLEASE REVIEW THE OCCUPANCY LOAD CALCULATIONS AND |
| POTENIAL EGRESS THRU THESE DOORS AND CORRECT OF JUSTIFY |
| WITH SPECIFIC DETAILS. |
| |
| |
| |
| |
| |
| 11) SHEET LS 1.06 - THERE IS AN OPEN/PUBLIC SPACE WITH |
| AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. |
| |
| THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN |
| OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 106 PERSONS. |
| |
| BASED ON THIS NEW OCCUPANCY LOAD THE DOORS/GATES |
| LEADING INTO THE GARAGE AREA SHALL SWING IN THE PATH OF |
| TRAVEL. |
| |
| PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| |
| 12 A) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE |
| WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ; |
| 14 PERSONS |
| |
| THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN |
| OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 89 PERSONS. |
| |
| BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO |
| THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN |
| ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER # |
| 4 ABOVE. |
| |
| PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| 12 B) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE |
| WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ; |
| 16 PERSONS |
| |
| THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN |
| OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 199 PERSONS. |
| |
| BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO |
| THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN |
| ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER # |
| 4 ABOVE. |
| |
| PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE |
| REFERENCES. |
| |
| |
| |
| |
| |
| |
| 13) SHEET FA 1.02 - THERE IS A PULL STATION AT STAIRWAY |
| # 3 THAT IS INDICATED MORE THAN 5' FROM THE EXIT DOOR. |
| |
| THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| CALLED OUT FOR CORRECTION. |
| |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 14) SHEET FA 1.02 - THERE IS NO PULL STATION LOCATED AT |
| THE REAR OFFICE EXIT DOOR 201 FROM THE OFFICE AREA. |
| |
| THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| CALLED OUT FOR CORRECTION. |
| |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| 15) SHEET FA 1.02 - THERE IS A PULL STATION INDICATED |
| ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.02 |
| DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION. |
| |
| THERE IS NO EXIT DOOR SHOWN ON THIS PLAN SHEET AT |
| STAIRWAY # 5 AS COMPARED TO AE 4.02 WHICH INDICATES A |
| COMPLETLY DIFFERENT STAIRWAY DESIGN. |
| |
| THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| CALLED OUT FOR CORRECTION. |
| |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| |
| 16) SHEET FA 1.03 - THERE IS A PULL STATION INDICATED |
| ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.03 |
| DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION. |
| |
| THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| CALLED OUT FOR CORRECTION. |
| |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| |
| 17) SHEET FA 1.04 - THERE IS NO PULL STATION LOCATED AT |
| THE REAR OFFICE EXIT DOOR 401 FROM THE OFFICE AREA. |
| |
| THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| CALLED OUT FOR CORRECTION. |
| |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| |
| 18) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 19) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |