2018-09-28 12:56:31 | 1ST REVIEW FBC-2017 RESIDENTIAL MECHANICAL |
| |
| CODES IN EFFECT: |
| |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE MODEL NUMBERS FOR THE CONDENSER AND AIR HANDLER |
| ON THE AC CALCULATION COOLING EQUIPMENT SUMMARY DO NOT |
| MATCH THE MODEL NUMBERS ON THE AHRI CERTIFICATE. |
| |
| 2) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN- SECTION |
| 107.2.1 WPB. |
| |
| 3) THE 14X22" MAIN RETURN GRILL IS UNDERSIZED FOR 1225 |
| CFMS- MIN. 600 SQ. INCHES REQUIRED PER SECTION M1602.3 |
| FBC R. |
| |
| 4) INDICATE THE AIR HANDLER HAS A MINIMUM 3" CLEARANCE |
| ALONG THRE SIDES, BACK, AND TOP OF THE CLOSET WITH THE |
| TOTAL ENCLOSING SPACE NOT LESS THAN 12 INCJES WIDER |
| THAN THE AIR HANDLER- SECTION M1305.1.1 FBC M. |
| |
| 5) RETURN AIR FROM THE BEDROOMS IS REQUIRED BY SECTION |
| M1602.3 FBC M. PLEASE REVIEW ITEMS 1 OR 2 AND REVISE |
| THE PLAN TO PROVIDE EITHER TRANSFER DUCTS OR GRILLS. |
| |
| 6) PROVIDE A CONDENSATE DISPOSAL PLAN PER SECTION |
| M1411.3 FBC M. |
| |
| 7) SHOW THE LOCATION OF THE CONDENSER AND PROVIDE |
| MOUNTING PAD DETAILS |
| |
| 9) SIGNATURE OF THE CONTRACTOR OR QUALIFIER REQUIRED TO |
| BE ON THE PLAN PER SECTION 107.2.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |