Plan Review Notes For Permit 18090425 |
Permit Number |
18090425 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-14 15:38:38 | 1ST REVIEW FBC-2017 MECHANICAL | | REVISON #18090425 | | MASTER # 18010366 | | 9/14/18 | | | | CODES IN EFFECT: | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) CONTRACTOR'S SIGNATURE REQUIRED ON THE REVISED PLAN. | | | | 2) THE 8" DUCT IS UNDERSIZED FOR SUPPLYING 268 CFMS OF | | AIR WHEN CHECKED WITH THE DUCTOLATOR AT 0.1" FRICTION | | LOSS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|