Plan Review Notes
Plan Review Notes For Permit 18090428
Permit Number 18090428
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-10 12:45:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090428
 10/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AC SYSTEMS #2 & 3 HAVE INCREASED IN CAPACITY WHICH
 INDICATES THEY ARE OVERSIZED ACCORDING TO THE APPROVED
 AC COOLING AND HEATING CALCULATIONS THAT WERE SUBMITTED
 UNDER PERMIT #17080883. THIS IS AN ENERGY CODE
 VIOLATION PER SECTION C403.2.2 FBC EC.
  
 2) THE COOLING AND HEATING CAPACITIES FOR AC SYSTEMS #2
 & 3 SHOWN IN THE REVISED EQUIPMENT SCHEDULE DO NOT
 MATCH THE DATA SHOWN IN THE APPROVED ENERGY
 CALCULATIONS.
  
 3) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR
 SYSTEMS OF AHU- 2 & 3 PER SECTION 606.2.1 FBC M. PLEASE
 NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  