Plan Review Notes For Permit 18090399 |
Permit Number |
18090399 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-10-03 18:21:24 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING : | | 1. SECTION (FBC 107.2.1) PAGE A-1.1, GENERAL DESIGN, | | ?BROWARD COUNTY AMENDMENTS? NEEDS TO BE REMOVED FROM | | PLAN IN ADDITION TO ALL OF THE NON-RELATED GENERAL | | NOTES. | | 2. SECTION (FBC 1609.4.3) PAGE A-1.1, GENERAL DESIGN | | CRITERIA, WIND EXPOSURE CATEGORY ?C? SHOULD BE CATEGORY | | ?D?. | | 3. SECTION (FBC 310.4 & FBC 107.2.1) PAGE A-2.1, | | EXISTING BUILDING INFORMATION SHOWS AN ?R-3? OCCUPANCY | | THAT SHOULD BE AN ?R-2? OCCUPANCY AND THE WORD | | (RESTORATION) LEVEL 2 SHOULD BE CHANGED TO (ALTERATION) | | LEVEL 2. | | 4. SECTIONS: (FEB 801.2 & FEB 707.4), (FBC 1609 & FBC | | 107.2.1) PAGE A-2.1 EXTERIOR DOOR PRESSURES NEED TO BE | | SHOWN ON PLAN AND IN A SUBMITTED PRODUCT APPROVAL. | | 5. SECTIONS: (FBC 107.2.1), (F.S. 481.221), (FAC RULE | | 61G1-16.001) ALL PAGES, ARCHITECT?S REGISTRATION NUMBER | | AND SEAL ARE NOT CLEAR. | | |
|