2018-10-10 12:45:01 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090428 |
| 10/10/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) AC SYSTEMS #2 & 3 HAVE INCREASED IN CAPACITY WHICH |
| INDICATES THEY ARE OVERSIZED ACCORDING TO THE APPROVED |
| AC COOLING AND HEATING CALCULATIONS THAT WERE SUBMITTED |
| UNDER PERMIT #17080883. THIS IS AN ENERGY CODE |
| VIOLATION PER SECTION C403.2.2 FBC EC. |
| |
| 2) THE COOLING AND HEATING CAPACITIES FOR AC SYSTEMS #2 |
| & 3 SHOWN IN THE REVISED EQUIPMENT SCHEDULE DO NOT |
| MATCH THE DATA SHOWN IN THE APPROVED ENERGY |
| CALCULATIONS. |
| |
| 3) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR |
| SYSTEMS OF AHU- 2 & 3 PER SECTION 606.2.1 FBC M. PLEASE |
| NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT |
| CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |