2018-10-12 13:29:181ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A2.3 DETAIL #1 PLEASE PLACE THE DIMENSIONS ON
 THE CLEAR FLOOR SPACE FOR ALL THE THE PLUMBING
 FIXTURES. THE URINAL WILL BE ENCROACHING INTO THE CLEAR
 FLOOR SPACE OF THE TOILET YOU HAVE 73" MINUS 60" FOR
 THE CLEAR FLOOR SPACE ONLY LEAVES YOU 13" FOR THE
 URINAL WHICH ARE NORMALLY OVER 14" FROM THE WALL TO THE
 FRONT OF THE URINAL IT SHALL COMPLY WITH FBC ACC
 604.3.1, 604.3.2
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  