2018-10-08 10:51:26****CORRECTIONS****
 W.P.B. PERMIT: 18090364
 REVIEWED: OCTOBER 8, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.5]PROVIDE ENGINEERING FOR ENHANCED
 NAILING AS STATED IN PRODUCT APPROVAL UNDER GENERAL
 LIMITATIONS #5.7
  
 2. [FBC 107.2.5]PROVIDE PAGES 1-6 OF PRODUCT EVALUATION
 TO STATE LIMITATIONS.
  
 3. [FBC 107.2.5]PROVIDE LAYOUT TO SHOW STRUCTURES ON
 SITE AND THE LOCATION OF ROOF BEING REPLACED. INCLUDE
 ROOF PITCH, HEIGHT AND DIMENSIONS. PAGE 2 OF LAYOUT
 SHOWS PEEL AND STICK. PLEASE UPDATE TO MATCH ROOF
 SYSTEM BEING INSTALLED. YOU CAN USE THE BUILDING LAYOUT
 FROM PROPERTY APPRAISERS FOR YOUR LAYOUT TO SHOW THE
 LOCATION OF ROOF BEING REPLACED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  