2018-10-04 14:35:30 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW: |
| PLUMBING COMMENTS: DENIED |
| |
| 1. CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY |
| CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA |
| ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES & |
| 61G1 FLORIDA ADMINISTRATIVE CODE. SEAL AND SIGNATURE |
| REQUIRED. |
| 2. PROVIDE PIPING MATERIALS TYPE & FIRE RATED |
| ASSEMBLIES FOR NEW OR RELOCATED PIPING FLOOR |
| PENETRATIONS PER WPB FBC 107.2.1 |
| 3. RE: PLAN SHEET P-1.0; FIXTURE DRAIN FOR KITCHEN SINK |
| SHALL BE PROVIDED WITH AN AIR ADMITTANCE VALVE IN |
| ACCORDANCE WITH FBC PL SECTION 918 OR SHALL CONNECT TO |
| THE VERTICAL PORTION OF THE EXISTING VENT AND SHALL NOT |
| CONNECT BELOW THE WEIR OF THE TRAP PER FBC PL 909.2. |
| 4. RE: PLAN SHEET P-1.0; FIXTURE DRAIN FOR LAVATORY |
| SHALL BE PROVIDED WITH AN AIR ADMITTANCE VALVE IN |
| ACCORDANCE WITH FBC PL SECTION 918 OR SHALL CONNECT TO |
| THE VERTICAL PORTION OF THE EXISTING VENT AND SHALL NOT |
| CONNECT BELOW THE WEIR OF THE TRAP PER FBC PL 909.2. |
| UPON REVIEW OF THE DIFFERENCE BETWEEN THE DEMO PLAN |
| (A-2.0)AND THE PROPOSED PLAN (A-2.1) IT APPEARS THAT |
| THE EXISTING VERTICAL VENT WILL BE DEMOLISHED ALONG |
| WITH THE WALL REMOVAL. PLEASE CLARIFY. WPB FBC 107.2.1 |
| 5. RE: PLAN SHEET P-1.0; THIS PROJECT IS NOT CONSIDERED |
| RESIDENTIAL (ONE AND TWO FAMILY) AS NOTED IN WPB FBC |
| 107.3.5.3, BUT PLUMBING AS NOTED IN WPB FBC |
| 107.3.5.1.3; THEREFORE REFERENCES TO FBC RESIDENTIAL |
| CODE SUCH AS P2701, TABLE P3002.1.1 AND P3002.1.2 SHALL |
| BE REPLACED WITH APPROPRIATE SECTIONS OF FBC PLUMBING |
| CHAPTERS 4 AND 7. ADDITIONALLY THE CHART FOR PLUMBING |
| FIXTURE MAXIMUM FLOW RATES SHALL CONFORM TO THE |
| REQUIREMENTS OF FBC PLUMBING CHAPTER 6. |
| 6. RE: PLAN SHEET P-1.0; REPLACE THE NOTE CONCERNING |
| THE ANTI-SCALD CONTROL VALVE(S) FOR SHOWERS AND |
| BATHTUBS WITH THE FOLLOWING " SHOWER AND COMBINATION |
| TUB/SHOWER CONTROLS SHALL BE PRESSURE BALANCED |
| PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE |
| TYPES WITH HIGH TEMPERATURE LIMITING STOP. FPC PL |
| 424.3" |
| 7. RE: PLAN SHEET P-1.0; PLUMBING NOTE #1. ADD THE WORD |
| "PLUMBING" AFTER THE WORD "EDITION". WPB FBC 107.2.1 |
| 8. RE: PLAN SHEET P-1.0; PLUMBING NOTE #10. REPLACE THE |
| WORD "CHAMBERS" WITH THE WORDS "HAMMER ARRESTORS". WPB |
| FBC 107.2.1, FPC PL 604.9 |
| 9. RE: PLAN SHEET P-1.0; PLUMBING NOTE #5. ADD TO NOTE |
| THE WORDS "SHOULD FIELD CONDITIONS WARRANT DESIGN |
| CHANGE ' AREVION SHALL BE SUBMITTED TO THE WPB BUILDING |
| DEPARTMENT FOR REVIEW FOR COMPLIANCE." WPB FBC SECTION |
| 105 |
| 10. RE: PLAN SHEET P-1.0; THE SCOPE OF WORK DOES NOT |
| SEEM TO INDICATE ANY STORM DRAINAGE WORK. PLEASE REMOVE |
| THE NOTE CONCERNING RAINWATER OR SHOW SUCH WORK ON THE |
| PLANS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |