2018-10-08 10:51:26 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18090364 |
| REVIEWED: OCTOBER 8, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. [FBC 107.2.5]PROVIDE ENGINEERING FOR ENHANCED |
| NAILING AS STATED IN PRODUCT APPROVAL UNDER GENERAL |
| LIMITATIONS #5.7 |
| |
| 2. [FBC 107.2.5]PROVIDE PAGES 1-6 OF PRODUCT EVALUATION |
| TO STATE LIMITATIONS. |
| |
| 3. [FBC 107.2.5]PROVIDE LAYOUT TO SHOW STRUCTURES ON |
| SITE AND THE LOCATION OF ROOF BEING REPLACED. INCLUDE |
| ROOF PITCH, HEIGHT AND DIMENSIONS. PAGE 2 OF LAYOUT |
| SHOWS PEEL AND STICK. PLEASE UPDATE TO MATCH ROOF |
| SYSTEM BEING INSTALLED. YOU CAN USE THE BUILDING LAYOUT |
| FROM PROPERTY APPRAISERS FOR YOUR LAYOUT TO SHOW THE |
| LOCATION OF ROOF BEING REPLACED. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |