2018-12-05 11:51:51 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18090469 |
| ADD: 360 ROSEMARY AVE. / PCN: 74-43-43-21-01-022-0040 |
| CONT: MOSS & ASSOCIATES LLC |
| TEL: 954-524-5678 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 1ST REVIEW |
| DATE: MONDAY DEC.10TH/ 2018. COMPLETED REVIEW. |
| ACTION: DENIED |
| |
| 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected]. |
| |
| 2A) PLEASE NOTE SHEET 002-G10.02 SHEET INDEX-VOLUME 1 |
| IS MISSING THE STRUCTURAL SHEETS S0.01 THROUGH S4.05, |
| THERE ARE 57 STRUCTURAL SHEETS MISSING FROM THE INDEX |
| OF DRAWINGS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2B) PLEASE NOTE SHEET 002-G10.02 SHEET INDEX-VOLUME 1 |
| IS MISSING THE SHEET 274-AE6.00. 107.2.1.2. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 3A) SHEET 007-LS0.01 THE LIFE SAFETY ANALYSIS SHEET NOR |
| ANY OF THE LIFE SAFETY SHEETS FOR EACH FLOOR SHOW A |
| CHART PER FLOOR FOR THE SQUARE FOOTAGE PER FLOOR PER |
| OCCUPANCY, NOR THE OCCUPANCY LOADS PER FLOOR, NOR THE A |
| MENTIONED ABOVE FOR THE WHOLE BUILDING. THE CLOSEST IS |
| A PLUMBING FIXTURE CALCULATION THAT SHOW A ZERO |
| OCCUPANT LOAD FOR LEVELS 2 THROUGH 8? PLEASE REVIEW THE |
| 2017 FBC-B TABLE 1004.1.2 PARKING GARAGES 200 GROSS |
| OCCUPANT LOAD FACTOR. 107.2.1.2 ADDITIONAL INFORMATION |
| IS REQUIRED. |
| |
| 3B) PLEASE NOTE THE DOLLAR AMOUNT STATED IN THE PERMIT |
| APPLICATION CANNOT BE CALCULATED AS TO THE VALUE OF THE |
| BUILDING SINCE AS STATED ABOVE THERE IS NO CHART PER |
| FLOOR FOR THE SQUARE FOOTAGE PER FLOOR PER OCCUPANCY, |
| NOR THE OCCUPANCY LOADS PER FLOOR, NOR THE A MENTIONED |
| ABOVE FOR THE WHOLE BUILDING. |
| |
| 3C) SHEET 007-LS0.01 THE LIFE SAFETY PLAN ANALYSIS. |
| THIS SHEET LIST CODE REFERENCES TO CHAPTER 4,9, 10 WITH |
| VARIOUS CODE SECTIONS. EXAMPLES: |
| 403.4.7 SMOKE REMOVAL 909.16 FIRE FIGHTERS SMOKE |
| CONTROL PANEL, 909.16.1 SMOKE CONTROL SYSTEMS, 909.16.2 |
| SMOKE CONTROL PANEL AND 909.16.3 CONTROL PANEL AND |
| PROPERTIES. PLEASE NOTE LISTING THESE CODE SECTIONS |
| DOES NOT MEAN CODE COMPLIANCE. |
| |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1. |
| W.P.B. ADMINISTRATIVE CODE/2017. DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART? PLEASE PROVIDE THE SMOKE CONTROL RATIONAL |
| ANALYSIS. |
| |
| 3D) SHEET 007-LS0.01 THE LIFE SAFETY PLAN ANALYSIS. |
| THIS SHEET LIST CODE REFERENCES TO CHAPTER 9 OF THE |
| FBC-B THE SECTION DEALING WITH THE FIRE COMMAND CENTER |
| 911.1 THROUGH 911.1.5. |
| |
| W.P.B. ADMINISTRATIVE CODE/2017. DRAWINGS & |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO |
| THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR |
| IN PART? PLEASE SHOW HOW COMPLIANCE WILL BE ACHIEVED. |
| |
| |
| 4) 2017 W. P. B. AMENDMENTS TO CHAPTER 1 |
| ADMINISTRATION. 109.3* BUILDING PERMIT VALUATION. IF, |
| IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| 107.2.1. |
| THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| PRIME OR MASTER PERMIT. |
| 5) SUPPORTING DOCUMENT FOLDER. WITHIN THE SUPPORTING |
| DOCUMENT FOLDER THERE IS LISTED SPECIFICATION MANUAL. |
| PLEASE NOTE THIS DOCUMENT IS NOT TO BE REVIEWED AND NOT |
| PART OF THE PLAN REVIEW DOCUMENTS, IT SHOULD BE REMOVED |
| OR MARKED VOID/ NOT REVIEWED. THIS DOCUMENT IS FROM THE |
| DESIGNERS OF RECORD AND DIRECTED TO THE CONTRACTORS OF |
| RECORD FOR SPECIFICATIONS. 107.2.1.3 QUALITY OF PLANS. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| 6) SHEET 059-S0.05 INDICATES WIND TUNNEL AND CLADDING |
| PRESSURES. THIS REVIEW CYCLE NO WIND TUNNEL TEST REPORT |
| WAS SUBMITTED. PLEASE SUBMIT THE WIND TUNNEL TEST IN |
| ELECTRONIC VERSION WITH AN ELECTRONIC SIGNATURE OR |
| PAPER WITH ORIGINAL SIGNATURE AND SEAL. WIND TUNNEL |
| TESTING IS TO COMPLY WITH: 2017 FBC-B 1609.1.1 |
| EXCEPTION 6.WIND TUNNEL TESTS IN ACCORDANCE WITH ASCE |
| 49 AND SECTIONS 31.4 AND 31.5 OF ASCE 7. |
| SHEET 059-S0.05 WIND TUNNEL COMPONENTS AND CLADDING |
| PRESSURES CANNOT BE VERIFIED, NO PRESSURES ARE GIVEN ON |
| THE ELEVATIONS. PLEASE ALSO SPECIFY IF THE PRESSURES |
| WHEN ADDED ARE IN VULT OR VASD. THE PRESSURES FOR |
| PRODUCT APPROVALS ARE IN VASD. |
| 7) MISSING ENERGY REPORT 2017 FBC-ENERGY C101.5 |
| COMPLIANCE. COMMERCIAL BUILDINGS SHALL MEET THE |
| PROVISIONS OF FLORIDA BUILDING CODE, ENERGY |
| CONSERVATION?COMMERCIAL PROVISIONS. |
| C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH ONE OF THE FOLLOWING: |
| |
| 7.1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, |
| EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD. |
| |
| 7.2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| SECTION C406.1.1. |
| |
| 7.3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| OF THE STANDARD REFERENCE DESIGN BUILDING. |
| |
| 8) THIS HIGH-RISE PROJECT QUALIFIES AS A THRESHOLD |
| BUILDING / FL S. S. 553.71(7) ?THRESHOLD BUILDING" |
| MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES |
| OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE |
| WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 8A) 109.3.6.1 THRESHOLD INSPECTION PLAN. COMPLETED, |
| SHEET 060-S0.06. THE ENFORCING AGENCY SHALL REQUIRE A |
| (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 8B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| PLACE. |
| |
| FORMS SENT TO [email protected] SAT. DEC. 01/2018 12:48 |
| PM/ |
| REPLIED: MON. DEC. 03/2018 8:37 AM |
| |
| 8C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 8D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| NOTE: SHEET 060-S0.06 THRESHOLD NOTES. GENERAL NOTE K |
| INDICATES THE SPECIAL INSPECTOR IS TO HAVE 10 YEARS |
| EXPERIENCE IN INSPECTION, DESIGN OF SIMILAR STRUCTURES. |
| |
| 8E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 8F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE.. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| CONCERNING SPECIAL INSPECTORS. |
| |
| 8G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| 8H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 8I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| 9) SHEET 005-AS0.01 SITE PLAN VERSES 006-AS0.02. IT |
| APPEARS THE SITE PLAN INCLUDES 360 S. ROSEMARY, 370 S. |
| ROSEMARY AND 352 EVERNIA ST. PLUS CITY OF W. P. B. |
| ABANDONMENT OF A PORTION OF THE ALLEY. PLEASE NOTE A |
| NEW PLAT WILL NEED TO BE RECORDED AND DOCUMENTATION OF |
| THE CITY OF WEST PALM BEACH ABANDONING A PORTION OF THE |
| ALLEY AND THE RELOCATION OF UTILITIES. PLEASE ALSO NOTE |
| THE ALLEYWAY BEHIND 352 EVERNIA ST. IT WOULD APPEAR THE |
| PROPERTY LINE IS DRAWN TO THE CENTERLINE OF THE ALLEY |
| WHEREAS THE CORNERS OF THE LOT ARE DESIGNATED AS THE |
| SOUTH SIDE OF THE ALLEY. PLEASE PROVIDE A SURVEY AND |
| OVERLAY OF THE NEW PROPOSED LOT LINES (SEE 005-AS0.01). |
| 2017 FBC-B SECTION 503 & 602, BUILDINGS CANNOT GO |
| BEYOND THE LOT LINES, THEY HAVE TO SIT ON ONE LOT. |
| |
| 10) BOTH SHEETS LS1.01 LIFE SAFETY PLAN LEVEL 1 & |
| 134-AE1.01: |
| |
| 10A) BOTH SHOW WHAT APPEARS TO BE A STRUCTURE JUST EAST |
| OF THE NEWLY CREATED PROPERTY LINE. PLEASE IDENTIFY IF |
| THIS LINE REPRESENTS THE WALL LINE OR ROOF LINE? PLEASE |
| ALSO SHOW THE EXTERIOR STAIR LOCATED ON THE WEST SIDE |
| OF THIS EXISTING BUILDING AND THE WIDTH OF THE |
| UNPROTECTED EXTERIOR STAIR. PLEASE ALSO PROVIDE HOW |
| MANY WINDOWS ARE WITHIN THIS WALL PER STORY AND SQ. FT. |
| AREA OF UNPROTECTED OPENINGS. PLEASE PROVIDE THE |
| DISTANCE FROM THE WALL LINE OF THIS EXISTING BUILDING |
| TO THE PROPERTY LINE. |
| |
| THE CREATION OF NEW LOT LINES/ AND OR PLAT ARE NOT TO |
| CREATE NEW NONCONFORMITIES TO EXISTING BUILDINGS. THE |
| 2017 FBC-B DEALS WITH: |
| |
| 10A)(1). LIGHT FRAME CONSTRUCTION IN 704.4.1. |
| LIGHT-FRAME CONSTRUCTION. STUDS AND BOUNDARY ELEMENTS |
| THAT ARE INTEGRAL ELEMENTS IN LOAD-BEARING WALLS OF |
| LIGHT-FRAME CONSTRUCTION SHALL BE PERMITTED TO HAVE |
| REQUIRED FIRE-RESISTANCE RATINGS PROVIDED BY THE |
| MEMBRANE PROTECTION PROVIDED FOR THE LOAD-BEARING WALL. |
| |
| 10A)(2). 704.10 EXTERIOR STRUCTURAL MEMBERS. |
| LOAD-BEARING STRUCTURAL MEMBERS LOCATED WITHIN THE |
| EXTERIOR WALLS OR ON THE OUTSIDE OF A BUILDING ( |
| EXTERIOR STAIRS) OR STRUCTURE SHALL BE PROVIDED WITH |
| THE HIGHEST FIRE-RESISTANCE RATING AS DETERMINED IN |
| ACCORDANCE WITH THE FOLLOWING: |
| 1.AS REQUIRED BY TABLE 601 FOR THE TYPE OF BUILDING |
| ELEMENT BASED ON THE TYPE OF CONSTRUCTION OF THE |
| BUILDING; |
| 2.AS REQUIRED BY TABLE 601 FOR EXTERIOR BEARING WALLS |
| BASED ON THE TYPE OF CONSTRUCTION; AND |
| 3.AS REQUIRED BY TABLE 602 FOR EXTERIOR WALLS BASED ON |
| THE FIRE SEPARATION DISTANCE. |
| |
| 10A)(3). TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL |
| OPENINGS. |
| |
| 10B) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY |
| PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL |
| 1. THE LIFE SAFETY PLAN SHOWS A 2 HOUR FIRE RATED WALL |
| VERSES THE ARCHITECTURAL SHEET 1ST FLOOR SHOWS A 1 HOUR |
| FIRE RATING. SEE FBC-B TABLE 601, 602 AND 704.10. |
| PLEASE NOTE THIS COMMENT IS FOR ALL FIRE RATED WALLS. |
| SHEET 188-AE4.01 ENLARGED FLOOR PLAN DOES SHOW WALL |
| TAGS. SHEET 276-AE7.01 PROVIDES PARTITION TYPES, AND |
| WALL RATINGS. WHEN YOU REFER TO THE UL FIRE RATED |
| ASSEMBLIES, THERE IS NO ASSEMBLY SHOWN ON THE |
| ARCHITECTURAL SHEETS FOR THE INSPECTOR TO FOLLOW, NOR |
| WHEN YOU DO LOOK UP THE ASSEMBLIES THE ASSEMBLY DOES |
| NOT INDICATE HOW TO TREAT THE FLOOR AND MORE IMPORTANT |
| THE WALL TO DECK ABOVE. THE PLAN NOTES JUST STATE TO |
| PROVIDE FR SEALANT AT THE TOP AND BOTTOM OF THE WALL. |
| PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-B SECTION |
| 715.1. JOINTS INSTALLED IN OR BETWEEN |
| FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING |
| ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME |
| PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE |
| RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH |
| THE SYSTEM IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS |
| SHALL BE TESTED IN ACCORDANCE WITH SECTION 715.3. |
| |
| 10C) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY |
| PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL |
| 1. ROOM 105 THE DIESEL TANK ROOM THE LIFE SAFETY PLAN |
| SHOWS A 4 HOUR WALL VERSES THE ARCHITECTURAL SHEET |
| SHOWING NO FIRE RATING. |
| |
| 10D) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY |
| PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL |
| 1. ROOM # 107 THE FIRE PUMP ROOM THE WALLS ARE NOT |
| SHOWN TO HAVE A FIRE RATING ON THE ARCHITECTURAL SHEET. |
| THE 2017 FBC-B 913.2.1 REQUIRES 2 HOUR RATING. |
| |
| 10E) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY |
| PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL |
| 1. ROOM 106 THE GENERATOR ROOM DOES NOT INDICATE RATING |
| OF THE WALLS FOR FIRE ON THE ARCHITECTURAL SHEET. |
| PLEASE SHOW COMPLIANCE WITH 403.4.8.1 OF THE 2017 |
| FBC-B. |
| |
| 10F) 10E) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE |
| SAFETY PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN |
| LEVEL 1. ROOMS 108 POWER ROOM AND 109 EMERGENCY |
| ELECTRIC ROOM ALSO SIMILAR SITUATION, THE ARCHITECTURAL |
| SHEETS DO NOT SHOW WALL RATINGS WHEREAS THE LIFE SAFETY |
| PLAN SHOW A 2 HOUR FIRE RATING. PLEASE NOTE THIS IS A |
| COMMON CODE VIOLATION FOR ALL OF THE 1ST FLOOR, |
| ELEVATOR SHAFTS, ELEVATOR MACHINE ROOMS, STAIRWELLS, |
| AND FIRE RESCUE LOBBY. 107.2.1.2 ADDITIONAL INFORMATION |
| REQUIRED. |
| 10G) SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL VERSES |
| 134-AE1.01 OVERALL FLOOR PLAN LEVEL 1.INTERIOR EXIT |
| STAIRWELL 1 SHOWS A EGRESS CORRIDOR, PLEASE CORRECT ON |
| BOTH SETS OF PLANS. THE VERTICAL INTERNAL EXIT STAIRWAY |
| IS TO TERMINATE AT AN EXIT DISCHARGE. FBC-B 1023.3, THE |
| EXCEPTION ALLOWS FOR AN EXIT PASSAGEWAY COMPLYING WITH |
| 1023.3.1. EXTENSION. PLEASE RENAME TO AN EXIT |
| PASSAGEWAY. |
| 10G)(1) INTERIOR EXIT STAIRWELL 1 AND EXIT PASSAGEWAY. |
| PLEASE NOTE ON THE MECHANICAL SHEET 350-M1.01 THE PLANS |
| INDICATE TO BUILD A 10 INCH WIDE RATED CHASE FOR |
| REFRIGERANT PIPING. THE FBC-B CODE SECTION 1023.2 |
| CONSTRUCTION FOR SHAFT CONSTRUCTION OF THE STAIRWELL |
| FOR 4 STORIES OR MORE REQUIRES 2 HOUR CONSTRUCTION OF |
| FIRE BARRIERS, VERTICAL AND HORIZONTAL. PLEASE REVIEW |
| FBC-B 1023.5 PENETRATIONS AND THE LIMITATION. THERE CAN |
| BE NO HORIZONTAL FIRE BARRIERS BUILT OUT OF DRYWALL, |
| THERE IS NO UL LISTING FOR HORIZONTAL USAGE. PLEASE BE |
| AWARE NO OTHER PLUMBING, OR ELECTRICAL PIPING CAN GO |
| THROUGH THE VERTICAL EXIT NOR THE EXIT PASSAGE WAY, THE |
| FPL VAULT IS JUST TO THE EAST OF THE EXIT |
| PASSAGEWAY!!!! |
| THE OTHER ISSUE WITH EXIT STAIRWELL 1 AND EXIT |
| PASSAGEWAY, SHEET 350-M1.01 DOES INDICATE STAIR |
| PRESSURIZATION FAN LOCATED ON THE MAIN ROOF, BUT THERE |
| IS NO PRESSURIZATION FAN FOR THE EXIT PASSAGEWAY. |
| PLEASE SHOW COMPLIANCE WITH FBC-B SECTION 1024.7 |
| VENTILATION. |
| 10H) LOADING DOCKS WOULD STILL BE CONSIDERED A S2 |
| OCCUPANCY AND REQUIRING SEPARATION FROM THE OTHER |
| OCCUPANCIES AND ANCILLARY USES, SEE TABLE 508.4 OF THE |
| FBC-B. |
| 10I) THE LOADING DOCKS DOES NOT INDICATE IF THIS IS TO |
| BE CONSIDERED AN OPEN OR ENCLOSED PARKING GARAGE? SHOW |
| COMPLIANCE WITH FBC-B 406.5 OPEN PARKING GARAGES OR |
| 406.6ENCLOSED PARKING GARAGES. PLEASE NOTE SHEET |
| 188-AE4.01 SHOWS THE WALL SEPARATING THE S2 OCCUPANCIES |
| FROM MERCANTILE OR BUSINESS AS A NON-RATED WALL BUT 2 |
| C20 AND WALL TYPE C12 BOTH SHOW A 2 HOUR FIRE RATING. |
| SE 2017 FBC-B TABLE 508.4. PLEASE ALSO SEE SHEET |
| 188-AE4.01 DOOR 115A, THIS DOOR DOES NOT SHOW A RATING |
| BETWEEN THE S2/ M, B OCCUPANCIES. SEE OPENING |
| PROTECTIVES. FBC-B 716-5. 107.2.1.2 ADDITIONAL |
| INFORMATION REQUIRE. |
| 10J) SHEET 134-AE1.01 SHOWS A STAIR BY THE CONCRETE |
| RAMP BY THE POWER ROOM 108. PLEASE NOTE THE SAME STAIR |
| ON SHEET 008-LS1.01 IS NOT COMPLETE. 107.2.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| 10K) ADDITIONAL INFORMATION IS REQUIRED, 107.2.1.2. |
| WHEN VIEWING THE 1ST LEVEL LIFE SAFETY PLAN 008-LS1.01 |
| AND SHEET 134-AE1.01 THE FURTHEST EAST PROPERTY LINE |
| GRID LINE 1 THRU 6 IT APPEARS TO BE A 2 HOUR FIRE RATED |
| WALL ON THE 1ST LEVEL. SHEET 154-AE2.02, IN VIEWING THE |
| EAST ELEVATION, GRID LINES 1-6 FOR THE 1ST FLOOR IT |
| WOULD APPEAR THIS AREA HAS COLUMNS AND OPEN AREAS IN |
| THE WALLS? THIS AREA IS ONLY 1 FOOT FROM THE PROPERTY |
| LINE, FBC-B TABLE 705.8 0-3 FEET FROM THE PROPERTY LINE |
| NO OPENINGS ARE ALLOWED. |
| 10L) SHEET 154-AE2.02 THE SOUTH ELEVATION & 164-AE2.19, |
| PLEASE PROVIDE THE TOTAL AMOUNT OF SQUARE FOOT AREA FOR |
| WALL ON THE 1ST FLOOR FROM GRID LINE F TO H. IT WOULD |
| APPEAR YOU ARE OVER THE ALLOWABLE OPENING SIZE OF 45% |
| OF OPENING SIZE FOR UNPROTECTED/ SPRINKLERED FOR 10 TO |
| 15 FOOT FIRE SEPARATION DISTANCE. I GOT A PERCENTAGE OF |
| 47% OPENING. 1360 SQ. FT. WALL AREA AND 643 SQ. FT. |
| OPENING AREA. FBC-B TABLE 705.8. |
| 10M) SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL 1 AND |
| SHEET 134-AE1.01 FLOOR PLAN LEVEL 1 SHOW A ROOM JUST TO |
| THE RIGHT OF ENGINEERING ROOM # 120 THAT DOES NOT HAVE |
| A ROOM TAG NOR IDENTIFY THE USEAGE OF THE ROOM? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| 10N) SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL 1 AND |
| SHEET 134-AE1.01 FLOOR PLAN LEVEL 1. PLEASE NOTE THE |
| FLOOR PLAN DOES IDENTIFY EACH ELEVATOR BUT DOES NOT |
| INDICATE WHICH MACHINE ROOMS ARE FOR WHICH ELEVATORS? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B |
| 3005.1 ACCESS. AN APPROVED MEANS OF ACCESS SHALL BE |
| PROVIDED TO ELEVATOR MACHINE ROOMS, CONTROL ROOMS, |
| CONTROL SPACES AND MACHINERY SPACES, MACHINE ROOMS, |
| CONTROL SPACES AND MACHINERY SPACES IS REQUIRED TO BE |
| APPROVED BY THE BUILDING OFFICIAL. SEE ALSO 2015 IBC |
| COMMENTARY. ONE CONCERN IS FOR ELEVATOR #10 A COMMON |
| ELEVATOR NOT PART OF THE RETAIL TENANT SPACE, BUT TO |
| ACCESS THE MACHINE ROOM FOR THIS ELEVATOR, THE MACHINE |
| ROOM IS LOCATED IN THE RETAIL TENANT SPACE. |
| 10O) 008-LS1.01. TO UNDERSTAND THE EXITING FOR CORRIDOR |
| 126 YOU HAVE TO GO TO THE LIGHTING FLOOR PLAN FOUND |
| UNDER 404-EL1.01. YOU FIND AN EXIT LIGHT BY GRID LINE |
| B/4 FOR THIS DOOR, BUT MISSING DOOR AND EXIT LIGHT BY |
| GRID LINE D/ 6.5. IT WOULD APPEAR THE DESIGNER IS |
| TAKING THIS OCCUPANT LOAD TO THE FRONT LOBBY FOR |
| EXITING. PLEASE CORRECT THE MISSING DOOR AND EXIT LIGHT |
| ON 404-EL1.01. |
| 10P) SHEET 008-LS1.01 LIFE SAFETY PLAN. NOTE ON THE |
| PLANS INDICATES: WHERE THE FIRE SERVICE ACCESS ELEVATOR |
| SHARE THE HOISTWAY WITH ADJACENT PASSENGER ELEVATORS, |
| THE ENTIRE SHAFT ENCLOSURE MUST COMPLY WITH FSAE |
| HOISTWAY PROTECTION. PLEASE EXPLAIN THE NOTE. THE PLAN |
| DEPICTS A SEPARATE HOISTWAY FOR THE FIRE SERVICE ACCESS |
| ELEVATOR. IN THE 2017 FBC-B SECTION 3007.5 HOISTWAY |
| ENCLOSURES. THE FIRE SERVICE ACCESS ELEVATOR HOISTWAY |
| SHALL BE LOCATED IN A SHAFT ENCLOSURE COMPLYING WITH |
| SECTION 713. |
| 10Q) PLEASE NOTE SHEET 188-AE4.01 ENLARGED LEVEL 1 |
| FLOOR PLAN AREA A. THE WALL TYPES ON ALL ELEVATOR WALLS |
| CONTAINING THE ELEVATOR DOORWAY ARE IDENTIFIED AS WALL |
| TYPE 2M6. SHEET 276-AE7.01 PARTITION TYPES. |
| THE ENLARGED FLOOR PLAN INDICATES THE WALL TYPE AS 2M6. |
| THE SHEET 276-AE7.01 PARTITION TYPES INDICATE THIS WALL |
| TO BE A 6 INCH CMU AND 1 5/8 METAL FURRING AND 5/8 INCH |
| GWB A 2 HOUR FIRE DESIGN UL DESIGN # U906. |
| 10Q)(1) PLEASE SUBMIT THE ACTUAL UL LISTED DESIGNS AS |
| PART OF THE PLANS. THE ACTUAL UL DESIGN U906 SHOWS ON |
| ONE SIDE OF THE BLOCK ? INCH PORTLAND CEMENT STUCCO OR |
| GYPSUM PLASTER WHICH WILL ADD ? HOUR TO THE |
| CLASSIFICATION. PLEASE CORRECT LISTING AND SHOW THE |
| CORRECT MATERIALS NOT FURRING AND ? INCH DRYWALL. |
| 2017 FBC-B SHAFTS. 713.4 FIRE-RESISTANCE RATING. SHAFT |
| ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS |
| THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED NOT EXCEED |
| 2 HOURS. SHAFT ENCLOSURES SHALL MEET THE REQUIREMENTS |
| OF SECTION 703.2.1. |
| FBC-B 703.2.1. 703.2.1 NONSYMMETRICAL WALL |
| CONSTRUCTION. INTERIOR WALLS AND PARTITIONS OF |
| NONSYMMETRICAL CONSTRUCTION SHALL BE TESTED WITH BOTH |
| FACES EXPOSED TO THE FURNACE, AND THE ASSIGNED |
| FIRE-RESISTANCE RATING SHALL BE THE SHORTEST DURATION |
| OBTAINED FROM THE TWO TESTS CONDUCTED IN COMPLIANCE |
| WITH ASTM E119 OR UL 263. WHERE EVIDENCE IS FURNISHED |
| TO SHOW THAT THE WALL WAS TESTED WITH THE LEAST |
| FIRE-RESISTANT SIDE EXPOSED TO THE FURNACE, SUBJECT TO |
| ACCEPTANCE OF THE BUILDING OFFICIAL, THE WALL NEED NOT |
| BE SUBJECTED TO TESTS FROM THE OPPOSITE SIDE (SEE |
| SECTION 705.5 FOR EXTERIOR WALLS). |
| 10Q)(2) PLEASE PROVIDE A LETTER FROM THE BLOCK |
| MANUFACTURER AS TO THE 6 INCH CMU MEETS THE MINIMUM |
| EQUIVALENT THICKNESS FOR THE REQUIRED FIRE RATING OF |
| THE ELEVATOR SHAFT WALL CONSTRUCTION SEE FBC-B TABLE |
| 722.3.2. THE LETTER MUST CONTAIN MANUFACTURER, THE TYPE |
| OF AGGREGATE AND THE EQUIVALENT THICKNESS IN INCHES AND |
| THE FIRE RATING THE BLOCK ACHIEVES. THE LETTER MUST BE |
| SIGNED AND THE PERSONS POSITION IN THE COMPANY |
| ATTESTING TO THIS AFFIDAVIT. |
| |
| 10R) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE |
| ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE |
| PLAN LEVEL 1 SHOW COMPLIANCE FOR ELEVATOR CARS TO |
| ACCOMMODATE AN AMBULANCE STRETCHER AS REQUIRED BY |
| SECTION 3002.4 OF THE 2017 FBC-B. |
| 10R)(1) FBC-B 3002.4 THE ELEVATOR CAR SHALL BE OF SUCH |
| A SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE |
| STRETCHER 24 INCHES BY 76 INCHES (610 MM BY 1950 MM) |
| WITH NOT LESS THAN 5-INCH (127 MM) RADIUS CORNERS, IN |
| THE HORIZONTAL, OPEN POSITION... |
| 10R)(2) FBC-B 3002.4. THE HOISTWAY DOOR FRAME SHALL BE |
| IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE |
| NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE |
| PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| 10S) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE |
| ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE |
| PLAN LEVEL 1 SHOW COMPLIANCE FOR: |
| 10S)(1) 2017 FBC-B 403.6.1 FIRE SERVICE ACCESS |
| ELEVATOR. NO FEWER THAN TWO FIRE SERVICE ACCESS |
| ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION |
| 3007 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120 |
| FEET MEASURED FROM THE ELEVATION OF THE STREET LEVEL |
| ACCESS. |
| |
| 10S)(2) 2017 FBC-B 2017 FBC-B 403.6.1 FIRE SERVICE |
| ACCESS ELEVATOR. PLEASE SHOW COMPLIANCE WITH EACH FIRE |
| SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF NOT |
| LESS THAN 3,500 POUNDS. |
| 10S)(3) SHOW COMPLIANCE WITH FBC-B 3007.6.5 FIRE |
| SERVICE ACCESS ELEVATOR SYMBOL. |
| 10S)(4) FBC-B 3007.3 WATER PROTECTION. AN APPROVED |
| METHOD TO PREVENT WATER FROM INFILTRATING INTO THE |
| HOISTWAY ENCLOSURE FROM THE OPERATION OF THE AUTOMATIC |
| SPRINKLER SYSTEM OUTSIDE THE ENCLOSED FIRE SERVICE |
| ACCESS ELEVATOR LOBBY SHALL BE PROVIDED. |
| 10T)(1) BOTH SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL 1 |
| & SHEET 134-AE1.01SHOW A INTERSTITIAL SPACE AND A |
| STAIRWELL 2, A LANDING, EGRESS CORRIDOR AND A STAIRWELL |
| 6. PLEASE CORRECT THE LABELING OF STAIRS AND EGRESS |
| CORRIDOR. THERE SHOULD BE NO STAIR LABELED STAIR 6. |
| SHEET AE3.19 DETAIL 1 OR 173-AE3.03 SHOWS THE VERTICAL |
| EXIT STAIR (STAIR 2) AND THE CONTINUATION OF THIS STAIR |
| BELOW LEVEL 2 TO THE INTERSTITIAL SPACE AND A |
| MID-LANDING THAT CONTINUES OVER TO THE SO-CALLED STAIR |
| 6. THIS IS ONE CONTINUOUS STAIRWAY WHERE THE MIDLANDING |
| IN THE INTERSTITIAL SPACE IS ELONGATED AND THEN |
| CONTINUES TO THE 1ST FLOOR EXIT DOORWAY. |
| THE 2017 FBC-B SECTION 1023.1STATES: INTERIOR EXIT |
| STAIRWAYS AND RAMPS SERVING AS AN EXIT COMPONENT IN A |
| MEANS OF EGRESS SYSTEM SHALL COMPLY WITH THE |
| REQUIREMENTS OF THIS SECTION. INTERIOR EXIT STAIRWAYS |
| AND RAMPS SHALL BE ENCLOSED AND LEAD DIRECTLY TO THE |
| EXTERIOR OF THE BUILDING. THIS STAIRWELL DOES NOT MEET |
| THE DEFINITION OF AN EXIT PASSAGEWAY BECAUSE THE STAIR |
| IS UP OFF THE FLOOR LEVEL LOCATED IN THE INTERSTITIAL |
| SPACE. |
| 10T)(2) PLEASE REVIEW SHEET 216-AE4.28 DETAIL 5, A CUT |
| SECTION THROUGH THE 2 HOUR FIRE RATED INTERIOR EXIT |
| STAIR. THE DETAIL SHOWS A 2 HOUR RATED SHAFT WALL |
| ASSEMBLY. SHEET 276-AE7.01 PARTITIONS 2SW INDICATES THE |
| USE OF SHAFT WALL CONSTRUCTION WITH A UL DESIGN U438. |
| PLEASE INDICATE WHICH SIDE OF THE SHAFT WALL |
| CONSTRUCTION IS TO BE WITHIN THE STAIRWELL SHAFT. THE |
| UL DESIGN PROVIDED DOES NOT INDICATE? PLEASE ALSO |
| PROVIDE THE UL DESIGN AS PART OF THE PLAN DOCUMENTS. |
| 107.2.1.2. ADDITIONAL INFORMATION REQUIRED TO SHOW CODE |
| COMPLIANCE. |
| 10T)(3) SHEET 216-AE4.28 DETAIL # 5 SHOWS THE INTERIOR |
| EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL SPACE WITH |
| A CROSS SECTION VIEW. AS THE STATEMENT ABOVE INDICATES |
| SHAFTWALL CONSTRUCTION SEPARATES THE STAIRWELL FROM THE |
| REMAINDER OF THE FIRST FLOOR AREA. WHAT THIS DETAIL |
| FAILS TO SHOW HOW COMPLIANCE HOW THE FIRE RESISTANCE |
| RATING IS TO BE MAINTAINED FOR ALL OF THE STEEL FRAMING |
| MEMBERS (STEEL ANGLES, SUPPORTS AND STEEL BEAMS) ARE TO |
| BE MAINTAINED. FBC-B 707.3.2 INTERIOR EXIT STAIRWAY AND |
| RAMP CONSTRUCTION. THE FIRE-RESISTANCE RATING OF THE |
| FIRE BARRIER SEPARATING BUILDING AREAS FROM AN INTERIOR |
| EXIT STAIRWAY OR RAMP SHALL COMPLY WITH SECTION 1023.1. |
| INTERIOR EXIT STAIRWAY AND RAMP ENCLOSURES SHALL HAVE A |
| FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE |
| CONNECTING FOUR STORIES OR MORE. SHOW COMPLIANCE. |
| 10T)(4) 10T)(3) SHEET 216-AE4.28 DETAIL # 5 SHOWS THE |
| INTERIOR EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL |
| SPACE WITH A CROSS SECTION VIEW. THIS SAME DETAIL SHOWS |
| A 2 HOUR FIRE RATED MASONRY WALL FROM FLOOR LEVEL OF |
| THE 1ST FLOOR THAT STOPS AS DEPICTED JUST AT THE BOTTOM |
| OF THE 2ND FLOOR CONCRETE PAN JOIST FLOOR SYSTEM. HOW |
| WILL THE 2 HOUR FIRE RATING ACHIEVED WHERE THE TWO |
| MATERIALS MAY OR MAY NOT TOUCH EACH OTHER? |
| 2017 FBC-B 715.1. JOINTS INSTALLED IN OR BETWEEN |
| FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING |
| ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL |
| BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM |
| DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME |
| PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE |
| RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH |
| THE SYSTEM IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS |
| SHALL BE TESTED IN ACCORDANCE WITH SECTION 715.3. |
| 10T)(5) SHEET 216-AE4.28 DETAIL # 5 SHOWS THE INTERIOR |
| EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL SPACE WITH |
| A CROSS SECTION VIEW. SINCE THE STRUCTURAL INDEX IS |
| MISSING 57 SHEETS, PLEASE PROVIDE WHERE THE STRUCTURAL |
| DETAILS ARE LOCATED FOR THE STRUCTURAL MEMBERS, AND |
| ATTACHMENT TO OTHER STRUCTURAL FRAMING MEMBERS. 2017 |
| WEST PALM BEACH AMENDMENTS 107.2.1.2. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 10T)(6) SHEET 208-AE4.20 DETAIL # 3 SHOWS THE INTERIOR |
| EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL SPACE WITH |
| A CROSS SECTION VIEW. SHEET 215-AE4.27 DETAIL 4 SHOWS A |
| CROSS SECTION OF THE STAIRWAY ON THE 1ST FLOOR A RETAIL |
| AREA WITH RAMP IS SHOWN AND DIRECTLY ABOVE THE STAIR |
| LANDING LOCATED IN THE A INTERSTITIAL SPACE WITH A 5 |
| INCH CONCRETE SLAB. PLEASE ALSO NOTE MAKING THE FIRE |
| RATED WALL ON THE EDGE OF THE INTERSTITIAL LANDING IS A |
| MASONRY WALL. SHEET 208-AE4.20 DETAIL 3 SHOWS THIS WALL |
| BUT THE MASONRY WALL DOES NOT HAVE A WALL TAG |
| IDENTIFYING THE FIRE RATING OR WALL TYPE. SEE 2017 |
| FBC-B 713.4. SHAFT ENCLOSURES SHALL HAVE A |
| FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE |
| CONNECTING FOUR STORIES. |
| 10T)(7) SHEET 216-AE4.28 DETAIL # 5 SHOWS A CROSS |
| SECTION OF THE STAIRWELL IN THE INTERSTITIAL SPACE. THE |
| DETAIL FAILS TO INDICATE HOW A 2 HOUR FIRE RATED FLOOR |
| ASSEMBLY IS TO BE ACHIEVED? SEE SECTION 713.4 OF THE |
| 2017 FBC-B, SECTION SHAFT ENCLOSURES SHALL HAVE A |
| FIRE-RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY |
| PENETRATED, BUT NEED NOT EXCEED 2 HOURS. ALSO TABLE 601 |
| FLOOR CONSTRUCTION. |
| 10T)(8) PLEASE NOTE THE STAIRWAY #2 AN INTERIOR EXIT |
| STAIRWAY THAT IS CONTINUOUS TO THE EXTERIOR DOES NOT |
| SHOW STAIRWELL PRESSURIZATION, SMOKEPROOF ENCLOSURES, |
| IN ANY OF THE MECHANICAL PLANS, SEE 2017 FBC-B 1023.11 |
| SMOKEPROOF ENCLOSURES. WHERE REQUIRED BY SECTION |
| 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND RAMPS |
| SHALL BE SMOKEPROOF ENCLOSURES IN ACCORDANCE WITH |
| SECTION 909.20. |
| 11) LEVEL 2: 09LS1.02, 135-AE1.02, & 190/191 AE4.02 A & |
| B: |
| |
| 11A)(1) THE LIFE SAFETY SHEET ANALYSIS, NOR LS1, NOR |
| LS2 SHOW AN ANALYSIS OF THE PARKING STRUCTURE, HOW MANY |
| TOTAL PARKING SPACES THERE IS OR HOW MANY ACCESSIBLE |
| PARKING SPACES THERE IS OR COMPLIANCE WITH THE 2017 |
| FBC-ACCESSIBLE PARKING SPACES. SHOW ACCESSIBLE MATRIX. |
| |
| 11A)(2) SHEET 135-AE1.02 THE OVERALL FLOOR PLAN FOR |
| LEVEL 2 SHOWS 4 ACCESSIBLE PARKING SPACES, 3 ACCESSIBLE |
| SPACES. SHOW THE ACCESSIBLE ROUTE FOR A WHEEL CHAIR TO |
| BE ABLE TO GET TO AN ELEVATOR WITHOUT HAVING TO GO OUT |
| INTO THE VEHICULAR TRAVEL LANE. ACCESSIBILITY CODE |
| SECTION 206.2. WHERE REQUIRED. AN |
| ACCESSIBLE ROUTE SHALL BE PROVIDED WHERE REQUIRED BY |
| 206.2. |
| 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE |
| SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE |
| FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES |
| THAT ARE ON THE SAME SITE. |
| |
| 11B) COMMENT FOR ALL PARKING FLOORS. PLEASE ALSO SHOW |
| COMPLIANCE WITH SECTION 208.2.4. VAN PARKING SPACES. |
| WHERE VAN PARKING IS PROVIDED PURSUANT TO SECTION |
| 502.2, FOR EVERY SIX OR FRACTION OF SIX PARKING SPACES |
| REQUIRED BY 208.2 TO COMPLY WITH 502, AT LEAST ONE |
| SHALL BE A VAN PARKING SPACE COMPLYING WITH 502. |
| |
| 11C) COMMENT FOR ALL PARKING FLOORS. SHEET 182-AE3.18 |
| BUILDING SECTION. THE PLAN SHOWS ELEVATIONS OF THE |
| VARIOUS FLOOR LEVELS AND BY MEASURING BETWEEN FLOOR |
| SLABS IT WOULD APPEAR THERE MAYBE ONLY 7 FEET 8 INCHES |
| FROM THE BOTTOM OF THE FLOOR PRECAST AND FINISH FLOOR |
| BELOW. PLEASE PROVIDE THE CLEAR HEIGHT BETWEEN FLOOR |
| SLABS AND THE PRECAST FLOOR JOIST ABOVE, AND ALSO |
| PROVIDE FOR THE FIRE SPRINKLERS TO HAVE A TRUE HEIGHT |
| FOR THE RAMPS AND FOR THE PARKING AREAS. PLEASE SHOW |
| HOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE SECTION |
| 502.5 VERTICAL CLEARANCE. PARKING SPACES FOR VANS AND |
| ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM SHALL |
| PROVIDE A VERTICAL CLEARANCE OF 98 INCHES MINIMUM. |
| |
| 11D) PLEASE REVIEW SHEET 270-AE5.39 PARKING DETAILS. |
| PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE SEE THE |
| ADVISORY 502.3.3 MARKING. |
| 2017 ACCESSIBILITY CODE. ADVISORY 502.3.3 MARKING. THE |
| METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY THESE |
| REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL |
| LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS PERMIT |
| THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING SPACE, |
| IT IS IMPORTANT THAT THE AISLE BE CLEARLY MARKED. |
| FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL |
| STRIPING OF ACCESS AISLES. |
| PLEASE REFER TO THE WEST PALM BEACH MUNI CODE 94-485 |
| FOR STALL PAINTING DETAILS AND REQUIRED DOUBLE LINE |
| DIMENSIONS. |
| |
| 11E) THE 2ND LEVEL FLOOR PLAN, : 09LS1.02, 135-AE1.02, |
| & 190/191 AE4.02 A & B: WILL NEED TO PROVIDE WHAT THE |
| DESIGN FOR THE PARKING FLOORS, IF THESE FLOOR LEVELS |
| ARE TO BE CONSIDERED AN OPEN OR ENCLOSED PARKING |
| GARAGE? SHOW COMPLIANCE WITH FBC-B 406.5 OPEN PARKING |
| GARAGES OR 406.6ENCLOSED PARKING GARAGES. |
| IF CONSIDERED OPEN SHOW COMPLIANCE ON THE ELEVATION |
| SHEETS AE2.10 THROUGH AE2.22. PLEASE SHOW THE WALL AREA |
| IN SQ. FEET. THE OPENING IN SQUARE FEET, PERCENTAGE OF |
| OPENING, DEDUCT FOR THE ALUMINUM ARCHITECTURAL SCREEN |
| AND TAKE A SECOND DEDUCTION FOR THE BIRD SCREEN AS |
| WELL. SHOW COMPLIANCE WITH 406.5.2 OPENINGS OF THE 2017 |
| FBC-B AND 406.5.6 FIRE SEPARATION DISTANCE CONCERNS |
| WITH SOUTH WALL ON GRID LINES F-H SHEET 182AE3.18 SHOWS |
| THIS AREA OF THE PARKING GARAGE EXTENDED OVER THE 1ST |
| FLOOR LEVEL. |
| |
| 11F) BOTH SHEETS 135-AE1.02 LEVEL 2 AND 190AE4.02 BOTH |
| SHOW ATTENDANT BOOTHS AND A GATED ENTRANCE TO THE |
| PARKING LEVELS. |
| |
| 11F)(1) PLEASE SHOW CUT SECTIONS FOR THE ATTENDANT |
| BOOTHS OF HOW THEY ARE GOING TO BE ANCHORED FOR THE |
| WIND, DOES THE WIND TUNNEL TEST HAVE A PRESSURE POINT |
| FOR THE BOOTHS, IF NOT HOW ARE PRESSURES TO BE DERIVED? |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B |
| 1609.1.1 DETERMINATION OF WIND LOADS. |
| |
| 11F)(2) ADDITIONAL INFORMATION IS REQUIRED FOR THE |
| ATTENDANT BOOTHS, ARE THESE BOOTHS PRE-MANUFACTURERED |
| (MODULAR) BUILDINGS UNDER FLORIDA S. 553 PART I |
| MANUFACTURED BUILDINGS? |
| |
| 11G) THE PLANS ALSO SHOW USE OF VEHICULAR GATES. IF |
| THEY USE KEY CARDS THE THEY WOULD ALSO BE CONSIDERED |
| AUTOMATIC VEHICULAR GATES HAVING TO COMPLY WITH: FBC-B |
| 3110.1 AUTOMATIC VEHICULAR GATES SHALL COMPLY WITH THE |
| REQUIREMENTS OF SECTIONS 3110.2 THROUGH 3110.4 AND |
| OTHER APPLICABLE SECTIONS OF THIS CODE. |
| |
| 11H) OFFICE 202, AREA OF 5,812 SQ. FT. AND FUTURE |
| RESTROOMS MAY BE AT THE OWNERS OWN RISK!!!! DEPENDING |
| ON IF THE OFFICE AREA IS SUB-DIVIDED IN TO 2 TENANTS |
| AND THE LARGER OF THE 2 TENANTS HAS OVER 49 OCCUPANTS |
| THEN 2 EXITS WOULD BE REQUIRED. 2017 FBC-B TABLE |
| 1006.2.1 .SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY. |
| |
| 11I) THIS SHEET (155-AE2.10 KEY NOTE 13 AND OTHER |
| ELEVATION SHEETS) INDICATE THE USE OF COMPOSITE METAL |
| PANELS. PLEASE PROVIDE DOCUMENTATION FOR CODE |
| COMPLIANCE WITH FBC-B 1407.2. MCM USED AS EXTERIOR WALL |
| FINISH OR AS ELEMENTS OF CLADDING OR WEATHER RESISTANCE |
| SHALL COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14. |
| PROVIDE DOCUMENTATION FOR ALL OF THE CODE SECTIONS |
| INCLUDED INCLUDING SEPARATION DISTANCE FOR FIRE. |
| |
| 11J) SHEET 190-AE4.02 AREA A. JUST OUTSIDE OF STAIR 2 |
| THERE IS A MECHANICAL SHAFT THAT GOES VERTICALLY |
| THROUGH THE BUILDING INCLUDING THE FUTURE SHELL OFFICE |
| FLOORS. THE WALL TYPE IS NOT INDICATED WITH A WALL TAG |
| IT WOULD APPEAR TO BE A 2 HOUR FIRE RATED SHAFT WALL. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 12) SHEET 204-AE4.09 FLOOR PLAN & TERRACE PLAN. |
| |
| 12A) DOORS 901A, 901B, 901C & 901D ALL ONLY HAVE 1 FOOT |
| ON THE PULL SIDE OF THE DOOR LATCH. THE 2017 |
| FBC-ACCESSIBILITY CODE REQUIRED 18 INCHES MINIMUM. 2017 |
| FBC- ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| DOORS. DOORS 901 B & 901C BOTH HAVE ADA PUSH PLATE |
| BOLLARDS, PLEASE PROVIDE DETAILS FOR AN ACCESSIBLE |
| ENTRANCE. SHOW COMPLIANCE WITH 2017 ACCESSIBILITY CODE |
| 404.3 AUTOMATIC AND POWER-ASSISTED DOORS AND GATES. |
| AUTOMATIC DOORS AND AUTOMATIC GATES SHALL COMPLY WITH |
| 404.3. FULL-POWERED AUTOMATIC DOORS SHALL COMPLY WITH |
| ANSI/BHMA A156.10 (INCORPORATED BY REFERENCE, SEE |
| ?REFERENCED STANDARDS? IN CHAPTER 1). LOW-ENERGY AND |
| POWER-ASSISTED DOORS SHALL COMPLY WITH ANSI/BHMA |
| A156.19 (1997 OR 2002 EDITION) (INCORPORATED BY |
| REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1). |
| |
| 12B) EGRESS DOORS THAT ARE NOT ACCESSIBLE (901A & 901D) |
| WILL NEED DIRECTIONAL SIGNAGE TO WHERE THE ACCESSIBLE |
| MEANS OF EGRESS IS LOCATED. SHOW COMPLIANCE WITH: |
| 2017 FBC-ACCESSIBILITY CODE SECTION 216.4.3 DIRECTIONAL |
| SIGNS. SIGNS REQUIRED BY SECTION 1003.2.13.6 OF THE |
| INTERNATIONAL BUILDING CODE (2000 EDITION) OR SECTION |
| 1007.7 OF THE INTERNATIONAL BUILDING CODE (2003 |
| EDITION) (INCORPORATED BY REFERENCE, SEE ?REFERENCED |
| STANDARDS? IN CHAPTER 1) TO PROVIDE DIRECTIONS TO |
| ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH 703.5. |
| |
| 12C) SHEET 204-AE4.09 9TH FLOOR AND TERRACE PLAN. THERE |
| IS A NOTE STATING CROSSHATCHED AREA INDICATES THE |
| EXTENT OF SPRAYED ON INSULATION THERMAL INSULATION |
| APPLIED TO THE UNDERSIDE OF THE LEVEL OF THE 9TH FLOOR |
| SLAB. SEE SECTIONS FOR ADDITIONAL INFORMATION. NEITHER |
| SECTIONS 170-AE3.00 NOR 182-AE3.18 PROVIDE ANY MORE |
| INFORMATION ABOUT THE SPRAY ON THERMAL INSULATION. THE |
| ENERGY CALCULATIONS WILL ALSO NEED TO SHOW THE SAME |
| TYPE OF INSULATION AN R-RATING. 107.2.1.2 ADDITIONAL |
| INFORMATION REQUIRED. SHEET 271-AE5.40 SHOWS |
| LIGHTWEIGHT INSULATING CONCRETE BEING APPLIED TO THE |
| ROOF TOP STRUCTURAL DECK. |
| |
| 12D) SHEET 204-AE4.09 9TH FLOOR AND TERRACE PLAN SHOWS |
| THE USE OF CONCRETE PEDESTAL PAVER SYSTEMS SPECIALTY |
| ENGINEERED FOR APPLICABLE WIND LOAD RATING. IF THIS IS |
| TO BE A DEFERRED SUBMITTAL PLEASE REQUEST IN THE |
| RESPONSE NARRATIVE. 107.2.1.2 ADDITIONAL INFORMATION |
| REQUIRED. DELEGATED ENGINEERING. 61G15-30.003 |
| ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006 |
| (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW BEFORE BEING SUBMITTED TO THE BUILDING |
| DEPARTMENT. |
| |
| 13) SHEET 143-AE1.10 FLOOR PLAN LEVEL 18/ ROOF PLAN: |
| |
| 13A) PLEASE PROVIDE HOW THE WINDOW WASHER EQUIPMENT |
| ROOF ANCHOR WILL WORK WITHOUT INTERFERING WITH THE |
| HORIZONTAL ALUMINUM METAL PANEL SYSTEM. WILL THE |
| ALUMINUM METAL PANEL SYSTEM TAKE THE ADDITIONAL WEIGHT |
| OF THE WINDOW WASHERS? EQUIPMENT/ SCAFFOLDING. PLEASE |
| SHOW COMPLIANCE WITH 2017 FBC-B SECTIONS: |
| 1607.9.3 ELEMENTS SUPPORTING HOISTS FOR FA?ADE ACCESS |
| EQUIPMENT. IN ADDITION TO ANY OTHER APPLICABLE LIVE |
| LOADS, STRUCTURAL ELEMENTS THAT SUPPORT HOISTS FOR |
| FA?ADE ACCESS EQUIPMENT SHALL BE DESIGNED FOR A LIVE |
| LOAD CONSISTING OF THE LARGER OF THE RATED LOAD OF THE |
| HOIST TIMES 2.5 AND THE STALL LOAD OF THE HOIST. |
| |
| 1607.9.4 LIFELINE ANCHORAGES FOR FA?ADE ACCESS |
| EQUIPMENT. IN ADDITION TO ANY OTHER APPLICABLE LIVE |
| LOADS, LIFELINE ANCHORAGES AND STRUCTURAL ELEMENTS THAT |
| SUPPORT LIFELINE ANCHORAGES SHALL BE DESIGNED FOR A |
| LIVE LOAD OF AT LEAST 3,100 POUNDS FOR EACH ATTACHED |
| LIFELINE, IN EVERY DIRECTION THAT A FALL ARREST LOAD |
| MAY BE APPLIED. |
| |
| 13B) THE OVERALL ROOF PLAN SHOWS METAL STAIRS AND METAL |
| PLATFORM AND GUARDRAIL SYSTEM AT GRIDLINE D BETWEEN 3 |
| AND 4, PLEASE PROVIDE A CUT SECTION THROUGH THIS AREA |
| TO BE ABLE TO DETERMINE CODE COMPLIANCE. 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED. SHEET 170-AE3.00 |
| SHOWS THE SAME METAL STAIR PLATFORM AND GUARDRAIL |
| SYSTEM BUT NO CUT SECTIONS OR LIVE LOAD, LOADING |
| CRITERIA. |
| |
| 14) PLEASE NOTE, ONCE THE WIND TUNNEL TESTING REPORT IS |
| SUBMITTED, REVIEWED AND APPROVED PRODUCT APPROVALS THEN |
| CAN COME IN AFTER PERMIT ISSUANCE AS A DEFERRED |
| SUBMITAL. WILL NEED A WRITTEN RESPONSE IF DEFERRED |
| SUBMITTALS WILL BE USED FOR PRODUCT APPROVALS. |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 15A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 15B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 16) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 17) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2 |
| PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP VENTILATORS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G) EXTERIOR PRE-ENGINEERED A/C STANDS AND OR CURBS |
| |
| 18) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 19) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| COMPLIANCE WITH 2017BC-B SECTIONS; |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.3 STRUCTURAL DESIGN. |
| 1408.4 WEATHER RESISTANCE. |
| 1408.4.1 EIFS WITH DRAINAGE. |
| 408.4.1.1 WATER-RESISTIVE BARRIER. |
| 1408.5 INSTALLATION. |
| |
| 20) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, |
| THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE |
| AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE. |
| |
| 21) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS. |
| 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 22) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS |
| 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| 23) . FOR ELECTRONIC REVIEWS. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
2018-11-01 09:54:14 | BUILDING PLANS EXAMINER PLEASE CHECK THE AMOUNT OF |
| PENETRATION IN AND OUT OF THE STAIRWELLS FOR THE BDA |
| SYSTEM SHOWN ON PAGES T5.03. JLEAHY |