2018-10-31 15:55:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E8.01
  
 1) NOTE #12 STATES SEE GROUNDING RISER, COULD NOT FIND
 GROUNDING RISER IN SET.
  
 WHAT MEANS IS GOING TO BE PROVIDED TO HAVE A GEC
 AVAILABLE FOR ALL THE SEPARATELY DERIVED SYSTEMS IN
 BUILDING?
  
  
 2) FEEDER SCHEDULE: ON THE ALUMINUM SCHEDULE
  
 4000A FEEDER ONLY HAS AN AMPACITY OF 3465 AMPERES
 240.4(C)
 3200A FEEDER ONLY HAS AN AMPACITY OF 2692 AMPERES
 240.4(C)
  
 WHERE THE OVERCURRENT DEVICE IS RATED OVER 800 AMPERES,
 THE AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE
 EQUAL TO OR GREATER THAN THE
 RATING OF THE OVERCURRENT DEVICE DEFINED IN 240.6.
  
  
 3) FIRE PUMP CONTROLER CIRCUIT IS FED THROUGH LSDP
 WHICH CANNOT HAVE OTHER LOADS THAT ARE NOT FIRE PUMP
 ASSOCIATED LOADS 695.4(B)(3)(A)(3)
  
 DISCONNECTING MEANS SUPPLIED BY ONE OF THE INDIVIDUAL
 SOURCES SPECIFIED IN 695.3(A) CANNOT BE INSTALLED IN
 DISTRIBUTION
 EQUIPMENT THAT SUPPLIES OTHER THAN FIRE PUMP LOADS.
 ?SUFFICIENTLY REMOTE? ALSO CANNOT BE INTERPRETED AS
 PERMITTING THE FIRE PUMP
 DISCONNECTING MEANS TO BE LOCATED IN A SEPARATE
 SWITCHBOARD SECTION OF EQUIPMENT THAT SUPPLIES OTHER
 THAN FIRE PUMP LOADS.
  
  
 4) TRANSFER OF POWER TO FIRE PUMP SHALL TAKE PLACE IN
 PUMP ROOM 695.3(F) NOT IN EMERGENCY ELECTRICAL ROOM AND
 PUMP ROOM.
  
 TRANSFER OF POWER. TRANSFER OF POWER TO THE FIRE PUMP
 CONTROLLER BETWEEN THE INDIVID UAL SOURCE AND ONE
 ALTERNATE SOURCE
 SHALL TAKE PLACE WITHIN THE PUMP ROOM. [20:9.6.4]
  
  
 5) A SINGLE MEANS OF DISCONNECT AND ONE ADDITIONAL
 DISCONNECT WILL BE PERMITTED BUT NOT TWO PLUS A
 TRANSFER SWITCH. 695.4(B)(1)(A,B,C)
  
 A SINGLE DISCONNECT ING MEANS AND ASSOCIATED
 OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE PERMITTED TO
 BE
 INSTALLED BETWEEN THE FIRE PUMP POWER SOURCE(S) AND ONE
 OF THE FOLLOWING: [20:9.1.2]
 (1) A LISTED FIRE PUMP CONTROLLER
 (2) A LISTED FIRE PUMP POWER TRANSFER SWITCH
 (3) A LISTED COMBINATION FIRE PUMP CONTROLLER AND POWER
 TRANSFER SWITCH
  
  
 6) FEED FROM FPL TRANSFORMER TO FIRE PUMP CONTROLER TO
 ENCASED IN A MINIMUM OF 2"
  
 SERVICE CONDUCTORS AND CONDUCTORS SUPPLIED BY ON-SITE
 POWER PRODUCTION FACILITIES SHALL BE PHYSICALLY ROUTED
 OUTSIDE A BUILDING(S) AND SHALL
 BE INSTALLED AS SERVICE-ENTRANCE CONDUCTORS IN
 ACCORDANCE WITH 230.6, 230.9
  
  
 7) LOAD CALCULATION NEEDS TO BE LAYED OUT SO THE I CAN
 UNDERSTAND HOW LOADS WHERE ACHIEVED.
  
 THE CALCULATED LOAD OF A FEEDER OR S ERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED, AS DETERMINED BY
 PART II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND
 FACTORS PERMITTED BY PART III OR IV OR REQUIRED BY PART
 V HAVE BEEN APPLIED.
 THE AMPACITY OF SERVICE-ENTRANCE CONDUCTORS SHALL NOT
 BE LESS THAN EITHER 230.42(A)(1), (A)(2), OR (A)(3).
  
  
 8) SHOW LOAD CALCULATION FOR 3200 A FEED FROM GENERATOR
 TO 4000A TRANSFER SWITCH
  
 THE CALCULATED LOAD OF A FEEDER OR S ERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED, AS DETERMINED BY
 PART II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND
 FACTORS PERMITTED BY PART III OR IV OR REQUIRED BY PART
 V HAVE BEEN APPLIED.
  
  
 9) FAULT CURRENT CALCULATION FOR SERVICE MAINS, AND SUB
 PANELS.
  
 THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL
 IMPEDANCE, THE EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS,
 AND OTHER CHARACTERISTICS
 OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND
 COORDINATED TO PERMIT THE CIRCUIT PROTECTIVE DEVICES
 USED TO CLEAR A FAULT TO DO
 SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT
 OF THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE
 EITHER BETWEEN TWO OR
 MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY CIRCUIT
 CONDUCTOR AND THE EQUIPMENT GROUNDING CONDUCTOR(S)
 PERMITTED IN 250.118.
 LISTED EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR
 LISTING SHALL BE CONSIDERED TO MEET THE REQUIREMENTS OF
 THIS SECTION.
  
  
 10) FOR CIRCUIT BREAKERS 1200 AMPERES AND OVER ARC
 ENERGY REDUCTION REQUIRED.
  
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A
 CIRCUIT BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL APPLY.
  
  
 11) ON RISERS ON PAGES E8.02, E8.03 SYMBOL OF A CIRCLE
 AND "M" IN THE MIDDLE AT ALL HIGH VOLTAGE AND LOW
 VOLTAGE PANELS?
  
  
 12) DAS SYSTEM RISER SHOWS SEVERAL PENETRATION OF THE
 STAIRWELL. THIS WILL BE REFERED OVER TO THE BUILDING
 PLANS EXAMINER FOR REVIEW.
  
  