2018-10-03 18:21:24****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING :
 1. SECTION (FBC 107.2.1) PAGE A-1.1, GENERAL DESIGN,
 ?BROWARD COUNTY AMENDMENTS? NEEDS TO BE REMOVED FROM
 PLAN IN ADDITION TO ALL OF THE NON-RELATED GENERAL
 NOTES.
 2. SECTION (FBC 1609.4.3) PAGE A-1.1, GENERAL DESIGN
 CRITERIA, WIND EXPOSURE CATEGORY ?C? SHOULD BE CATEGORY
 ?D?.
 3. SECTION (FBC 310.4 & FBC 107.2.1) PAGE A-2.1,
 EXISTING BUILDING INFORMATION SHOWS AN ?R-3? OCCUPANCY
 THAT SHOULD BE AN ?R-2? OCCUPANCY AND THE WORD
 (RESTORATION) LEVEL 2 SHOULD BE CHANGED TO (ALTERATION)
 LEVEL 2.
 4. SECTIONS: (FEB 801.2 & FEB 707.4), (FBC 1609 & FBC
 107.2.1) PAGE A-2.1 EXTERIOR DOOR PRESSURES NEED TO BE
 SHOWN ON PLAN AND IN A SUBMITTED PRODUCT APPROVAL.
 5. SECTIONS: (FBC 107.2.1), (F.S. 481.221), (FAC RULE
 61G1-16.001) ALL PAGES, ARCHITECT?S REGISTRATION NUMBER
 AND SEAL ARE NOT CLEAR.
  