Plan Review Notes For Permit 18090428 |
Permit Number |
18090428 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-12 13:29:18 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. A2.3 DETAIL #1 PLEASE PLACE THE DIMENSIONS ON | | THE CLEAR FLOOR SPACE FOR ALL THE THE PLUMBING | | FIXTURES. THE URINAL WILL BE ENCROACHING INTO THE CLEAR | | FLOOR SPACE OF THE TOILET YOU HAVE 73" MINUS 60" FOR | | THE CLEAR FLOOR SPACE ONLY LEAVES YOU 13" FOR THE | | URINAL WHICH ARE NORMALLY OVER 14" FROM THE WALL TO THE | | FRONT OF THE URINAL IT SHALL COMPLY WITH FBC ACC | | 604.3.1, 604.3.2 | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|