2018-10-05 11:59:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090395
 10/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 DUCTLESS AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 2) M-1: PROVIDE A CHECK VALVE ON THE CONDENSATE LINE OF
 THE FAN COIL UNIT- SECTION 307.2.4.1 FBC M.
  
 3) M-1: INDICATE THE SIZE AND METAL GAUGE OF THE
 CONDENSER STRAPS SHOWN IN THE MOUNTING DETAIL- SECTION
 107.2.1 WPB.
  
 4) M-1: INDICATE HOW THE CU WILL PROTECTED AGAINST
 VEHICULAR IMPACT- SECTION 303.4 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  