Plan Review Notes
Plan Review Notes For Permit 18090449
Permit Number 18090449
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-01 10:56:54PLAN PASSED WITH PROVISIONS:
  
 AS PER FBC EB 808.1 FOR A LEVEL 2 ALTERATION
  
 KITCHEN LIGHTING TO BE AFCI PROTECTED AS PER 210.12A&B
 NEC
  
 EXHAUST FAN IN KITCHEN TO BE AFCI PROTECTED AS PER
 210.12 NEC
  
 ALL RECEPTACLES BOTH NEW AND REPLACED TO BE AFCI/GFCI
 PROTECTED IN KITCHEN THAT SERVE COUNTERTOPS 210.8A#6 &
 210.12A
  
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER