Plan Review Notes
Plan Review Notes For Permit 18090399
Permit Number 18090399
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-04 14:35:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE. SEAL AND SIGNATURE
 REQUIRED.
 2. PROVIDE PIPING MATERIALS TYPE & FIRE RATED
 ASSEMBLIES FOR NEW OR RELOCATED PIPING FLOOR
 PENETRATIONS PER WPB FBC 107.2.1
 3. RE: PLAN SHEET P-1.0; FIXTURE DRAIN FOR KITCHEN SINK
 SHALL BE PROVIDED WITH AN AIR ADMITTANCE VALVE IN
 ACCORDANCE WITH FBC PL SECTION 918 OR SHALL CONNECT TO
 THE VERTICAL PORTION OF THE EXISTING VENT AND SHALL NOT
 CONNECT BELOW THE WEIR OF THE TRAP PER FBC PL 909.2.
 4. RE: PLAN SHEET P-1.0; FIXTURE DRAIN FOR LAVATORY
 SHALL BE PROVIDED WITH AN AIR ADMITTANCE VALVE IN
 ACCORDANCE WITH FBC PL SECTION 918 OR SHALL CONNECT TO
 THE VERTICAL PORTION OF THE EXISTING VENT AND SHALL NOT
 CONNECT BELOW THE WEIR OF THE TRAP PER FBC PL 909.2.
 UPON REVIEW OF THE DIFFERENCE BETWEEN THE DEMO PLAN
 (A-2.0)AND THE PROPOSED PLAN (A-2.1) IT APPEARS THAT
 THE EXISTING VERTICAL VENT WILL BE DEMOLISHED ALONG
 WITH THE WALL REMOVAL. PLEASE CLARIFY. WPB FBC 107.2.1
 5. RE: PLAN SHEET P-1.0; THIS PROJECT IS NOT CONSIDERED
 RESIDENTIAL (ONE AND TWO FAMILY) AS NOTED IN WPB FBC
 107.3.5.3, BUT PLUMBING AS NOTED IN WPB FBC
 107.3.5.1.3; THEREFORE REFERENCES TO FBC RESIDENTIAL
 CODE SUCH AS P2701, TABLE P3002.1.1 AND P3002.1.2 SHALL
 BE REPLACED WITH APPROPRIATE SECTIONS OF FBC PLUMBING
 CHAPTERS 4 AND 7. ADDITIONALLY THE CHART FOR PLUMBING
 FIXTURE MAXIMUM FLOW RATES SHALL CONFORM TO THE
 REQUIREMENTS OF FBC PLUMBING CHAPTER 6.
 6. RE: PLAN SHEET P-1.0; REPLACE THE NOTE CONCERNING
 THE ANTI-SCALD CONTROL VALVE(S) FOR SHOWERS AND
 BATHTUBS WITH THE FOLLOWING " SHOWER AND COMBINATION
 TUB/SHOWER CONTROLS SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP. FPC PL
 424.3"
 7. RE: PLAN SHEET P-1.0; PLUMBING NOTE #1. ADD THE WORD
 "PLUMBING" AFTER THE WORD "EDITION". WPB FBC 107.2.1
 8. RE: PLAN SHEET P-1.0; PLUMBING NOTE #10. REPLACE THE
 WORD "CHAMBERS" WITH THE WORDS "HAMMER ARRESTORS". WPB
 FBC 107.2.1, FPC PL 604.9
 9. RE: PLAN SHEET P-1.0; PLUMBING NOTE #5. ADD TO NOTE
 THE WORDS "SHOULD FIELD CONDITIONS WARRANT DESIGN
 CHANGE ' AREVION SHALL BE SUBMITTED TO THE WPB BUILDING
 DEPARTMENT FOR REVIEW FOR COMPLIANCE." WPB FBC SECTION
 105
 10. RE: PLAN SHEET P-1.0; THE SCOPE OF WORK DOES NOT
 SEEM TO INDICATE ANY STORM DRAINAGE WORK. PLEASE REMOVE
 THE NOTE CONCERNING RAINWATER OR SHOW SUCH WORK ON THE
 PLANS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715