2018-09-14 11:17:51PERMIT # 18090360
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO: THE FOLLOWING ITEMS WILL BE REVIEWED
 AT TIME OF FIELD INSPECTION. FAILURE TO COMPLY WITH ALL
 FIRE CODE REQUIREMENTS WILL RESULT IN A FAILED
 INSPECTION UNTIL COMPLIANCE IS MET.
  
 1) SHEET G.002: NORTH EXIT STATES - 3.6" WIDTH REQUIRED
 / 36" WIDTH PROVIDED ---- REMOVE DECIMAL TO CORRECT
 NUMBER
  
 2) SHEET G.002: WEST EXIT STATES - 87.60" WIDTH
 REQUIRED / 52" WIDTH PROVIDED -----PLEASE CORRECT OR
 EXPLAIN DISCREPANCY IN REQUIREMENT.
  
 3) PER NFPA 1: 13.3.2.6* EXTERIOR ROOFS, CANOPIES,
 PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR
 PROJECTIONS. IN BUILDINGS PROTECTED THROUGHOUT BY
 AUTOMATIC SPRINKLERS IN ACCORDANCE WITH
 NFPA 13, AUTOMATIC SPRINKLER PROTECTION SHALL BE
 PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE WITH
 13.3.2.6.
 13.3.2.6.1: UNLESS THE REQUIREMENTS OF 13.3.2.6.2,
 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE
 INSTALLED UNDER EXTERIOR PROJECTIONS EXCEEDING 4 FT
 (1.2 M) IN WIDTH. [13:8.15.7.1]
 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH
 MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE,
 OR FIRE RETARDANT?
 TREATED WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE
 RETARDANT?TREATED WOOD AND FIRE-RETARDANT COATINGS FOR
 BUILDING MATERIALS. [13:8.15.7.2]
  
  