Date |
Text |
2018-10-31 15:55:50 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| NFPA 70 2014 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| PAGE E8.01 |
| |
| 1) NOTE #12 STATES SEE GROUNDING RISER, COULD NOT FIND |
| GROUNDING RISER IN SET. |
| |
| WHAT MEANS IS GOING TO BE PROVIDED TO HAVE A GEC |
| AVAILABLE FOR ALL THE SEPARATELY DERIVED SYSTEMS IN |
| BUILDING? |
| |
| |
| 2) FEEDER SCHEDULE: ON THE ALUMINUM SCHEDULE |
| |
| 4000A FEEDER ONLY HAS AN AMPACITY OF 3465 AMPERES |
| 240.4(C) |
| 3200A FEEDER ONLY HAS AN AMPACITY OF 2692 AMPERES |
| 240.4(C) |
| |
| WHERE THE OVERCURRENT DEVICE IS RATED OVER 800 AMPERES, |
| THE AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE |
| EQUAL TO OR GREATER THAN THE |
| RATING OF THE OVERCURRENT DEVICE DEFINED IN 240.6. |
| |
| |
| 3) FIRE PUMP CONTROLER CIRCUIT IS FED THROUGH LSDP |
| WHICH CANNOT HAVE OTHER LOADS THAT ARE NOT FIRE PUMP |
| ASSOCIATED LOADS 695.4(B)(3)(A)(3) |
| |
| DISCONNECTING MEANS SUPPLIED BY ONE OF THE INDIVIDUAL |
| SOURCES SPECIFIED IN 695.3(A) CANNOT BE INSTALLED IN |
| DISTRIBUTION |
| EQUIPMENT THAT SUPPLIES OTHER THAN FIRE PUMP LOADS. |
| ?SUFFICIENTLY REMOTE? ALSO CANNOT BE INTERPRETED AS |
| PERMITTING THE FIRE PUMP |
| DISCONNECTING MEANS TO BE LOCATED IN A SEPARATE |
| SWITCHBOARD SECTION OF EQUIPMENT THAT SUPPLIES OTHER |
| THAN FIRE PUMP LOADS. |
| |
| |
| 4) TRANSFER OF POWER TO FIRE PUMP SHALL TAKE PLACE IN |
| PUMP ROOM 695.3(F) NOT IN EMERGENCY ELECTRICAL ROOM AND |
| PUMP ROOM. |
| |
| TRANSFER OF POWER. TRANSFER OF POWER TO THE FIRE PUMP |
| CONTROLLER BETWEEN THE INDIVID UAL SOURCE AND ONE |
| ALTERNATE SOURCE |
| SHALL TAKE PLACE WITHIN THE PUMP ROOM. [20:9.6.4] |
| |
| |
| 5) A SINGLE MEANS OF DISCONNECT AND ONE ADDITIONAL |
| DISCONNECT WILL BE PERMITTED BUT NOT TWO PLUS A |
| TRANSFER SWITCH. 695.4(B)(1)(A,B,C) |
| |
| A SINGLE DISCONNECT ING MEANS AND ASSOCIATED |
| OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE PERMITTED TO |
| BE |
| INSTALLED BETWEEN THE FIRE PUMP POWER SOURCE(S) AND ONE |
| OF THE FOLLOWING: [20:9.1.2] |
| (1) A LISTED FIRE PUMP CONTROLLER |
| (2) A LISTED FIRE PUMP POWER TRANSFER SWITCH |
| (3) A LISTED COMBINATION FIRE PUMP CONTROLLER AND POWER |
| TRANSFER SWITCH |
| |
| |
| 6) FEED FROM FPL TRANSFORMER TO FIRE PUMP CONTROLER TO |
| ENCASED IN A MINIMUM OF 2" |
| |
| SERVICE CONDUCTORS AND CONDUCTORS SUPPLIED BY ON-SITE |
| POWER PRODUCTION FACILITIES SHALL BE PHYSICALLY ROUTED |
| OUTSIDE A BUILDING(S) AND SHALL |
| BE INSTALLED AS SERVICE-ENTRANCE CONDUCTORS IN |
| ACCORDANCE WITH 230.6, 230.9 |
| |
| |
| 7) LOAD CALCULATION NEEDS TO BE LAYED OUT SO THE I CAN |
| UNDERSTAND HOW LOADS WHERE ACHIEVED. |
| |
| THE CALCULATED LOAD OF A FEEDER OR S ERVICE SHALL NOT |
| BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH |
| CIRCUITS SUPPLIED, AS DETERMINED BY |
| PART II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND |
| FACTORS PERMITTED BY PART III OR IV OR REQUIRED BY PART |
| V HAVE BEEN APPLIED. |
| THE AMPACITY OF SERVICE-ENTRANCE CONDUCTORS SHALL NOT |
| BE LESS THAN EITHER 230.42(A)(1), (A)(2), OR (A)(3). |
| |
| |
| 8) SHOW LOAD CALCULATION FOR 3200 A FEED FROM GENERATOR |
| TO 4000A TRANSFER SWITCH |
| |
| THE CALCULATED LOAD OF A FEEDER OR S ERVICE SHALL NOT |
| BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH |
| CIRCUITS SUPPLIED, AS DETERMINED BY |
| PART II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND |
| FACTORS PERMITTED BY PART III OR IV OR REQUIRED BY PART |
| V HAVE BEEN APPLIED. |
| |
| |
| 9) FAULT CURRENT CALCULATION FOR SERVICE MAINS, AND SUB |
| PANELS. |
| |
| THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL |
| IMPEDANCE, THE EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS, |
| AND OTHER CHARACTERISTICS |
| OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND |
| COORDINATED TO PERMIT THE CIRCUIT PROTECTIVE DEVICES |
| USED TO CLEAR A FAULT TO DO |
| SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT |
| OF THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE |
| EITHER BETWEEN TWO OR |
| MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY CIRCUIT |
| CONDUCTOR AND THE EQUIPMENT GROUNDING CONDUCTOR(S) |
| PERMITTED IN 250.118. |
| LISTED EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR |
| LISTING SHALL BE CONSIDERED TO MEET THE REQUIREMENTS OF |
| THIS SECTION. |
| |
| |
| 10) FOR CIRCUIT BREAKERS 1200 AMPERES AND OVER ARC |
| ENERGY REDUCTION REQUIRED. |
| |
| WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR |
| WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A |
| CIRCUIT BREAKER IS RATED |
| OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND |
| (B) SHALL APPLY. |
| |
| |
| 11) ON RISERS ON PAGES E8.02, E8.03 SYMBOL OF A CIRCLE |
| AND "M" IN THE MIDDLE AT ALL HIGH VOLTAGE AND LOW |
| VOLTAGE PANELS? |
| |
| |
| 12) DAS SYSTEM RISER SHOWS SEVERAL PENETRATION OF THE |
| STAIRWELL. THIS WILL BE REFERED OVER TO THE BUILDING |
| PLANS EXAMINER FOR REVIEW. |
| |
| |