2018-09-13 10:19:49RESIDENTIAL (R2) SHUTTERS, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED.
  
 2- THE DESIGN PRESSURES FOR OPENING #3 NEED TO BE
 REVISED. THIS OPENING IS LOCATED IN END ZONE 5 NOT
 INTERIOR ZONE 4. SEC. 1609.6.4.3 FBC.
  
  